8
Storage
Temperature
-25
℃~
55
℃
Humidity
20%
~
90%
(Non condensing)
Altitude
<1000m
High altitude area load=rated power × derating coefficient (corresponding
to altitude)
Altitude(m)
1000
1500
2000
2500
3000
3500
4000
4500
5000
Derating
coefficient
100%
95%
91%
86%
82%
78%
74%
70%
67%
Note: if the UPS is installed or used in the place where the altitude is
above than 1000m, the output power must be derated in using, please
refer to the above table.
2. Installation
Dangerous: For safety, please cut off the mains power switch before
installation, the battery breaker also need to be cut off if it is a long backup
time model (“L” model)
Note: 1. Installation and wiring must be performed in accordance with
the local electric code and the following instructions by professional
people.
2. Suggest installing on ground directly.
2.1 Unpacking Inspection
1. Inspect the appearance of the UPS to see if there is any damage
during transportation. Do not turn on the unit and notify the carrier
and dealer immediately if there is any damage or lacking of some
parts.
2. Unpack the packaging and check the package contents. The
shipping package contains:
A UPS
A user manual
Ten connection terminals
Summary of Contents for EX series
Page 1: ...EX SERIES EX6K L EX10K L EX3110K L EX3115K L EX3120K L USER MANUAL...
Page 8: ...4 1 2 Front View 1 3 Rear View EX6KL EX10KL EX6K EX10K EX3110KL EX3115KL EX3120KL EX10K EX6K...
Page 9: ...5 EX6KL EX10KL EX3110KL EX3115KL EX3120KL...
Page 20: ...16...
Page 21: ...17...
Page 25: ...21...
Page 33: ...29 4 2 Operate mode 1 AC mode AC Mode 2 Battery Mode Battery Mode...
Page 34: ...30 3 Standby Mode Standby Mode 4 Bypass Mode Bypass Mode...