Pelletherm V.4 LT 

 

 

 

 

 

 

 

 

 

40 

 

6.9. 

SAFETY AND UNPREDICTED RISKS. 

 
RISKS FROM USAGE OF THE SYSTEM. 
 

The modules of the system – a hot water pellet boiler from series “Pelletherm V.4 LT” and an 
automated  pellet  burner  from  series  “GP  xx  sc”  are  designed  and  manufactured  in 
compliance  with  the  main  safety  requirements  of  the  acting  European  standards  and 
provisions. Dangerous conditions might occur in the following situations:  

  The hot water pellet boiler from series “Pelletherm V.4 LT” has been used incorrectly;  
  The automated pellet burner from series “GP xx sc” has been used incorrectly;  
  The system has been installed by unqualified staff;  
  The guides for safe usage, presented in this manual book, have not been observed;  
  The  guides  for  safe  usage  of  the  automated  pellet  burner,  presented  in  its  manual 

book, have not been observed. 

 

UNPREDICTED RISKS. 

 
The  modules  of the  system  (hot  water  pellet  boiler from  series  “Pelletherm  V.4  LT”  and  an 
automated  pellet  burner  from  series  “GP  xx  sc”)  are  designed  and  manufactured  in 
compliance  with  the  acting  safety  standards.  Although  all  possible  risky  situations  are 
preliminary considered, resulting from incorrect operation, the following might occur:  

  Risks  from  burning,  caused  by  high  temperatures  from  the  burning  process  in  the 

combustion chamber and/or by access to its door. Also by access to the covers of the 
combustion  and  the  convection  chambers,  as  well  as  during  cleaning  of  the  ash 
residues in the burner’s zone or by incompletely burned fuel in the ash  container of 
the hot water pellet boiler; 

  Risks  from  electrical  shock  by  indirect  contact.  The  boiler  and  the  burner  are 

connected to the power supply network and the control modules are positioned in the 
interface  panel  of  the  boiler  and  in  the  burner’s  controller,  all  equipped  with  the 
necessary  components  for  overload  and  short  circuit  protection.  The  ground 
connection  of  all  modules  connected  to  the  electrical  network  are  mandatory  and 
must be performed by an authorized technician;  

  Risk from fingers injuries during opening or closing and cleaning. It is recommended 

to use proper individual protection equipment;  

  Risk  from  strangulation  in  case  of  insufficient  chimney  draught,  clogging  of  the 

boiler’s  flue  tract  or  improper  sealing  of  its  cover  panels,  doors  and  others,  through 
which the flue gasses, separated by the operating burner, could flow out.  

 

6.10.  COMPLETION OF THE APPLIANCE WARRANTY CARD. 

 

The attached WARRANTY CARD must be completed by filling the required 
information in its fields, as the signature and stamp fields must be  
completed too, in order to ensure the WARRANTY CARD VALIDITY of the  
hot water pellet boiler from series “Pelletherm V.4 LT” and of the automated  
pellet burner from series “GP xx sc”.  

 

The automated pellet burner from series “GP xx sc” is delivered with its own  
warranty card, which also has to be fully completed.  
 

 
6.11.  ACTIONS AFTER EXPIRATION OF THE SYSTEM’S LIFE CYCLE. 

 
After  expiry  of  the  system’s  modules  life  cycle,  their  termination  must  be  environmentally 
friendly and protective. For that purpose the system has to be disassembled, its modules and 
components  have  to  be  delivered  to  waste  disposal  offices,  by  observing  the  principles  for 
separate collection of wastes.   

Summary of Contents for GP ** sc

Page 1: ...1 MANUAL FOR INSTALLATION OPERATION AND MAINTENANCE OF A SYSTEM CONSISTING OF A HOT WATER PELLET BOILER FROM SERIES PELLETHERM V 4 LT AND AN AUTOMATED PELLET BURNER FROM SERIES GP xx sc http www green...

Page 2: ...ture company thanks you for your choice The manufacture company submits this manual to help the team that will install adjust and service the system hot water pellet boiler and pellet burner as well a...

Page 3: ...G SECTION COVER CAP 25 5 4 6 INSTALLATION OF THE COVER FLAP IN FRONT OF THE FLUE GAS OUTLET 25 5 4 7 INSTALLATION OF THE BOILER S HORIZONTAL COVER PANELS 27 5 4 8 INSTALLATION OF THE COVER OVER THE BO...

Page 4: ...from series GP xx sc All legal provisions regarding safety All legal provisions regarding environment protection Provisions regarding installation start and adjustment All harmonized provisions of th...

Page 5: ...y the boiler s body heat exchanging surfaces and is then transferred to the heat carrier filled in the system The hot water boiler s delivery kit from series Pelletherm V 4 LT includes Heat exchanger...

Page 6: ...trical which ensures its usage in systems with programmable room thermostat Automatic system operation availability to regulate it through room thermostat weekly programmer guaranteeing maximum heat c...

Page 7: ...hot water boiler s part is the boiler body heat exchanger unit as the automated pellet burner from series GP xx sc is mounted on its side The heat exchanger is offered in 2 variants the so called lef...

Page 8: ...e has been overheated resulting from emergency situations Photo sensor for dynamic control of the burning process System for modulation of the firing air flow rate during the process of initial fuel i...

Page 9: ...Energy efficiency class according to regulation U 2015 1187 Efficiency at nominal heating output mode 92 92 92 CO emissions in the flue gases 0 C 1013 mbar at 10 2 mg m3 163 0 Dust emissions in the fl...

Page 10: ...let burner model GP 20_18 sc GP 25 sc GP 32 sc Boiler weight kg 342 342 362 Boiler water volume l 50 50 60 System overall dimensions B 546 1080 780 1250 546 546 546 W 1080 1080 1080 D 780 780 780 H 12...

Page 11: ...d fuel cogeneration boiler no Combination boiler no Fuel Preferred fuel only one Other suitable fuel s Log wood moisture content 25 no no Chipped wood moisture content 15 35 no no Chipped wood moistur...

Page 12: ...fficiency Auxiliary electricity consumption At rated heat output el n At rated heat output elmax 0 156 kW At 30 50 of rated heat output if applicable elmin 0 134 kW Of incorporated secondary emission...

Page 13: ...moisture content 15 35 no no Chipped wood moisture content 35 no no Compressed wood in the form of pellets or briquettes yes no Sawdust moisture content 50 no no Other woody biomass no no Non woody b...

Page 14: ...fficiency Auxiliary electricity consumption At rated heat output el n At rated heat output elmax 0 156 kW At 30 50 of rated heat output if applicable elmin 0 134 kW Of incorporated secondary emission...

Page 15: ...moisture content 15 35 no no Chipped wood moisture content 35 no no Compressed wood in the form of pellets or briquettes yes no Sawdust moisture content 50 no no Other woody biomass no no Non woody b...

Page 16: ...output if applicable elmin 0 134 kW Of incorporated secondary emission abatement equipment if applicable In standby mode PSB 0 013 kW Contact details Ekoterm Proekt EAD ZMM Haskovo AD 6300 Haskovo 67...

Page 17: ...erm V 4 LT 17 Figure 4 2 System overall sizes front view Figure 4 3 Overall and connection sizes dimensions of a hot water pellet boiler from series Pelletherm V 4 LT pellet burner mounting flange sid...

Page 18: ...Pelletherm V 4 LT 18 Figure 4 4 Overall and connection sizes dimensions of the system rear view Figure 4 5 Overall and connection sizes dimensions of the system top view...

Page 19: ...oiler from series Pelletherm V 4 LT and a pellet burner from series GP xx sc Boiler s convections tract cover Boiler s combustion chamber cover Boiler s combustion chamber cover panel Pellet burner mo...

Page 20: ...cording to standard EN ISO 17225 2 2014 is presented in the automated pellet burner from series GP xx sc manual book Ash container Boiler s combustion chamber door Boiler s combustion chamber First pa...

Page 21: ...et burner from series GP xx sc depends on The adjusted operational heating output of the burner The contamination level on the boiler s heat exchanging surfaces The sealing level of the boiler combust...

Page 22: ...nt of the boiler must be at least 1000 mm The minimum allowed distance between the boiler s rear side and a wall must be at least 400 mm The minimum distance between the boiler side where the pellet b...

Page 23: ...nnect the hot water pellet boiler from series Pelletherm V 4 LT to the heating installation by using proper fittings and accessories to be performed in accordance to the preliminary prepared technical...

Page 24: ...ing of the pellet burner After the burner has been mounted the connection screws must be tightened equally in order to ensure proper sealing between the flange and the boiler body Figure 5 3 View of m...

Page 25: ...F THE ASH CLEANING SECTION COVER CAP Figure 5 5 The cover cap for cleaning of the ash residues positioned after the second flue pass of a hot water boiler from series Pelletherm V 4 LT is properly pos...

Page 26: ...rmal loads therefore it symmetrically manufactured It is recommended to turn the cover flap on every two to three weeks of operation Figure 5 6 The directing cover flap is dismounted and the boiler s...

Page 27: ...letherm V 4 LT 5 4 8 INSTALLATION OF THE COVER OVER THE BOILER S CONVECTION TRACT This cover is equipped with protection element made of stainless steel Figure 5 9 Directing cover over the boiler s co...

Page 28: ...l There are connectors to power supply to burner and to room thermostat Depending on whether it is with left or right burner mounting the connectors are positioned on the same boiler cover side as the...

Page 29: ...to change the system construction without engagement to inform the end users 5 4 13 CONNECTING THE SYSTEM TO THE POWER SUPPLY Connecting the system consisting of a hot water pellet boiler from series...

Page 30: ...ay mixing valve 10 Circulations pump 2 The exemplar hydraulic scheme is only informative and can not be practically used as implemented hydraulic scheme The installation and warm tests completion of t...

Page 31: ...When initiating the system to operation consisting of a hot water pellet boiler from series Pelletherm V 4 LT and a pellet burner from series GP xx sc the following main requirements must be observed...

Page 32: ...rheating It is factory adjusted to stop the automated pellet burner from series GP xx sc power supply in case the circulation water temperature exceeds the limit adjusted in the factory to 95 o C Swit...

Page 33: ...Description of the electrical connectors installed on the boiler s interface panel Room thermostat connector Switch START Communication connector Pellet burner connector Emergency thermostat Switch PO...

Page 34: ...and also to check the chimney condition The same effect might occur during the transition seasons autumn and spring when the natural chimney draught is decreased due to high ambient temperatures If th...

Page 35: ...ON the button POWER but only after the failure reason has been eliminated The ash content does not change significantly the fuel s calorific value but requires special construction of the burner in or...

Page 36: ...n be performed by decreasing the burner s heating output level For detailed information see the burner s manual book Do not decrease the burner s heating output below the system s minimum output becau...

Page 37: ...ted in its manual book In case the system operation is stopped a complete cleaning from the ash residues over the boiler s heat exchanging surfaces must be performed because the ash has corrosive infl...

Page 38: ...ompany that services and maintains the system 6 8 USER INTRODUCTION TO THE PROCEDURES FOR MAINTENANCE AND ADJUSTMENTS OF THE SYSTEM It is necessary that the user is completely introduced with the pres...

Page 39: ...e boiler s bottom gather the ash residues in fire proof or another proper container after that in reverse order mount the ash container back and close the door mount the other cover panels of the boil...

Page 40: ...the hot water pellet boiler Risks from electrical shock by indirect contact The boiler and the burner are connected to the power supply network and the control modules are positioned in the interface...

Page 41: ...ut It is necessary to adjust the burner s heating output level High temperature assignment by the room thermostat if connected It is necessary to decrease the room thermostat temperature assignment 3...

Page 42: ...er the combustion chamber surfaces inside the boiler Low temperature of the inlet water Adjust the circulations pump thermostat The recommended circulations water operational temperature is at least 6...

Page 43: ...using a room thermostat Use the room thermostat socket only Do not supply external voltage Remove the bridge connection when using a room thermostat Use the room thermostat socket only Do not supply e...

Page 44: ...Pelletherm V 4 LT 44 Figure 8 1 Control panel wiring diagram of a hot water pellet boiler from series Pelletherm V 4 LT co operating as a system together with a pellet burner from series GP xx sc...

Page 45: ...Pelletherm V 4 LT 45 Figure 8 2 Wiring diagram of the boiler s connector panel used to connect the pellet burner...

Page 46: ...Pelletherm V 4 LT 46...

Page 47: ...dical maintenance presented in the present manual book are not observed Attempts to recover any defects performed by the buyer or by other unauthorized persons Changes in the system s appliances const...

Page 48: ...Pelletherm V 4 LT 48...

Reviews: