8. WIRING DIAGRAM OF A BOILER FROM SERIES “PELLETHERM V.4 LT” IN
COMBINATION WITH A PELLET BURNER FROM SERIES “GP XX SC”.
The control panel wiring diagram of a hot water boiler from series “Pelletherm V.4 LT”,
operating in combination with pellet burner from series “GP x sc”, is presented on Figure 8.1.
The connectors CONN1 – CONN3 and the NTC sensor are installed in
the boiler.
TD – Thermo-disc (installed on the pellet burner inlet feeding pipe) -95
0
C.
Remove the bridge connection in CONN2, if using a room thermostat!
Use the room thermostat socket only. Do not supply external voltage!
Remove the bridge connection when using a room thermostat!
Use the room thermostat socket only. Do not supply external voltage!
See the wiring diagram!
Figure 8.2 presents the wiring diagram to connect a pellet burner from series “GP xx sc” to
the connector panel of the boiler from series “Pelletherm V.4 LT”, positioned on its rear side.
The wiring diagram of an automated pellet burner from series “GP xx sc” is
presented in its manual book.
Putting NTC sensor is required in the cartridge located in pipe hot water outlet
with a clamp.
This is an operation related to safety and should be performed by a trained
person!!