Pelletherm V.2 M01 23
5.2.2. SETTING UP BOILER "PELLETHERM V.2 M01".
When installing the boiler for easy manipulation it is necessary to pay attention to the
following (Figure 5.1):
Minimum space for manipulation in front of the boiler must be 1000 mm;
Minimum permissible distance between the rear of the boiler and wall should not be
less than 350 mm;
Minimum distance on the right side of the equipment (on the side of fuel bunker) and
wall should be 500 mm, in order to ensure free access to the feed screw and the
other modules of the equipment located in this compartment;
Minimum distance on the left side of the boiler shall be 450 mm, to provide lateral
access to the boiler in cleaning its ash and servicing the smoke suction fan;
Minimum distance of the free space above the boiler must be at least 1000 mm, in
order to provide easy access to the bunker for charging with fuel, and also cleaning
the heat exchanger from the accumulated ash.
Figure 5.1. Location of boiler "Pelletherm V.2 M01" in a boiler room.
Setting up of the boiler is done according to the requirements fot connection to
the electric net - the equipment is set up so as to ensure free access to the
plug box (230VAC/50Hz).
Completion of the installation and implementation of hot tests of the boiler are
recorded in the report for commissioning and adjustment where mandatory
the fields are filled in with the necessary information.
5.2.3. SETTING UP THE BOILER IN COMPLIANCE WITH THE REQUIREMENTS FOR
CONNECTION TO THE ELECTRIC NET.
The system is setting up so as to ensure free access to the plug box (230VAC/50Hz).
Connecting the hot-water boiler of series "Pelletherm V.2 M01" is made through the power
cord supplied.