After the ash cleaning procedure has been finished, the elements (turbulizers,
flue duct lids) are installed and tightened in a reverse manner;
5.8.
Showing and teaching the end user about the maintenance and
adjustment procedures of the boiler
It is necessary to show and teach the end user the maintenance procedures for
operating the boiler efficiently and keep its reliability in high degree order. Also
the installer should demonstrate and teach the end user how to change the
operative parameters of the control board of the boiler in order to operate the
unit, according to the local heat consumption:
The end user should be introduced with the following:
•
this instruction manual;
•
the operation of the boiler;
•
the method for adjustment of the thermal capacity and the operation
mode control of the boiler;
•
the procedure for boiler’s maintenance:
•
the procedure for ash cleaning from the combustion chamber of the
boiler;
•
the procedure for cleaning the ash residue of the convective duct of
the boiler;
•
the procedure for charging the fuel hopper with wood logs – the
logs are arranged in the fuel hopper in the chamber, in order to allow
easy flow rate of volatile flue gases to the burner’s nozzle of the boiler.
It is strongly required to utilize chopped wood logs, which have
moisture content, according to the requirements for the fuel.;
•
ignition procedure – the ignition process is described in details in
5.3.3;
•
procedure for ash cleaning – the end user should clean the deposited
ash on the combustion chamber surfaces, as well as the ash, deposited
on the other surfaces of the boiler. The detailed description is shown in
5.7;
•
cleaning the ash as well as other residues from the turbine of the
flue gases fan – it is highly recommended to perform regular ash
cleaning. It is required to stop the boiler and clean the turbine in case