VPLCE532E Vision Motion Controller User Manual V1.5
→
Terminal Definition
Terminal
Name
Function
485B
485 differential data B / -
485A
485 differential data A / +
EGND
Communication public end
CANL
CAN differential data L / -
CANH
CAN differential data H / +
3.2.1.
RS485, CAN Communication Specification & Wiring
RS485 serial port supports MODBUS_RTU protocol and custom communication,
which contains 485A, 485B and public end.
The CAN interface of the controller adopts the standard CAN communication
protocol, which mainly includes three ports, CANL, CANH and the public end. And it can
connect to CAN expansion modules and other standard CAN devices.
→
Specification
Item
RS485 (port 1)
CAN
Maximum Communication Rate
(bps)
115200
500K
Terminal Resistor
No
120Ω
Topological Structure
Daisy Chain Topology
Daisy Chain Topology
The number of nodes can be
extended
Up to 127
Up to 16
Communication Distance
The longer communication distance is, the lower
communication rate is, and maximum of 100m is
recommended.
Note: for CAN communication, the baud rate only supports 500K.