Wiring Note:
⚫
The wiring principle of high-speed digital output OUT (0-7) and low-speed digital
output OUT (8-15) is shown in the figure above. The external signal receiving end can
be an optocoupler or a relay or solenoid valve, all can be connected as long as the
input current does not exceed 300mA.
⚫
For the connection of the public end, please connect the "EGND" port on the IO power
supply to the negative pole of the DC power supply of the external input device. If the
DC power supply of the external device and the controller power supply are in the
same power supply system, this connection can also be omitted.
⚫
The E5V port is a 5V power output port, which can be used when some loads need to
provide an external 5V power input, the maximum current is 300mA.
3.5.2.
Basic Usage Method
(1)
Please follow the above wiring instructions to wiring correctly.
(2)
After powered on, please use any one interface among the three interfaces ETHERNET,
RS232 and RS485 to connect to ZDevelop.
(3)
Open or close output port
directly through “
OP
” command, also, it can be
opened or
closed
through “ZDevelop/View/
Op
”. Please refer to “ZBasic” for details.