ZMC416BE Motion Controller User Manual V1.5
Topology
Daisy chain connection structure
Point to point
Nodes can be
extended
Up to 127
Up to 16
Up to 10
Communication
Distance
Longer communication distance, lower communication rate,
max 100m is recommended.
→
Wiring Reference
Connect 485A and 485B of RS485 to 485A and 485B of the controller correspondingly,
and connect the common terminal EGND of both parties of RS485 communication
together.
Connect the CANL and CANH of the standard CAN module to the CANL and CANH of
the other side correspondingly. And public ends of the CAN bus communication both
parties are connected together. In CAN bus left and right sides, connect a 120
Ω
resistor
respectively (please see below graphic).