10
Starting up and stopping the appliance
Press
for 5 seconds.
Locking/unlocking the keyboard
To lock and unlock the keyboard:
- Hygro Control must be
active,
- press
and
simultaneously for 3 seconds,
- the
message is displayed or is removed.
Adjusting the reference values
- Hygro Control must be
active,
- press
for 3 seconds, the modifiable value blinks,
- use
or
to set the value,
- press
to validate,
- and then
to exit.
Value range
minimum
maximum
Comfort setting
Humidity
55% 70%
65%
Temperature
5 °C
32 °C
28°C
Test mode / Manual override
To force the appliance to operate for 30 minutes, even if the pool hall conditions do not trigger the
request:
- Hygro Control must be
active,
- press on
for 3 seconds, a value blinks,
- press
again for 10 seconds,
- all the digits light
,
or
and the appliance starts up.
Parameter setting in hygro-thermostat or hygrostat mode
- Hygro Control must be
on standby,
- press
and
for 3 seconds :
(hygro-thermostat mode),
- press
or
to select the function:
(hygrostat mode),
(thermostat mode)
- validate by pressing
.
Hygro Control shipped with the setting for hygro-thermostat mode for appliances with the
heating option for hygrostat mode for devices without the heating option.
This setting must be changed if a heating option is added or removed.
To quit this mode, press the
button for 5 seconds.
If the keyboard is not used for 30 seconds, the setting will be abandoned and the last
(non validated) setting will not be taken into account.
EN
Summary of Contents for CAE
Page 22: ...1 Sch ma lectrique Sch ma de puissance CAE 508 510 513...
Page 23: ...2 Sch ma de commande CAE 508 510 513...
Page 25: ...4 Dimensions weight without option Kg CAE 508 228 CAE 510 235 CAE 513 240...
Page 26: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...
Page 27: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...