14
a post-ventilation runs for 3 minutes when the reference temperature is reduced on the thermostat
located in the pool hall (with the “VI/VP” switch on “VI”, without any dehumidification or defrosting
cycles in progress): check that the circulator stops.
1.4.5.3 Titanium water condenser
connect the intake and output to the filter using a by-pass, according to
the markings on the appliance (before the pool water treatment system),
see §1.3.8.2,
Adjusting the by-pass for the water condenser
:
- open valve
half way
- open valves
and
completely
plan to shunt the filter clock from the S-S terminals on the CAE electrical terminal board,
in the case of a hydraulic connection with pump that is independent of the filtering system, plan to
power this pump using the P-P terminals on the CAE terminal board (maximum power: 60W with
230V AC, otherwise relay the power supply from an extra electric contactor),
starting up:
- follow the procedure describe in §1.4.2,
- set the “TH” digital display thermostat fitted inside the electrical box:
- press “SET”
to display the current reference value (factory preset at
27°C, thus the thermostat output will be activated when the pool room
temperature will rises above 29°C and deactivated if the temperature
drops below 27°C): the “
out 1
” LED blinks (hysteresis = 2°C),
- press
or
(possible range values: 25°C minimum and 45°C
maximum),
- press “SET”,
or do not operate for 15 seconds, to confirm.
check that the filter pump starts when the adjustment of this digital display
thermostat is reduced to below the surrounding temperature.
check that the « VCA » indicator lights when the thermostat reference value
is lowered. By default, check that the filter pump is operational and sufficiently irrigates the water
condenser (see by-pass adjustment).
when the water condenser option is operational (VCA indicator on), check that the « EV » solenoid
valve is powered from terminals E and V (230V ac) on the appliance terminal board.
If this is not the case adjust the by-pass so that there is a sufficient flow of water in the condenser to
activate the flow controller fitted at the output of the water condenser (this safety device is connected
between terminals I and D, see the electric wiring diagram in the appendix).
Warning - low temperature: if the dehumidifier hot water battery is not supplied by a
boiler, but by an aero-thermal or a geothermal system, the heating circuit water will be at
a maximum temperature of 45-40°C. The power of the battery will then be considerably
lower (3 to 4 times less) than the nominal power given for water at 90-70°C. If the power
of the battery is lower than the heating needs of the room, plan for additional heating by
radiator, heated floor or fan convector.
EN
Summary of Contents for CAE
Page 22: ...1 Sch ma lectrique Sch ma de puissance CAE 508 510 513...
Page 23: ...2 Sch ma de commande CAE 508 510 513...
Page 25: ...4 Dimensions weight without option Kg CAE 508 228 CAE 510 235 CAE 513 240...
Page 26: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...
Page 27: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...