16
Led lit continuously Meaning
“défaut hors
température”
= temperature range
fault
-
temperature < than 10°C or > than 40°C (compressor stopped),
-
restart sensor is out of order.
-
In all cases, if the ventilator is active before the triggering of this fault, it is
maintained for 3 minutes before stopping.
-
If the returns to within its operating range:
-
there is a 30 seconds delay before the fault is cleared,
-
there is a 3 minute delay before restarting the compressor and the fan (if a
dehumidification request is still active)
“cycle de dégivrage”
= defrosting cycle
-
cooling circuit temperature < than -5°C or > than 40°C,
-
a defrosting cycle is in progress (temperature is >-5°C). The compressor is
stopped and ventilation is maintained,
-
the defrosting sensor is out of order.
The defrosting cycle stops when the temperature of the sensor goes over
2.2°C. If the sensor is out of range (<-5°C or >40°C) during the active
defrosting cycle, this LED remains on for 3 minutes with the ventilation
operating, before it stops.
In all cases, if the ventilator is active before the triggering of this fault,
ventilation is maintained for 3 minutes before stopping.
If the sensor returns within its operating range:
-
there is a delay of 30 seconds before the fault is cleared,
-
there is a 3 minute delay before the compressor and fan restart (if a
dehumidification request is still active)
Others
Description
“VI/VP switch”
“intermittent ventilation” (standard setting)
or “permanent ventilation” (to permanently circulate the pool hall air)
Using VI, a post-ventilation is active for 3 minutes.
The ventilation is active when:
- dehumidification is triggered,
- a defrosting cycle is started,
- pool hall air heating is triggered,
-
active for at least 5 minutes in one hour without any of these
triggers.
On VP, the compressor starts after a delay of 3 minutes.
“Connecteur module
de prog.”
= programming
module connector
ECP 600 programming connector or implementation of a diagnosis module
by the technical support department
ECP 600 250Vac T=10A 6,3x32 fuse
2.2 Troubleshooting procedures
Checks to make before any operation:
- correct electrical supply (voltage and cable size)
- all cables are correctly connected
- Hygro Control operational
- appliance has triggered dehumidification but not heating
See faults
table
§2.1
The appliance does not work.
No fault displayed on the
ECP 600, green light on
The compressor is working
but not the ventilation
No LED lit on ECP
600
Display of a fault on
ECP 600
The ventilation is working
but not the compressor
EN
Summary of Contents for CAE
Page 22: ...1 Sch ma lectrique Sch ma de puissance CAE 508 510 513...
Page 23: ...2 Sch ma de commande CAE 508 510 513...
Page 25: ...4 Dimensions weight without option Kg CAE 508 228 CAE 510 235 CAE 513 240...
Page 26: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...
Page 27: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...