17
Voltage between terminals 30-31 on
ECP 600 is 230V AC
No LED lit on ECP 600
yes
no
Test fuses F1 and F2,
and the power supply
The voltage between terminals 4-5
on the ECP 600 is 12 V ac?
Replace the ECP 600
no
yes
Check the Hygro Control and its wiring
yes
Shunt terminals 1, 5 and 7,
does the appliance start?
no
no
Replace C1
The compressor is working
but not the ventilation
Voltage between terminals 22-
23 on ECP 600?
yes
Capacitor C1?
no
Connection between
the ventilator and the
ECP 600?
Replace the
ECP 600
yes
yes
Replace the
ventilator motor
Re-connect
no