1.3 Installation
1.3.1 Electrical regulations for swimming pools
Refer to the current regulations in force in your country.
French standard C15.100 Section 702 - U.T.E:
In volumes 0 and 1, only protection using Very Low Voltage (article 411.1) with a nominal voltage not
exceeding 12 V AC or 30V DC is allowed. The protection must be installed outside volumes 0, 1 and 2
(the appliance has a protection index of at least IP X5).
In volume 2 (see figures 702A and 702B), the appliances must be:
- either class II for lighting,
- or class I protected by a 30 mA or less ground fault circuit breaker,
- or powered by a separation transformer in compliance to paragraph 413.5.1
The appliance has a protection index of at least IP X2.
h: unknown variable
V: volume
Figure 702 B:
dimensions of volumes for
above-ground pools
Figure 702 A:
volume sizes for in-ground
pools and foot baths
EN