6
1.3.3.2 Appliance fixed to the wall
Using the two anchoring points at the back of the appliance in a “solid wall” (see emplacement and
dimensions in the appendix - fixing elements not supplied). Make sure that the 2 anti-vibration rubber
parts are fitted on the bottom corners.
1.3.4 Connection of the condensation drain
- fit a drain pipe of appropriate size and length on the original outlet pipe (Ø16 outer diam.)
- allow a sufficient slope to ensure a proper flow for the drained water,
- connect the extremity of the pipe to a water evacuation drain with U-bend,
- ensure that the pipe is not bent or angled, and that the extremity of the pipe is not immersed.
The outlet is located on the right side of the device when viewed from the front (see marker "AØ16" §
"Dimensions" in the appendix). This outlet can be moved to the left side (access via the rear panel).
1.3.5 Electrical connections
1.3.5.1 Voltage and protection
The electrical supply must be provided through a protection and circuit breaking device (not
supplied) complying with the standards and regulations in force in the country where it is installed (in
France standard NF C 15100).
use the supply cable delivered with the appliance: 2 poles + Earth 10/16 A in 3G1.5 (section
1.5mm²),
Extension cords and adapters must NOT be used.
An adequately protected electrical socket
must be installed close to the device by a qualified technician,
Electrical protection: 30 mA ground fault circuit breaker (at the head of the line),
The appliance must be earthed.
Risk of electrical shock inside the device. Only a qualified and experienced
technician must install the device cables.
If the power cable is damaged it must be replaced by a qualified technician or by a
Zodiac Pool Care Europe service station.
Electric cables must be fixed.
Prior to any operation, check that:
-
the voltage on the identification plate of the appliance corresponds to the mains
voltage available on site.
-
the socket and the power supplied are adapted to the power requirements of the
dehumidifier,
-
the male plug on the power cord is adapted to the socket available.
Pool
* minimum distance
** maximum distance
DT 850
suction grid
blowing grid
fresh air intake
condensation drain with angle pipe
air renewal system (see §1.3.2)
EN