The ventilation is working but not the compressor
yes Sirocco
three-phase
yes
Sirocco
single-phase
EN
yes
Redo the connections
between the contactor
and the compressor
yes
yes
Is the compressor indicator
on the ECP 600 lit?
Set the VI/VP switch
on the ECP 600 to
VI
Voltage between 20-21
on ECP 600? (±230V~)
Replace
ECP 600
no
no
Is the appliance being
ventilated all the time?
Voltage on the
compressor terminals
(±230V~ or ±400V~)?
yes
Replace the
contactor
no
no
Re-connect the Hygro
Control and check that
it is operational
Wait for the
end of the
cycle
Voltage between A1
and A2 on
compressor
contactor (±230V~)?
no
yes
Call a certified ZPCE
station to check the
compressor
no
Is the appliance in a defrost cycle
(indicator lit on ECP 600)?
Re-connect
terminals 20-21 and
A1-A2
Voltage on contactor
power terminals
(±230V~ or
±400V~)?
no
yes
Is the contactor
primed?
yes
no