 2.4 I  Opti on connecti on

2.4.1 "Heati ng priority" opti on (depending on model)

•  

This  functi on  helps  to  keep  the  water  temperature  constant  by  checking  the  water  temperature  at  regular  ti me 

intervals (minimum 5 minute cycle every 220 minutes (modifi able ti me)) by fi ltrati on pump control. The fi ltrati on is 

kept operati ng  while the pool temperature is below the temperature requested.

•  

For the connecti on, connect the fi ltrati on ti mer to terminals 1 and 2 and add a shunt between terminals 3 and 4.

1

2

1- 

2 : power for the fi ltrati on pump power contactor coil

: fi ltrati on ti mer
: power contactor (tripolar or bipolar) for the fi ltrati on system 

pump motor

: separate cable for the "heati ng priority" functi on
: heat pump terminal (see wiring diagram § “5.3 I  Wiring 

diagrams”)

: fuse

•  

Modifi cati on of the ti me between 2 fi ltrati on operati ons (value in number of minutes): 

 - press 

 and 

 or 

 at the same ti me for 3 seconds: 

 appears,

 - press  

 unti l the 

 parameter appears, then press  

 or 

 to change the parameter using 

the  

 and 

 keys.

 -

Once the value has been modifi ed, press  

 or 

 to confi rm, 

 - press 

 to exit the menu.

2.4.2 "Remote control" opti on (depending on model)

•  

This opti on enables the device's user interface to be duplicated to enable the device to be controlled by remote. To 

do so, use the remote control kit available as an accessory.

•  

For the connecti on, consult the manual supplied with the kit.

Summary of Contents for Z200 M2

Page 1: ...H0548500 A 2015 11 Instructions for installation and use English More documents on www zodiac poolcare com Z200 PI20 Power Everpac EN...

Page 2: ...you read this installation and user manual as well as the warnings and warranty booklet delivered with the device Failure to do so may result in material damage or serious or fatal injury and will in...

Page 3: ...h plug except PI2051 with plug except 11M C Joint x2 D Screw in connector x2 E 40 adaptation x2 F 50 reduction x2 G Condensation evacuation kit 15 H Wintering cap x2 I Wintering cover Heating priority...

Page 4: ...3G1 5 3G1 5 3G2 5 3G2 5 Proof pressure bar 6 Service pressure bar 1 5 Head loss mCE 1 1 1 5 1 5 Minimum optimum water ow rate m h 4 6 8 8 Maximum water ow m h 10 Values provided for information purpos...

Page 5: ...connectors Top view of the device with dimensions for attachment to the ground The device must not be installed In a location subject to high winds With the blowing towards a permanent or temporary o...

Page 6: ...installed to make it easier to work on the device water entry valve by pass valve water exit valve water entry adjustment valve optional water exit adjustment valve optional water treatment minimum d...

Page 7: ...device s information plate The electricity supply cable must be insulated against any cutting or hot elements that may damage or crush it The equipment must be connected to an earth socket The electri...

Page 8: ...er power contactor tripolar or bipolar for the ltration system pump motor separate cable for the heating priority function heat pump terminal see wiring diagram 5 3 I Wiring diagrams fuse Modi cation...

Page 9: ...ating range to heat up Cover the basin with a sheet bubble canopy canvas etc to prevent heat loss Take advantage of a period with mild outdoor temperatures on average 10 C at night your heat pump will...

Page 10: ...ulation running Close valve B gradually so that the lter pressure is increased by 150g 0 150 bars Open valves A C and D fully then valve E by half the air which has built up in the heat pump condenser...

Page 11: ...ater is circulating through the heat pump press ashes for 10 seconds then the setpoint temperature is displayed xed 3 4 2 Locking unlocking the keyboard Locking the keyboard Unlocking the keyboard Pre...

Page 12: ...the heat pump 4 2 I Maintenance It is recommended that the device be general serviced at least on a yearly basis to ensure proper operation maintain performance levels and prevent some potential fail...

Page 13: ...mp cannot manage to deice its evaporator it will stop itself this means that the outdoor temperature is too low below 7 C The device is not working If there is no display check the supply voltage and...

Page 14: ...Insu cient water ow Increase ow using by pass check that the pool lter is not clogged Water temperature too high 32 C maximum Wait until the temperature falls Flow controller blocked Check the ow con...

Page 15: ...relay Earth KM4 Complementary relay C1 Compressor condenser M1 Compressor C2 Ventilator condenser M2 Ventilator CD Flow controller SD1 Water temperature sensor E1 High pressure switch SD2 Air temperat...

Page 16: ...49180 St Barth l my d Anjou cedex S A S U au capital de 1 267 140 SIREN 395 068 679 RCS PARIS Votre revendeur Your retailer Mod le appareil Appliance model Num ro de s rie Serial number Trouvez plus d...

Reviews: