Error solution
Steps:
1.
Check whether the inlet voltage of control box is stable, if it’s within the
specified range
of 200V-250V
2.
when standby, enter monitoring interface of operation control box and see what’s the voltage appear in
UDC interface, then run the motor to see how much voltage rise while scram(usually around 410V)[the
inlet voltage multiplied by 1.41 = interface voltage]
3.
if the voltage showed in UDC is wrong, using Isolation transformer with 80V to supply power, then
detect the both ends voltage of + /- control board’s rectifier bridge: inlet voltage multiplied by 1.41; C73
ends impedance: around12.5K; Two terminal voltage (means pin3 to pin4 safety line of U9): around
0.56V
4.
if the voltage showed in UDC is wrong, using Isolation transformer with 80V to supply power, then see
impedance of R143 of main control board: 100
Ω
; C77 Two terminal impedance: around 3.3M; Two
terminal voltage (means pin1 to pin4 safety line of U9): around 0.56V.
5.
[share the maintenance picture with E3]
E4
---Overvoltage when shutdown (the bus voltage is less than 180v for 3s
when shutdown
Summary of Contents for WR580
Page 1: ...WR580 PRODUCT MANUAL V1 0 ...
Page 2: ...Application Model Code Hardware Structure Error Solution Catalogue ...
Page 5: ...Composition of the product ...
Page 9: ...Model description motor Motor model serial number ...
Page 21: ...Function Aging mode Press to enter the aging mode Then press to start press again to stop ...
Page 24: ...External interface definition power 1 2 3 4 Ground wire Power Socket definition L N ...
Page 28: ...Main board PCBA appearance ...
Page 29: ...Control box theory diagram ...
Page 60: ...谢 谢 ...