background image

 

 
 

 

 
 
 
 

 

 

 
 

MINIMUM POSITION SETTING                                                

CHECKOUT

 

The    ZDs    have    a    minimum 
position  setting  that  allows  the 
damper  to  remain  open  to  a  pre- 
set  position instead  of  closing  off 
fully.        This  minimum  position 
provides for a small amount of air 
to  be  by-passed  through  the 
damper  to  lessen  the  need  for  a 
separate  by-pass  damper  and 
provide continual air circulation.

 

 

 

To  set  the  minimum  position,  set  when  there  is  no  power  to  the 
damper and it is  in  the  open position.   Loosen the long minimum 
position  set  screw  and  move  to  a  desired  setting  shown  on  the 
minimum  position  label  and  re-tighten.    When  the  damper  is 
powered closed the minimum position screw will stop the  damper 
at the position set.

 

NOTE:  This label and screw does not indicate the position of 
the damper.  It is only used to set the minimum position.

 

 

The ZD  damper is  a  very simple damper to checkout.   The  two  (2) 
wire spring return design simply requires a check  for voltage at  the 
motor when the damper is to be CLOSED.  There must be 24 Volts 
AC,  at  the  motor  when  the  controller  or  switch  provides  power  to 
the  motor.      When  the  is  no  power  to  the  motor  the  damper  will 
spring return back to its normally open position.

 

REPLACEMENT MOTOR

 

 

To replace the motor, loosen the locking set screw on the inside collar 
ring  of  the  motor  that  holds  the  motor  to  the  damper  blade  shaft, 
remove  the  moved  and replace with the new motor. And re- tighten 
the set screw.

 

 

 
 
 
 