ZONEMASTER MAXIPOINT V2 DAMPER CONTROL SYSTEM
- Installation Manual
20
7.8 Programming On/Off Mode
Programmable on/off time control for each group is an important
feature of the MaxiPoint V 2 system. This system has a 5-1-1 program
capability with three possible program settings; one for weekdays
(Monday to Friday), one for Saturday and one for Sunday respectively.
Each program has 4 programmable events per day: On time 1, Off time
1, On time 2 and Off time 2. Each program event can be enabled/
disabled and their times can be adjusted as desired. All 4 sets of
programs are disabled in the factory default with settings as listed in
the following table.
On time 1
Off time 1
On time 2
Off time 2
Monday to Friday
6.30AM
8.00AM
5.30PM
10.00PM
Saturday
7.30AM
12.30PM
6.00PM
11.30PM
Sunday
7.30AM
12.30PM
6.00PM
11.30PM
NOTE: The Turbo function cannot be programmed.
It is activated manually from the touchpad as needed.
1) Set Clock and Day
a)
Press the button once to enter into
the ‘Function’ Screen.
b)
Use the or button to select the
‘Clock’, and then press button to
enter the sub menu of the clock setting.
c)
Use or button to select hours,
minutes and weekdays. Press or
button to change hours, minutes and
weekdays.
d)
Pressing button can exit the ‘CLOCK’
and ‘FUNCTION; setting mode.
Alternatively, it will return to the sleep
mode itself in 15 seconds if no key is
being pressed.
NOTE: The days displayed at the bottom of
the screen are the days the air conditioning
system has been operating since being
commissioned or last serviced. Adjust the
clock regularly to ensure its accuracy.