SYSTEM CONTROLLER OPERATIONS – DIGI3U

HEAT PUMP OPERATION

The 

DIGI3U

controller, when configured for Heat Pump operation,

allows the use of a standard Heat Pump thermostat  (1 stage cool / 2
stage heat) to be connected to the 

STAT 1

position on the controller.

Emergency Heat control is selected from the Heat Pump thermostat
wired to the 

STAT 1

position. Standard Gas/Electric thermostats are

used for 

STAT 2

and 

STAT 3

positions.

Cool Mode with LAT: 

When a thermostat makes a call for cool, Y, G, and

W-O/B LEDs and outputs to unit are energized. Any non-calling zone
dampers are energized to close. The cool call continues to operate unless
the supply air temperature drops below 45°, at which time the controller
will de-energize “Y” for approximately 3 minutes. 

After 3 minutes, if the leaving air has risen above 45°, Y will energize,
restarting cool operations. When the cool mode is satisfied from the last
calling thermostat, W/OB remains energized until an opposite call for
heat is made.  

If this controller is configured for “B” reversing valve operation, W-O/B LED
will not energize for cool mode; “B” energizes reversing valve in heating.

After all calls for cooling are satisfied Y, G and all damper LEDs will go
off and controller will initiate a 3-minute purge. During this time
controller will not allow a call for heat or cool.  

Heat Mode with LAT:

When a thermostat makes a call for heat, Y & G

LEDs and unit outputs are energized. Any non-calling zone damper
LEDs and outputs are energized to close. The heat call will continue to
operate unless the supply air temperature rises above 120°, at which
time the controller will de-energize “Y” for approximately 3 minutes.
After 3 minutes, if leaving air is less than 120°, Y will reenergize and
heat will restart.  

Auxiliary heat is energized after 3 minutes of run time and if the leaving
air temperature is 88° or less. The auxiliary heat will cycle off when the
leaving air temperature reaches 100°. When the controller energizes W2
to the heat pump strip heater, the W2 LED is illuminated. When all calls
for heat are satisfied, W, W2 ,G and damper LEDs will go off and
controller will initiate a 3-minute purge. During this time, controller will
not allow a call for heat or cool.

Configure DIGI3U for heat pump operations. 

Place jumpers JP1 and JP2 in desired position: JP1 “O,” reversing valve for cooling (“B” position

will energize reversing valve in heating), 

JP2 set in HP position

.

HEAT PUMP CONFIGURATION REQUIRES USING THE LAT SENSOR

Summary of Contents for DIGI3U

Page 1: ...DIGI3U Three Zone Universal Controller for Gas Electric or Heat Pump Applications Installation Guide Part D3MAN Zoning Systems That s all we do 3 Zone Controller for the RNC Market October 2011...

Page 2: ...the controller The resistor is used in place of the LAT for 2 zone Gas Electric installations that do not have a bypass When bypass is used the optional LAT leaving air sensor must be connected in pla...

Page 3: ...s LAT capacity control is not applied a field supplied freeze protection and high limit device must be installed to protect equipment This should only be applied to designs in which both zones are app...

Page 4: ...2 W WIRING GAS ELECTRIC DIGI3U S S terminals for LAT capacity control If not applied leave 1k ohm resistor in place and field supplied high and low limits should be added Transformer damper transforme...

Page 5: ...ition for unit energizing reversing valve for cool place in B position for unit energizing reversing valve in heat JP2 Heat Pump or Gas Electric jumper is used to configure controller Factory set for...

Page 6: ...12va per damper TR SERIES DAMPER M M 1 2 3 3 TR1 TR2 2 1 DIGI3U SYSTEM CONTROLLER ONE TO THREE TR SERIES DAMPERS Fused 24V 40VA Transformer Transformer and 2 amp fuse TR SERIES DAMPER M M 1 2 3 3 TR1...

Page 7: ...puts to furnace and dampers After all calls are satisfied controller will initiate a 3 minute purge During this time controller will not allow any calls for heat or cool Cool Operation without LAT If...

Page 8: ...n place to function in this mode Changeover Gas Electric While controller is operating in heat or cool if another thermostat places a call for the opposite mode a changeover sequence will begin The co...

Page 9: ...ter all calls for cooling are satisfied Y G and all damper LEDs will go off and controller will initiate a 3 minute purge During this time controller will not allow a call for heat or cool Heat Mode w...

Page 10: ...energized PWR Power LED orange On when DTHP4A is powered Flashing during capacity control cutout DPR Damper status LED red One per damper On when damper is closed Emergency Heat Operation To put the...

Page 11: ...control of the unit based upon thermostat input Occasionally software upgrades may become available If so the DIGI3U software can be field upgraded by changing this microcontroller F HVAC System Statu...

Page 12: ...on supports a synchronous 24V AC 60Hz 12VA motor and termi nal board The motor is designed for continuous full stall operation Special winding and heavy duty gearing provide for long motor life and ea...

Page 13: ...or to bypass more than 2000 CFM use the electronic bypass RECTANGULAR ROUND BAROMETRIC BYPASS BYPASS DAMPERS BAROMETRIC AIRFLOW 1 2 4 3 1 Damper Shaft 2 Lock Nut 3 Lever Arm 4 Counter Weight BAROMETR...

Page 14: ...Damper incorrectly wired Correct damper wiring Emergency Heat does not Work STAT 1 must make heat call in Emergency Heat Verify heat call STAT 2 and STAT 3 can make Emergency heat call after STAT 1 V...

Page 15: ...on and blower fan is running 15 Verify air is being delivered to zone 1 and not to any of the other zones 16 At zone 1 verify air is coming out of the register diffuser 17 At next zone a Verify air is...

Page 16: ...9963 Fax 714 898 6802 Visit our Web Site http www zonexsystems com PATENTED PRODUCT Zonex Systems reserves the right to discontinue or change at any time specifications or designs without notice and w...

Reviews: