background image

21

Bypass air in CFM.  Calculated at 1500 FPM.
Formula used:  B = W X H / 144 X 1500, where B = Bypass air in CFM, W = damper width in inches, H= damper height in inches, 144 = 144
sq. inches per sq. ft., 1500 = 1500 FPM.

BYPASS POSITION INDICATOR

SLAVING BYPASS DAMPERS

Use only one Pressure Sensor when slaving two
or more Bypass Dampers together. Connect the
Pressure Sensor to one damper as described
above. Connect the slave dampers in parallel as
shown. Up to 4 dampers can be slaved to
one Sensor. The slaved dampers will self
synchronize each time the dampers reach full
open or full close.

24

28

32

36

40

44

48

8

2000

2333

2667

3000

3333

3667

4000

10

2500

2917

3333

3750

4167

4583

5000

12

3000

3500

4000

4500

5000

5500

6000

14

3500

4083

4667

5250

5833

6417

7000

16

4000

4667

5333

6000

6667

7333

8000

18

4500

5250

6000

6750

7500

8250

9000

20

5000

5833

6667

7500

8333

9167

10000

22

5500

6417

7333

8250

9167

10083

11000

24

6000

7000

8000

9000

10000

11000

12000

28

7000

8167

9333

10500

11667

12833

14000

32

8000

9333

10667

12000

13333

14667

16000

36

9000

10500

12000

13500

15000

16500

18000

40

10000

11667

13333

15000

16667

18333

20000

44

11000

12833

14667

16500

18333

20167

22000

48

12000

14000

16000

18000

20000

22000

24000

8

10

12

14

16

18

20

22

8

667

833

1000

1167

1333

1500

1667

1833

10

833

1042

1250

1458

1667

1875

2083

2292

12

1000

1250

1500

1750

2000

2250

2500

2750

14

1167

1458

1750

2042

2333

2625

2917

3208

16

1333

1667

2000

2333

2667

3000

3333

3667

18

1500

1875

2250

2625

3000

3375

3750

4125

20

1667

2083

2500

2917

3333

3750

4167

4583

22

1833

2292

2750

3208

3667

4125

4583

5042

24

2000

2500

3000

3500

4000

4500

5000

5500

28

2333

2917

3500

4083

4667

5250

5833

6417

32

2667

3333

4000

4667

5333

6000

6667

7333

36

3000

3750

4500

5250

6000

6750

7500

8250

40

3333

4167

5000

5833

6667

7500

8333

9167

44

3667

4583

5500

6417

7333

8250

9167

10083

48

4000

5000

6000

7000

8000

9000

10000

11000

WIDTH IN INCHES

HEIGHT IN INCHES

SLAVE 

DAMPER

ACTUATOR

DAMPER

ACTUATOR

To Static Pressure Controller As Shown On The Bypass Wiring Diagram On The Next Page.

RC
RO
MC

TO NEXT SLAVE 
BYPASS DAMPER 
IF APPLICABLE 

* *

RC RO MC

*

* *

RC RO MC

*

ROUND AND RECTANGULAR

BYPASS DAMPER MOTORS

 

 

 

 

 

CW

CCW

RC

MC

RO 

SHAFT END MARKING IS PARALLEL

WITH DAMPER BLADE. DAMPER TRAVEL

IS 60

°

 ON ROUND BYPASS AND 90

°

ON RECTANGULAR BYPASS

Note: Clockwise to close
on rectangular bypass and
counterclockwise on
round bypass.

BYPASS DAMPERS – ELECTRONIC

RC

MC

RO

101ASPC

Static

Pressure

Control

See Page 22

RECTANGULAR BYPASS SELECTION TABLE

Summary of Contents for DigiTract 4-2

Page 1: ...DigiTract 4 2 Two Stage Heat Cool Comfort Control System Installation Guide Part DT4MAN Rev April 2003 Zoning Systems That s all we do...

Page 2: ...Heat Pump DTHP4 2 11 Calibration 11 LAS Installation 11 ZONE THERMOSTATS Types 12 Zonex Systems Gas Electric Models 12 Digital SADIGI 12 Digital SADIGI Operation 13 Programmable 101PROG 12 Communicati...

Page 3: ...he auxiliary heat to maintain a minimum supply air temperature of 88 degrees See Capacity Controller section page 11 for further information The Zone Dampers are air valves placed in the forced air du...

Page 4: ...BBD diam Rectangular RBB W x H PROGRAMMABLE DIGITAL 101PROG SADIGI OVER 5 TONS ELECTRONIC BYPASS Round STMPD diam Rectangular STCD W x H STATIC PRESSURE CONTROLLER 101ASPC BYPASS TRANSFORMER FIELD SUP...

Page 5: ...e LAS downstream of the bypass takeoff Ensure wire polarity is correct Refer to CAPACITY CONTROLLER LAS INSTALLATION on P 11 for further information NOTE Shielded conductor provided for installations...

Page 6: ...er sized and fused for the total number of zone dampers See DAMPER TRANSFORMER on page 23 Emergency heat terminal E Use only if emergency heat source is different from auxiliary heat W2 If used do not...

Page 7: ...1AMPD 101MRTD 101CD DAMPER RELAY BOARD R C MC RC W W Y RO TB2 TB1 N C N C N C N C N C N C N C N C 101 SERIES DAMPER TO ADDITIONAL 101 SERIES DAMPERS IF APPLICABLE FUSED 24VAC XFMR Transformer and fuse...

Page 8: ...nating Dampers for the zones not calling for cool are powered closed and the dampers for the zones calling for cool are left open This is indicated by the DPR LEDs If the DPR LED is illuminated on the...

Page 9: ...o know this number if conferring with technical support F Heat Mode Fan Control Selection Jumper In the A position the blower is energized by the furnace when heat is energized gas furnaces In the B p...

Page 10: ...e if the System Controller receives a call for the opposite mode the System Controller will continue to run in the current mode for 15 minutes or until all current calls are satisfied Then the System...

Page 11: ...per is closed STATUS LEDs O B Y1 Y2 G W2 PWR DPR MODE FUNCTION OFF OFF OFF OFF OFF OFF OFF Off Power off OFF OFF OFF OFF OFF ON OFF On Power on blower off all zones satisfied OFF OFF OFF ON OFF ON 0 V...

Page 12: ...gized G made to R requests that the DTHP4 2 energize the indoor blower fan C Heat pump unit 24V power return C Damper Terminals Connects dampers for up to four zones and damper power supply TR1 TR2 24...

Page 13: ...rgize Y1 and operate with a minimum run time of 4 minutes regardless of the leaving air temperature At the completion of the minimum run time if the leaving air temperature drops below 45 F Y is deene...

Page 14: ...n SADIGIRS 101PROG Programmable dual setpoint single stage heat cool electronic non power robbing auto changeover weekday weekend 5 1 1 programmable manual override capable Thermostat includes a larg...

Page 15: ...n the room temperature drops two degrees below the heat setpoint and after running a minimum of 2 minutes turn off when the temperature has risen to the heat setpoint When in Auto or Cool mode the the...

Page 16: ...d easy spring open operation A cross pin on the motor shaft provides positive direct drive to the damper blade shaft without a coupling or set screws allowing for a quick and easy motor change if requ...

Page 17: ...19 21 PART 101AMPD06 101AMPD08 101AMPD10 101AMPD12 101AMPD14 101AMPD16 101AMPD18 6 8 10 12 14 16 18 Nominal CFM Duct Diameter Duct Velocity FPM Damper P WC 10 12 14 16 6 8 7 9 410 660 1450 1000 110 25...

Page 18: ...ully closed and cycle off when the damper is opening or in the full opened position Since this is a spring open damper in the event of power failure the damper fails to the full open position RECTANGU...

Page 19: ...MOTOR 48 MAXIMUM WIDTH A Rectangular heavy duty dampers should operate at 1500 FPM E G A 24 x 12 damper 2 square feet 2 square feet X 1500FPM 3000 CFM 4 200 280 390 490 700 1090 1500 2000 2500 3000 36...

Page 20: ...tic pressure and noise at the diffusers Zonex Systems offers two types of bypass dampers Barometric and Electronic Each is available in round or rectangular configuration Barometric bypass dampers are...

Page 21: ...or 5 minutes to equalize pressure Then make sure all dampers are open by checking for air flow out of each damper c By moving counter weight up or down the lever arm adjust it so that the damper just...

Page 22: ...olume is 400 CFM and we have a four ton system Thus the air volume we need to bypass is 400 4 400 which equals 1200 CFM Using the ROUND BYPASS SELECTION TABLE we would select a 12 inch bypass since it...

Page 23: ...16500 18333 20167 22000 48 12000 14000 16000 18000 20000 22000 24000 8 10 12 14 16 18 20 22 8 667 833 1000 1167 1333 1500 1667 1833 10 833 1042 1250 1458 1667 1875 2083 2292 12 1000 1250 1500 1750 200...

Page 24: ...ass damper is Closed Bypass dampers using a square motor have a grey release lever on the bottom side of the damper near motor to manually open or close the damper c At 101ASPC Static Pressure Control...

Page 25: ...ng system go to step 12 2 At System Controller a Disconnect LAS sensor at terminals and place jumper wire between terminals b Turn power switch ON 3 Turn off all thermostats except zone 1 4 At zone 1...

Page 26: ...ext zone a Verify air is not coming out of register diffuser b At thermostat b 1 Set power switch on b 2 Set to Heat mode b 3 Set Fan switch to Auto mode b 4 Set heat setpoint several degrees above ro...

Page 27: ...Thermostat has cooling anticipator compensator Remove anticipator Air flow too low over evaporator Isolate and correct air flow problem Bypass damper opening prematurely Adjust bypass damper closed w...

Page 28: ...Fax 714 898 6802 Visit our Web Site http www hvaccomfort com E mail us at calecon hvaccomfort com PATENTED PRODUCT Zonex Systems reserves the right to discontinue or change at any time specifications...