AUXILIARY HEAT/REHEAT
The zone thermostat provides the following Auxiliary Heat options; Baseboard, Baseboard W1 and Reheat (see figure on
the following page for more details) with configurable dead band of 2°, 3°, or 4°.
Note: Reheat has a fixed 2° dead band.
Baseboard:
the thermostat’s auxiliary output will energize when the room temperature drops 2° - 4° below the heat set
point. Auxiliary heat operations will remain energized until the heat call is satisfied.
Baseboard W1:
the auxiliary output will energize before the unit heater at 1° below heat set point. When the room
temperature drops 2° - 4° below set point the thermostat will send a heat call to the unit heater. Auxiliary heat operations
will remain energized until the heat call is satisfied.
Reheat:
when the zone temperature drops 2° below the heat set point the damper will modulate to approximately 40%
providing air flow over the electric heat strips, the AUX terminal will energize, and strip heat will provide reheat.
Note: When using in duct electric strip heater, an airflow proving switch is required for safe operation.
Configuration of Auxiliary Heat/Reheat is accomplished by selecting “SELECT AUX HEAT” function in the Advanced
Menu. To access the Advanced Menu tap the degree symbol of the room temperature (the degree symbol should
change color to green) then tap the in the upper right corner of the thermostat, see
Fig 1
. Tap “Select Aux Heat”, see
Fig 2
. Select the desired Auxiliary Heat/Reheat and dead band (2°, 3°, or 4°) see
Fig 3
. Tap on to save desired settings.
To return to the home screen tap
baseboard
Fig 1
Fig 2
Fig 3
Home Screen
Advanced Menu
Select Aux Heat Menu