Chapter 6 Grounding System Installation
6-7
3. The lightning arrester is installed indoor. Its grounding cable should be
connected to the outdoor grounding copper bar and should not contact with the
conductor of the indoor cabling rack. The lightning arrester frame is insulated
from the cabling rack.
The installation of the lightning arrester frame is shown in Fig. 6.2-4.
Wall
Feeder
window
Antenna feeder cable
GPS Feeder
GPS lightning
arrester
Cabling
rack
Jumper
Lightening
arrester shelf
Antenna feeder
arrester
Fixing board of
the lightning
arrester
Insulation
tube
The lightning arrester is
connected to the outdoor busbar
through a grounding cable
Fig. 6.2-4 Installing the Lightning Arrester Frame