Item
Description
Door and Window
Doors and windows should be sealed by dustproof rubber strips. Install
double glazed windows that should be strictly sealed. Height and width of
the equipment room main door should not obstruct the transportation of
equipment. Door locks and keys are complete.
Wall
It should not be easy for equipment room walls/ceiling to produce
powder/dust, or to peel off. Decoration materials should be flame resistant,
such as wallpaper, flat paint.
Groove
The grooves are used to route cables. The inner groove surface
should be smooth and clean. The reserved length/width and the
number/location/dimension of holes should meet the router layout
requirements.
Water Sup-
ply/Drainage
Water pipes, drainage pipe, or rain pipes should not go through the
equipment room. Fire hydrants should not be placed in the equipment room.
Instead, they should be set at places that are easily visible and accessible,
such as along the passage or near the staircase.
Equipment Room
Partition
The equipment installation place should be partitioned from the equipment
room door. The screen baffle is intended to ward off some dust.
Worktable and Chair
The worktable, terminal table, and chair should be antistatic. The surface
resistance and system resistance of the electrostatic leakage of table/chair
surface are the same (1×105 Ω – 1×109 Ω).
Air-conditioner
Installation Position
The air conditioner should be installed in such a position that the ventilated
air should not blow the equipment directly.
Other Requirements
Avoid the breeding of microorganisms such as epiphyte and mildew. No
rodent animals (for example, rats) should exist.
A.2 Temperature, Humidity and Altitude
The ZXR10 T8000 requirements for temperature, humidity, and altitude are described in
Table A-2
.
Table A-2 Temperature, Humidity and Altitude Requirements
Item
Parameter
Temperature
-5
℃
– 45
℃
Humidity
5%–90%
Working Environment
Requirement
Altitude
3000 m
Temperature
-40
℃
– 70
℃
Humidity
0–95%
Storage Environment
Requirements
Altitude
< 3000 m
A-2
SJ-20110901170352-005|2011-10-15 (R2.0)
ZTE Proprietary and Confidential