FV637 Rev. A 3/26/2019
Page 4
2.2a.
Optional ACA version: Connect supplied AC adapter to
power port on electronics box.
2.2b.
Optional HW6 (Hardwired 6V) version: Connect supplied
inline connector and hardwire adapter. When securing the CWB
wires to the screw terminals on HW6 unit, the BLACK WITH
DASHED MARKINGS should be connected to the Positive (+)
terminal, and the SOLID BLACK wire should be connected to the
Negative (-) terminal.
MJ unit (sold separately)
Note: Do not connect more than 8 solenoids to a single transformer
2.3. Tighten electronics module assembly to shank and connect
water line(s).
2.4. Ensure that sink is clear of tools/debris and is in normal
operating condition.
2.5. Turn on water supply(ies). Water supply must be turned on in
order for sensor to perform wet calibration step.
Do not engage the sensor for 30 seconds after the connection
is made. The sensor will perform automatic calibration.
-CWB
-HW6
-MJ
-HW6
18 AWG (MIN)
MAX LENGTH 40’
ACA