Z1700

INSTALLATION  INSTRUCTIONS  FOR

SHOKTROL  WATER  HAMMER  ARRESTOR

Rev.

D

Date:

4/17/2018

C.N. No.

139910

Form #

WH1

Page 1 of 2

Zurn SHOKTROLS provide complete protection against water hammer in common pipe diameters for varying pipe lengths
wherever flow velocity is subject to sudden change - in quick closing, solenoid-actuated valves used with lavatories and
sinks, dishwashers, and residential automatic washers; in improperly adjusted water closet flush valves; in pumping sys-
tems, and in drinking fountains or similar installations where water flow is valved for intermittent operation.

Each SHOKTROL has its shock-absorbing air cushion hermetically sealed within the unit. Consequently, there is no loss of
air from the SHOKTROL due to leakage past worn elastomeric sealing surfaces nor due to permeation through elastomeric
features. In addition, the SHOKTROL’s 18-8 stainless steel construction makes it virtually immune to attack and degradation
by high levels of chloramine and other common waterborne chemicals which quickly degrade elastomeric components.

Pressure and Temperature Requirements

Max. Working Pressure:  125 psi
Max. Static Pressure:      250 psi
Max. Temperature:          300° F

SIZING AND LOCATION

When a unit of equipment is located at the remote end of a long
run of piping, the Zurn SHOKTROL should be placed as close
to the point of valve closure as possible. At this location, the
SHOKTROL will control any developed energy and prevent shock
waves from surging through the piping system (Illus. 1). Properly
sized SHOKTROLS should be selected for such installations using
Tables 1-A and 1-B below.

ILLUSTRATION 1: REMOTE INSTALLATIONS

Zurn SHOKTROLS should
always be installed in an
upright position on a horizontal
run of piping.

Approved by:

100

3/4 [19]

3-1/2 [90]

1 [.5]

200

3/4 [19]

3-1/2 [90]

1-1/2 [.7]

300

1 [25]

4-1/2 [114]

1-3/4 [.8]

400

1 [25]

6-5/8 [168]

2-3/4 [1.2]

500

1 [25]

7-1/2 [191]

3-1/4 [1.5]

600

1 [25]

8-1/2 [216]

3-3/4 [1.7]

Dimensions in Inches [mm]

Size

A

C

Approx. Wt. 

Lbs. [kg]

Table I-A. For Pressure Up To 65 spig

1/2"

3/4"

1"

1-1/4"

1-1/2"

2"

25

One #100 One #100 One #200 One #300

One #400

One #500

50

One #100 One #200 One #300 One #400

One #500

One #600

75

One #200 One #300 One #400

One #100 & 

One #500

One #600

One #500 & 

One #600

100

One #300 One #400 One #500 One #600

One #300 & 

One #600

Two #600

125

One #300 One #400 One #600

One #100 & 

One #600

One #500 & 

One #600

One #500 & 

Two #600

150

One #400 One #500 One #600

One #400 & 

One #600

Two #600

Three #600

For further sizing information, see "Plumbing & Drainage Institute Standard WH-201."

Length

 of 

Pipe

Z1700 Series Zurn Shoktrol Water Hammer Arrestors 

Nominal Pipe Diameters

Table I-B. For Pressure 65 psig to 85 psig

1/2"

3/4"

1"

1-1/4"

1-1/2"

2"

25

One #200 One #200 One #300 One #400

One #500

One #600

50

One #200 One #300 One #400 One #500

One #600

One #300 & 

One #600

75

One #300 One #400 One #500 One #600

One #300 & 

One #600

Two #600

100

One #400 One #500 One #600

One #300 

& One 

#600

One #500 & 

One #600

One #500 & 

Two #600

125

One #400 One #500

One #300 

& One 

#600

One #400 

& One 

#600

Two #600

One #200 & 

Three #600

150

One #500 One #600

One #300 

& One 

#600

Two #600

One #400 & 

Two #600

Four #600

For further sizing information, see "Plumbing & Drainage Institute Standard WH-201."

Length

 of 

Pipe

Z1700 Series Zurn Shoktrol Water Hammer Arrestors 

Nominal Pipe Diameters

WARNING

: Cancer and Reproductive Harm - 

www.P65Warnings.ca.gov

ADVERTENCIA: 

Cáncer y daño reproductivo - 

www.P65Warnings.ca.gov

AVERTISSEMENT: 

Cancer et effets néfastes sur la reproduction - 

www.P65Warnings.ca.gov

Reviews: