Motor Lead Pigtail Splice

for 5/8 kV Non-Shielded Cables

for 1000 Volts or less cables (heavy-duty and two-hole lug applications)

Instructions

78-8096-4634-8-

F

Kit Contents (kit contains 3 splices):

3—Lug Covers

3—Locking Pins

3—Tubes Silicone Grease

3—Bag Solvent Cleaning Cloths

3—Mastic Sealing Strip(s)*

3— Strips Scotch

®

 

Linerless Rubber 

Splicing Tape 

130C

 

3—Instruction Sheet

*Quantity varies with kit number.

  Kit 

Cable

 

Size

 

Range

 

 

Cable

 

 

Max.

 

 Number 

(AWG/kcmil)

 

Insulation 

 

Bolt

 

 

Feeder  Motor

 

Lead  O.D.

 

Range  Length

 

5316 

8–4 

10–4 

0.30–0.51

 

in. 

1

2

 

in.

 

5317 

2–1/0 

4–1/0 

0.43–0.65

 

in. 

3

4

 

in.

 

5318 

1/0–250 

2–250 

0.53–0.88

 

in. 

1

1

4

 

in.

 

5319 

250–500 

4/0–500 

0.75–1.12

 

in. 

1

1

2

 

in.

3M

 

Motor Lead 

Pigtail Splice Kits

for 5/8 kV or less Non-Shielded Cables

5316, 5317, 5318, 5319

Technical Information:

•  For non-shielded cables

•  Rated 5/8 kV

•   For cables rated 1000 Volts or less (heavy-duty and two 

hole lug applications)

•  Cable Size Range:   Feeder:  #8 AWG—500 kcmil 

Motor Lead:  #10 AWG—500 kcmil

•  Copper Conductors

 
 

 

CSA Certified for 

600V or Less

Table 1

 

Caution

Working around energized systems may cause serious 

injury or death. Installation should be performed by 

personnel familiar with good safety practice in handling 

electrical equipment. De-energize and ground all 

electrical systems before installing product.

Summary of Contents for 5316

Page 1: ...in 5317 2 1 0 4 1 0 0 43 0 65 in 3 4 in 5318 1 0 250 2 250 0 53 0 88 in 11 4 in 5319 250 500 4 0 500 0 75 1 12 in 11 2 in 3M Motor Lead Pigtail Splice Kits for 5 8 kV or less Non Shielded Cables 5316 5317 5318 5319 Technical Information For non shielded cables Rated 5 8 kV For cables rated 1000 Volts or less heavy duty and two hole lug applications Cable Size Range Feeder 8 AWG 500 kcmil Motor Lea...

Page 2: ... insulation for approximately 6 using solvent saturated cloths provided in kit 2 3 FOR 8kV ONLY Fill lug insulation gaps with Scotch Linerless Rubber Splicing Tape130C Figure 1 2 4 Bolt lugs together See Table 1 on cover for maximum bolt length See Figure 2 for proper bolt lug arrangement Figure 2 3 0 Install Lug Cover 3 1 Separate cables and apply mastic strip between and around them 1 2 from end...

Page 3: ...positioned between the cables Figure 5 Note The kit contains a small tube of Silicone Grease Use it to lightly lubricate the mastic and vinyl tape wraps This will aid in the installation of the Lug Cover 3 5 Be sure that the punched holes are beyond the cable end of the mastic and vinyl tape wrap Insert the plastic locking pin through the holes Figure 5 Hint Inserting the pin from the back side of...

Page 4: ... Y46 use PUADP adapter Anderson VC6 3 and VC6 FT require no die set 3M Scotch and Scotchlok are trademarks of 3M Company Important Notice All statements technical information and recommendations related to 3M s products are based on information believed to be reliable but the accuracy or complete ness is not guaranteed Before using this product you must evaluate it and determine if it is suitable ...

Reviews: