background image

ABB Automation Inc.

Substation Automation and Protection Division
Coral Springs, FL 33065

Instruction Leaflet

All possible contingencies which may arise during installation, operation or maintenance, and all details and
variations of this equipment do not purport to be covered by these instructions. If further information is
desired by purchaser regarding this particular installation, operation or maintenance of this equipment, the
local ABB Power T&D Company Inc. representative should be contacted.

!

CAUTION

Before putting protective relays into service,

remove all blocking inserted for the purpose

of securing the parts during shipment. Make

sure that all moving parts operate freely.

Inspect the contacts to see that they are clean

and close properly, and operate the relay to

check the settings and electrical connections.

1. APPLICATION

The current transformers should not saturate when

carrying the maximum external fault current. This
requirement is met if the burden impedance does not
exceed:

where

N

p

= proportion of total ct turns in use.

V

cL

= Current transformer accuracy class

C voltage.

I

ext.

= maximum external fault current in

secondary RMS amperes. (let I

ext

. =

100 if max. external fault current is
less than 100A)

R

s

= current transformer secondary wind-

ing resistance, ohms.

For example, if the 400:5 tap of 800:5 C400 current
transformers are used, N

p

 = 400/800 = 0.50, if I

ext.

 =

120A, R

s

 = 1.0 ohm the burden should not exceed:

N

p

V

pL

I

ext.

100

(

)

R

s

1.33 I

ext.

(

)

------------------------------------------------------------

 for CA-16 applications

N

p

V

cL

I

ext.

100

(

)

R

s

I

e xt.

--------------------------------------------------------------

 for CA-26 appliations

N

p

V

cL

I

ext.

100

(

)

R

s

1.33 I

ext.

(

)

--------------------------------------------------------------

  =

0.05

400

120

100

(

)

×

1.0

×

1.33

120

×

-------------------------------------------------------------------------------

1.13  ohms

=

Types CA-16 and CA-26
Percentage Differential Relays
for Bus and Transformer 
Protection

Effective: September 1995

Supersedes I.L. 41-337.3K, Dated October 1985

( | ) Denotes Changes since previous issue

41-337.3L

CONTENTS

This instruction leaflet applies to the following
types of relays:

CA-16 Bus Differential Relay
CA-26 Transformer Differential Relay

The CA-16 relay should not be utilized for trans-
former differential applications since it is too sensi-
tive for overriding the inrush. Likewise the CA-26
relay should not be used for bus protection with
the “four-circuit bus” connections of Figure 8. The
CA-26 relay is suitable for combination bus-trans-
former applications. See “CONNECTIONS”.

Courtesy of NationalSwitchgear.com

Summary of Contents for CA-16

Page 1: ...nt transformer accuracy class C voltage Iext maximum external fault current in secondary RMS amperes let Iext 100 if max external fault current is less than 100A Rs current transformer secondary wind...

Page 2: ...41 337 3L 2 Photo Figure 1 Types CA 16 Relay front view Photo Figure 2 Types CA 16 Relay rear view Courtesy of NationalSwitchgear com...

Page 3: ...se fluxes cause a contact opening torque 2 2 Operating Circuit The operating circuit consists of an auto transformer and an operating element The primary of the auto transformer which is the whole win...

Page 4: ...fastened to the bottom of the guide rod by two small nuts Its position determines the pick up current of the ele ment The auto transformer is designed to saturate at high values of current to limit t...

Page 5: ...ent transformers connected to the bus and the oper ating circuit is energized in accordance with the current flowing in the differential connection of the current transformers A current of 5 amperes i...

Page 6: ...es of the current transformers involved The time of operation of the relays is shown in Figure 6 4 2 CA 26 Transformer Relay The type CA 26 transformer differential relay includes an indicating instan...

Page 7: ...feeder ct s taking the precau tion that each feeder group has less than 14 amperes load current restraint coil continuous rating If the bus reduces to more than four circuits parallel ct s until only...

Page 8: ...9 connections where there are more than three sources the source ct s should be paralleled to reduce the effective number of source connections to three The four circuit bus connections of Figure 8 ar...

Page 9: ...of the four mounting holes on the flange for semi flush mounting or by means of the rear mounting stud or studs for projection mount ing Either a mounting stud or the mounting screws may be utilized f...

Page 10: ...acts and target indication should occur at approximately the same instant Position the stationary contact for a minimum of 1 32 inch wipe The bridging moving contact should touch both stationary conta...

Page 11: ...ve Fault Detector Loosen the lock nut at the top of the element and run the core screw down until it is flush with the top of the lock nut Back off the Micarta disc by loosening the two lock nuts Appl...

Page 12: ...41 337 3L 12 Sub 2 408C507 Figure 14 External Schematic of the Type CA 26 Relay for Wye Wye Delta Transformer Protection Sub 2 408C507 Courtesy of NationalSwitchgear com...

Page 13: ...41 337 3L 13 This Space Reserved for Notes Courtesy of NationalSwitchgear com...

Page 14: ...41 337 3L 14 This Space Reserved for Notes Courtesy of NationalSwitchgear com...

Page 15: ...41 337 3L 15 This Space Reserved for Notes Courtesy of NationalSwitchgear com...

Page 16: ...ral Ridge Drive Coral Springs Florida 33065 TEL 954 752 6700 FAX 954 345 5329 visit our website at www abbus com papd Sub 16 57D7903 Figure 15 Outline and Drilling for the CA 16 and CA 26 Relays in FT...

Reviews: