background image

Operating instruction

Modem 50-2400 baud 500FSD20 

EDS500 series - FSK modems 

Operating instruction

Modem 50-2400 baud 500FSD20

EDS500 series - FSK modems

Application, characteristics and technical data have to
be taken from the hardware data sheet:

500FSD20 Data sheet

  

1KGT150986

Operation

The 500FSD20 modem is a voice-frequency telegraphy
unit (VFT unit) which operates according to the
principle of binary frequency shift keying. The modem
can operate in two- and four-wire connection. The
mode of operation is set by a command line interface
(CLI).

Connections
Power connector (X1)

The EDS500 devices are equipped with a wide range
power supply for voltages between 24 and 60 Volts DC
(power consumption see device label). The connector
is a 3-pin Phoenix plug with screw terminals.

Pin allocation power supply (X1)

Pin Signal
1

24-60 V DC

2

Functional earth

1

2

3

3

GND

ADVICE

Due to the internal overvoltage protection,
interrupt any connection to ground of the device
for the time of the measurement before you carry
out isolation measurements. This includes the
earthing of the hat rail as well as all shields of all
transmission lines and supply feedings. RJ-12 plugs
or RJ-45 plugs can also establish earthing via the
shield.

Serial interface to DTE (X2)

The RJ-45 connector X2 forms an RS-232-D interface. If
the modem is connected to an RTU, an adapter cable
has to be used which connects the pin pairs.

Pin allocation serial interface DTE (RJ-45)

RS-232-D
Pin

Signal

V.24

Signal

V.28

Direction

8

1

1

DSR M1

107

output

Pin allocation serial interface DTE (RJ-45)

2

DCD M5

109

output

3

DTR S1

108.2

input

4

GND

GND

-

5

RxD C2

104

output

6

TxD D1

103

input

7

CTS M2

106

output

8

RTS S2

105

input

Interface to transmission line (X3)

In two-wire mode X3-1 and X3-2 form terminal NF1
which is used for transmission and reception.

In four-wire mode X3-1 and X3-2 form the transmitter
terminal NF1 and X3-3 and X3-4 form the receiver pair
NF2.

NF terminals

Transmit

Receive

2-wire

NF1: X3-1 and X3-2

NF1: X3-1 and X3-2

4-wire

NF1: X3-1 and X3-2

NF2: X3-3 and X3-4

Pin allocation transmission line interface (X3)

Pin Signal
1

NF1a

2

NF1b

3

NF2a

4

3

2

1

4

NF2b

Serial interface for configuration (Con0)

The serial interface of the device is  signal compatible
to RS-232. The connector is an RJ-12 female plug. The
factory presets are speed 57600 Baud, no parity, 1
stop bit, no flow control. Via the serial interface the
management console can be accessed .

Pin allocation serial interface RS-232 (RJ-12)

RS-232

RS-232 PC SUB-D9

Pin Signal Direction Pin Signal Direction
1

DCD Output

1

DCD Input

2

CTS

Output

8

CTS

Input

3

RTS

Input

7

RTS

Output

4

GND -

5

GND -

5

RxD

Output

2

RxD

Input

6

1

6

TxD

Input

3

TxD

Output

Summary of Contents for EDS 500FSD20

Page 1: ... to DTE X2 The RJ 45 connector X2 forms an RS 232 D interface If the modem is connected to an RTU an adapter cable has to be used which connects the pin pairs Pin allocation serial interface DTE RJ 45 RS 232 D Pin Signal V 24 Signal V 28 Direction 8 1 1 DSR M1 107 output Pin allocation serial interface DTE RJ 45 2 DCD M5 109 output 3 DTR S1 108 2 input 4 GND GND 5 RxD C2 104 output 6 TxD D1 103 in...

Page 2: ...ed via Con0 off No alarm flash Warning or configuration error Alarm Alarm red Alarm Configuration using a serial configuration cable The serial interface provides access to the command line Using a serial configuration cable 500CAB06 1KGT038912R0001 the device can be connected to a serial port of a PC notebook The default configuration for the serial connection is 57600 Baud 8N1 8 data bits no par...

Page 3: ...e restart ADVICE The established communication connection will be lost temporarily during restart Firmware Update The firmware is updated by transferring a firmware image to the device This is accomplished by first pressing the reset button for longer than 5 seconds to put the modem into firmware update mode Then with CON0 of the modem connected to a PC via a serial cable open a command window in ...

Page 4: ... 3 to the negative terminal of a DC power supply The communication line can be either connected in two wire or four wire configuration For two wire configuration connect terminal X3 1 and X3 2 to the pair of wires For four wire configuration connect terminal X3 1 and X3 2 to the pair of wires used for transmit direction and X3 3 and X3 4 to the pair used for receive direction The internal transfor...

Page 5: ...0 Label X1 X3 X2 1 2 3 1 2 3 4 Connect DIN rail to Protection earth 1 8 Figure 4 Schematic installation drawing NF2a NF2b NF1a NF1b Z0 Z0 A1 A1 E1 E1 A2 A2 E2 E2 S P T T T R NF1 NF2 OVP OVP Figure 5 Communication line connection by LF transformer two wire connection ...

Page 6: ...ontents of this document without prior notice With regard to purchase orders the agreed particulars shall prevail ABB Power Grids Germany AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third parti...