Security Products
Automatic Fire Detector in Conventional Technology
Detector Series FC650
Technical Data
Description
The FC650 fire detector series are conventional threshold
alarm detectors that comply with the respective standard of
the EN 54 standard series and are VdS approved.
The detectors feature an alarm indicator on the detector head
that is visible from all angles, and which can be triggered
with a permanent magnet for test purposes. A detector base
is provided for mounting and cable connection purposes,
into which the detector is simply plugged-in via the bayonet
connection. By connecting an address module to the
detector base, the relevant detector can be identified by the
alarm panel during an alarm, should the alarm panel have
the respective performance features. In this case, the first
detector that was triggered is detected for each detector
group.
Data can be read out of the detector and displayed using the
Programming Device FI700/PU. In this way, the degree of pol-
lution of the Optical Smoke Detector FC650/O can be read
out. The detector is screwed into the base of the FI700/PU for
this purpose, where the required data can be read out.
Application
The FC650 series offers detectors for different applications.
The Optical Smoke Detector FC650/O operates according
to the scattered-light principle and is used where smoke is
expected in case of a fire. The detector is equipped with
a dust barrier that protects the detector both against dust
contamination as well as penetration of outside light sources.
An insect screen prevents intrusion by small insects.
If factors such as dust, water vapour or cigarette smoke are
expected to affect the smoke detector operation or very fast
heat development is expected in the event of a fire, the Heat
Detectors FC650/TDIFF or FC650/TMAX should be used.
The Thermal Max. Detector FC650/TMAX triggers if a
predefined threshold temperature of 78 °C is exceeded.
The Thermal ROR Detector FC650/TDIFF also reacts to
fast increase in temperature, which generally occur in the
event of a fire, and at a temperature of 57 °C or higher.
The temperature is monitored with so-called measuring
thermistors.
All detectors are only intended for indoor use in dry ambience.
• Detector series compliant to EN 54 comprising
of smoke and heat detectors – VdS approved
• Alarm LED on the detector head
• Output of detector specific data using
the Programming Device FI700/PU
• Simple handling using bayonet connection
• Test activation possible using a magnet
• Anti-tamper mechanical block feature
• Remote indicator can be connected
to the detector base