background image

— 

INTRODUCTION
This document explains how to install the plug-in 
ABB OVR Surge Protective Devices (SPDs) for 
telephone and ISDN lines:

OVR TN/RJ11-2/6
protects the middle 2 (of 6) conductors on 
telephone lines with RJ11 connections.

OVR TN/RJ11-4/6
protects the middle 4 (of 6) conductors on 
telephone lines with RJ11 connections.

OVR TN/RJ11-6/6
protects all 6 conductors on telephone lines with 
RJ11 connections.

OVR ISDN/RJ45-4/8
protects the middle 4 (of 8) conductors on S/T 
interface ISDN lines with RJ45 connections.

OVR ISDN/RJ45-8/8
protects all 8 conductors on S/T interface ISDN 
lines with RJ45 connections.

2.  Before installation
2.1
  Make sure that the system’s maximum line 

voltage (DC or AC peak) will never exceed the 
maximum working voltage of the SPD. 

 

Otherwise the SPD will clamp signal voltages 
as though they were transient overvoltages.

Maximum Working 

Voltage

OVR TN/RJ11 

296 V

OVR ISDN/RJ45

58 V

2.2 Make sure that the SPD’s plug and socket 

connections are physically compatible with 
those connecting the equipment to the 
telephone (or ISDN) line.

2.3  Ensure that the current passing through the 

SPD does not exceed 300 mA.

3. Installation
3.1
  Connection
 

The SPD is connected in series with the 
telephone (or ISDN) line (see Figures 1 and 2).

 

If the SPD’s dirty line cable is longer than 
required, neatly coil and bind the surplus out 
of the way, keeping this away from clean 
cables.

3.4 Earthing
 

The SPD must be connected to a good 
electrical earth, either:

a)   through installation on a TS36 'top hat' DIN 

rail (which in turn is connected to earth), or

b)   by connecting a crimped 10mm² stranded 

green/yellow cable should be used to bond 
the SPD’s earth stud to earth.

 

This SPD earth bond should be less than  
1 metre long (otherwise the effectiveness of 
the SPD will be reduced).

 

Ideally the SPD would be connected to the 
main electrical earth or earth star point 
(located at a distribution board) (see Figure 
4, overleaf).

 

However, owing to the 1 metre (maximum) 
earth bond, the SPD will often be hard-wired 
to the ring main earth. 

 

Never connect the SPD to earth via the earth 
pin of a plug, as this may be removed.

 

If the earth bond is more than 1 metre from 
the SPD, earth bonds of 2, 3 or 4 metres are 
allowed if 2, 3 or 4 parallel earth bonds are 
used. These must be kept at least 5 cm apart 
from each other.

 

The SPD or base plate earth bond should be 
less than 1 metre long (otherwise the 
effectiveness of the SPD will be reduced).

 

10 mm² stranded green/yellow cable should 
 be used for this bond.

 

SPD or base plate earth bonds of 2, 3 or  
4 metres are allowed if:

 

–  2, 3 or 4 parallel earth bonds are used and

 

–   these parallel earth bonds are kept at 

least 5 cm apart from each other

 

Where even 4 metres of connecting lead is 
not sufficient, the incoming cable should be 
re-routed to bring it within 4 metres of the 
earth.

 

In circumstances where the cable cannot 
ideally be re-routed, the SPD can alternatively 
be connected to the electrical earth local to 
the equipment being protected (eg the earth 
bar of the local power distribution board) 
(see Figure 4).

... continued overleaf

1.  Safety note:
 

  Warning! Installation by person with 
electrotechnical expertise only.

 

 Warnung! Installation nur durch 
elektrotechnische Fachkraft.

 

 Avvertenza! Fare installare solo da un 
elettricista qualificato.

 

 Avertissement! Installation uniquement par 
des personnes qualifiées en électrotechnique.

 

 Advertencia! La instalación deberá ser 
realizada únicamente por electricistas 
especializados.

A protector on the mains power supply to 
equipment is also recommended in addition to 
protection on telephone & ISDN lines.

 

Simply plug it into the telephone socket and 
plug the protected equipment into the SPD.

 

Note: The mains power input to equipment 
should also be protected.

3.2  Mounting
 

Fixing holes on the base of the unit enable it 
to be screwed to any flat surface.

 

Before doing so, ensure that it is close to a 
good earthing point (see Section 3.4 
- Earthing).

3.3  Keep clean cables away from dirty cables
 

The outgoing clean cable (ie from the SPD’s 
socket end) should never be routed next to 
the incoming dirty line cable (the SPD's cable 
end) or the dirty earth cable  
(see Figure 3).

 

The clean cable must be kept at least 5 cm 
apart from either the SPD’s dirty cable, or 
those of neighbouring units.

ELECTRONIC SYSTEMS PROTECTION

Plug-in Lightning Barrier

Wilford Road,
Nottingham,
NG2 1EB, UK

LINE

CLEAN

To ISDN 
Line

From 

Equipment

EARTH

ELECTRONIC SYSTEMS PROTECTION

Plug-in Lightning Barrier

Wilford Road,
Nottingham,
NG2 1EB, UK

Figure 1:  
Plug-in series connection for OVR TN/RJ11-2/6, 4/6 and 6/6.

LINE

CLEAN

To Telephone 
Socket

From 

Equipment

EARTH

ELECTRONIC SYSTEMS PROTECTION

Plug-in Lightning Barrier

Wilford Road,
Nottingham,
NG2 1EB, UK

ELECTRONIC SYSTEMS PROTECTION

Plug-in Lightning Barrier

Wilford Road,
Nottingham,
NG2 1EB, UK

ELECTRONIC SYSTEMS PROTECTION

Plug-in Lightning Barrier

Wilford Road,
Nottingham,
NG2 1EB, UK

ELECTRONIC SYSTEMS PROTECTION

Plug-in Lightning Barrier

Wilford Road,
Nottingham,
NG2 1EB, UK

ELECTRONIC SYSTEMS PROTECTION

Plug-in Lightning Barrier

Wilford Road,
Nottingham,
NG2 1EB, UK

ELECTRONIC SYSTEMS PROTECTION

Plug-in Lightning Barrier

Wilford Road,
Nottingham,
NG2 1EB, UK

Installation Instructions for Mains Wire-In Protectors | 

1

Safety note:

Warning! Installation by person with 
electrotechnical expertise only.
Warnung! Installation nur durch 
elektrotechnische Fachkraft.
Avvertenza! Fare installare solo da un 
elettricista qualificato.
Avertissement! Installation uniquement par 
des personnes qualifiées en électrotechnique.
Advertencia! La instalación deberá ser 
realizada únicamente por electricistas 
especializados.

ESP protector installation should be 
conducted by a qualified competent person 
and comply with all relevant Regulations and 
Legislation (including BS 7671 Wiring 
Regulations and Building Regulations). 
Incorrect installation will impair the 
effectiveness of ESP protectors.

Always handle cables by their insulation. 
Never work on ESP protectors, earthing or 
their cables during a storm.

1.  Key points of installation

  

1.1  Install protectors very close to the power  
 

supply to be protected, either within the  

 

distribution panel or directly alongside it.

1.2  Mount units within a panel or WBX  

 

 

enclosure.

1.3  Units are installed in parallel.

1.4  Connect to phase(s), neutral and earth.

 

NOTE: Units must have a neutral  

 

 

connection (see 3.4).

1.5  Units installed at power distribution  

 

 

boards can be installed either:

 

-

on the load side of the incoming  

 

 

isolator

on the closest available out going way to  

 

the incoming supply 

1.6  Provide a means of isolation for the 
 

ESP unit.

1.7  The connecting leads to phase/live  

 

 

terminals should be suitably fused 

 

(up to  125 Amps) ensuring full  

 

 

discrimination with the immediate  

 

 

upstream supply fuse.

1.8  Connecting leads should be 10 mm

 

 

 

multi-stranded copper conductor  

 

 

(terminals can accept up to 25 mm

2

).

1.9  Keep the connecting leads as short as    
 

possible and ideally less than 25 cm

 

(10 inches) in length. This may be better

 

achieved with the equivalent M1R  

 

 

remote display variant which permits  

 

 

optimum positioning of both protector    

 

and display.

1.10 Bind the connecting leads tightly  

 

 

  over their entire length.

1.11 Maximum torque for power terminals is
        2.9Nm, wire stripping length 17mm.

1.12 Maximum torque for remote contact is
        0.25Nm, wire stripping length 7mm.

1

Installation instructions

ESP M1/M1R mains protectors

Figure 2:  
Plug-in series connection for OVR ISDN/RJ45-4/8 and 8/8.

Figure 3:  
Cable routeing.

Reviews: