background image

 

RELION® 670 SERIES

— 

Line distance protection REL670 

Version 2.2 

Product guide

Summary of Contents for RELION REL670

Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 Product guide...

Page 2: ...cription 48 23 Connection diagrams 51 24 Technical data 52 25 Ordering for customized IED 127 26 Ordering for pre configured IED 139 27 Ordering for Accessories 145 Disclaimer The information in this...

Page 3: ...ower system sections close to electrical centre at occurring out of step The IED can be used in applications with IEC UCA 61850 9 2LE process bus with up to eight merging units MU depending on other f...

Page 4: ...MSQI MET Usqi VN MMXU MET UN DRP RDRE DFR SER DR V MMXU MET U LMB RFLO 21FL FL ZMF PDIS 21 Z FUF SPVC U I C MMXU MET I C MSQI MET Isqi CV MMXN MET P Q ETP MMTR MET W Varh S CILO 3 Control S CSWI 3 Con...

Page 5: ...C 50 3I BRC PTOC 46 Iub S SCBR Control S SCBR Control S SCBR Control Other Functions available from the function library S CILO 3 Control S CSWI 3 Control ROV2 PTOV 59N 2 U0 CCS SPVC 87 INd I VDC PTOV...

Page 6: ...H 85 SMB RREC 79 0 1 SMP PTRC 94 1 0 SES RSYN 25 SC FUF SPVC U I CC PDSC 52PD PD S CILO 3 Control Q CBAY 3 Control S CSWI 3 Control Q CRSV 3 Control S XSWI 3 Control CC RBRF 50BF 3I BF CC RBRF 50BF 3I...

Page 7: ...ZCRW PSCH 85 ZC PSCH 85 ZM RPSB 68 Zpsb ZMF PDIS 21 Z ZCV PSOF FUF SPVC U I SDE PSDE 67N IN GUP PDUP 37 P PSL PSCH Zpsl VD SPVC 60 Ud OEX PVPH 24 U f GOP PDOP 32 P SA PFRC 81 df dt SA PTOF 81 f SA PT...

Page 8: ...50BF TRIP BUSBAR en05000276 vsd 3U 59 3U 27 2 2 2 2 IEC05000276 1 V1 EN Figure 5 The single breaker packages for single and three phase tripping typical arrangement for one protection sub system is s...

Page 9: ...d closing of ring bays automatic load transfer from one busbar to the other and so on The basic IED configuration is provided with the signal matrix single line diagram and the application configurati...

Page 10: ...user or do not need to be configured are not described in this manual Main protection functions Table 1 Example of quantities 2 number of basic instances 0 3 option quantities 3 A03 optional function...

Page 11: ...arth faults 0 5 ZDMRDIR 21D Directional impedance element for mho characteristic 0 2 ZDARDIR Additional distance protection directional function for earth faults 0 2 ZSMGAPC Mho impedance supervision...

Page 12: ...onstant Fahrenheit 0 2 1 1 1 1 CCRBRF 50BF Breaker failure protection 0 2 1 1 2 1 STBPTOC 50STB Stub protection 0 2 1 1 1B 1 B27 1 CCPDSC 52PD Pole discordance protection 0 2 1 1 2 1 GUPPDUP 37 Direct...

Page 13: ...E04 1B 3 E04 1B 3 E04 SAPFRC 81 Rate of change of frequency protection 0 6 1B 3 E04 1B 3 E04 1B 3 E04 1B 3 E04 Multipurpose protection CVGAPC General current and voltage protection 0 4 1 4 F01 4 F01 4...

Page 14: ...e Point indication 16 16 16 16 16 SPC8GAPC Single point generic control function 8 signals 5 5 5 5 5 AUTOBITS Automation bits command function for DNP3 0 3 3 3 3 3 SINGLECMD Single command 16 signals...

Page 15: ...c blocks Q T see Table 5 0 1 AND GATE INV LLD OR PULSETIMER RSMEMORY SLGAPC SRMEMORY TIMERSET VSGAPC XOR Extension logic package see Table 6 0 1 FXDSIGN Fixed signal function block 1 1 1 1 1 B16I Bool...

Page 16: ...ber of instances SCILO Interlocking 10 BB_ES 3 A1A2_BS 2 A1A2_DC 3 ABC_BC 1 BH_CONN 1 BH_LINE_A 1 BH_LINE_B 1 DB_BUS_A 1 DB_BUS_B 1 DB_LINE 1 ABC_LINE 1 AB_TRAFO 1 SCSWI Switch controller 10 SXSWI Cir...

Page 17: ...N1 1 RESIN2 59 POS_EVAL Evaluation of position indication 15 XLNPROXY Proxy for signals from switching device via GOOSE 20 GOOSEXLNRCV GOOSE function block to receive a switching device 20 Table 5 Tot...

Page 18: ...e Extended configurable logic block Total number of instances AND 180 GATE 49 INV 180 LLD 49 OR 180 PULSETIMER 89 RSMEMORY 40 SLGAPC 74 SRMEMORY 130 TIMERSET 109 VSGAPC 120 XOR 89 1MRK 506 372 BEN Lin...

Page 19: ...4 24 24 24 BINSTATREP Logical signal status report 3 3 3 3 3 RANGE_XP Measured value expander block 66 66 66 66 66 SSIMG 63 Insulation supervision for gas medium 21 21 21 21 21 SSIML 71 Insulation sup...

Page 20: ...e REL670 Customized REL670 A41 REL670 A42 REL670 B42 REL670 D42 Metering PCFCNT Pulse counter logic 16 16 16 16 16 ETPMMTR Function for energy calculation and demand handling 6 6 6 6 6 1MRK 506 372 BE...

Page 21: ...munication via GOOSE for interlocking 59 59 59 59 59 GOOSEBINRCV GOOSE binary receive 16 16 16 16 16 GOOSEDPRCV GOOSE function block to receive a double point value 64 64 64 64 64 GOOSEINTRCV GOOSE fu...

Page 22: ...3 3 3 3 DHCP DHCP configuration for front access point 1 1 1 1 1 QUALEXP IEC 61850 quality expander 96 96 96 96 96 Remote communication BinSignRec1_1 BinSignRec1_2 BinSignReceive2 Binary signal transf...

Page 23: ...for residual overcurrent protection 0 1 1 1 1 DTT Direct transfer trip 0 1 Table 7 Number of function instances in Synchrophasor report 8 phasors Function name Function description Number of instances...

Page 24: ...ups ACTVGRP Parameter setting groups TESTMODE Test mode functionality CHNGLCK Change lock function SMBI Signal matrix for binary inputs SMBO Signal matrix for binary outputs SMMI Signal matrix for mA...

Page 25: ...otection Additional security logic for differential protection LDRGFC Additional security logic for differential protection LDRGFC can help the security of the protection especially when the communica...

Page 26: ...lt in adaptive load compensation algorithm prevents overreaching of zone 1 at load exporting end at phase to earth faults on heavily loaded power lines The distance protection zones can operate indepe...

Page 27: ...s an individual function block available for independent configuration in ACT The IED can be used up to the highest voltage levels It is suitable for the protection of heavily loaded lines and multi t...

Page 28: ...ystems The phase selection function is design to accurately select the proper fault loop s in the distance function dependent on the fault type The heavy load transfer that is common in many transmiss...

Page 29: ...ir start can be linked per zone through the phase selector or the first starting zone This can provide fast operate times for evolving faults The operation of the phase selection is primarily based on...

Page 30: ...r of oscillation in its zone 1 should operate first Two current channels I3P1 and I3P2 are available in OOSPPAM function to allow the direct connection of two groups of three phase currents that may b...

Page 31: ...vice classes 6 Current protection Instantaneous phase overcurrent protection PHPIOC The instantaneous three phase overcurrent function has a low transient overreach and short tripping time to allow us...

Page 32: ...mal overload protection can allow the protected circuit to operate closer to the thermal limits The three phase current measuring protection has an I2t characteristic with settable time constant and a...

Page 33: ...ettings close to the system service voltage Two step overvoltage protection OV2PTOV Overvoltages may occur in the power system during abnormal conditions such as sudden power loss tap changer regulati...

Page 34: ...ve sequence voltage measurement and requires two phase phase or three phase neutral voltages to be connected Overfrequency protection SAPTOF Overfrequency protection function SAPTOF is applicable in a...

Page 35: ...y point Some example of protection functions are Distance protection function Undervoltage function Energisation function and voltage check for the weak infeed logic These functions can operate uninte...

Page 36: ...te via the system wide interbay bus IEC 61850 8 1 or by using hard wired binary inputs outputs The interlocking conditions depend on the circuit configuration and apparatus position status at any give...

Page 37: ...of LEDs or putting IED in ChangeLock state from remote In this way simple commands can be sent directly to the IED outputs without confirmation Confirmation status of the result of the commands is su...

Page 38: ...e logic can be controlled either by the autorecloser zone extension or by the loss of load current loss of load acceleration Scheme communication logic for residual overcurrent protection ECPSCH To ac...

Page 39: ...ceive logic LCCRPTRC function gives final trip output of the DTT scheme Features Carrier redundancy to ensure security in DTT scheme Blocking function output on CR Channel Error Phase wise trip output...

Page 40: ...block that inverts the input signal to the output LLD function block Loop delay used to delay the output signal one execution cycle OR function block The OR function is used to form general combinator...

Page 41: ...unction block FXDSIGN The Fixed signals function FXDSIGN has nine pre set fixed signals that can be used in the configuration of an IED either for forcing the unused inputs in other function blocks to...

Page 42: ...tion file CFG and a data file DAT The same applies to all events which are continuously saved in a ring buffer The local HMI is used to get information about the recordings The disturbance report file...

Page 43: ...ions CVMMXN CMMXU VMMXU and VNMMXU current and voltage sequence measurement functions CMSQI and VMSQI and IEC 61850 generic communication I O functions MVGAPC are provided with measurement supervision...

Page 44: ...s functionality Function for energy calculation and demand handling ETPMMTR Power system measurement CVMMXN can be used to measure active as well as reactive power values Function for energy calculati...

Page 45: ...303 AP3 IEC16000092 V1 EN Figure 13 Access points non redundant left and redundant communication right DHCP is available for the front port and a device connected to it can thereby obtain an automatic...

Page 46: ...3 standard This allows design of simple substation automation systems including equipment from different vendors Disturbance files uploading is provided Measurands for IEC 60870 5 103 I103MEAS 103MEAS...

Page 47: ...When IEDs are used in Substation Automation systems with LON SPA or IEC 60870 5 103 communication protocols the Event and Multiple Command function blocks are used as the communication interface for v...

Page 48: ...module SLM for SPA IEC 60870 5 103 LON and DNP 3 0 The Serial and LON communication module SLM is used for SPA IEC 60870 5 103 DNP3 and LON communication SLM has two optical communication ports for p...

Page 49: ...with rear cover IEC08000165 2 en vsdx J G F K H IEC08000165 V2 EN Figure 16 Case with rear cover and 19 rack mounting kit IEC06000182 2 en vsd IEC06000182 V2 EN Figure 17 A 1 2 x 19 size IED side by...

Page 50: ...86 190 5 7 50 428 3 16 86 465 1 18 31 228 6 9 00 482 6 19 00 The H and K dimensions are defined by the 19 rack mounting kit Mounting alternatives 19 rack mounting kit Flush mounting kit with cut out d...

Page 51: ...ts Connection diagram 670 series 2 2 1MRK002801 AG Connection diagrams for Configured products Connection diagram REL670 2 2 A41X00 1MRK002807 LE Connection diagram REL670 2 2 A42X00 1MRK002807 LF Con...

Page 52: ...n instrument transformers Note that for functions which measure an analogue signal which do not have corresponding primary quantity the 1 1 ratio shall be set for the used analogue inputs on the IED E...

Page 53: ...s 10 Ir for 1 min 4 Ir continuously Dynamic withstand 250 Ir one half wave Burden 20 mVA at Ir 1 A 150 mVA at Ir 5 A max 350 A for 1 s when COMBITEST test switch is included Voltage inputs Rated volt...

Page 54: ...110 V 80 mVA at 220 V all values for individual voltage inputs Note All current and voltage data are specified as RMS values at rated frequency Table 12 MIM mA input module Quantity Rated value Nomina...

Page 55: ...V 110 125 V 220 250 V RL 20 RL 20 RL 20 RL 20 Power consumption 24 30 V 50 mA 48 60 V 50 mA 110 125 V 50 mA 220 250 V 50 mA 220 250 V 110 mA max 0 05 W input max 0 1 W input max 0 2 W input max 0 4 W...

Page 56: ...be activated simultaneously with influencing factors within nominal range Table 17 IOM Binary input output module Quantity Rated value Nominal range Binary inputs 8 DC voltage RL 24 30 V 48 60 V 110 1...

Page 57: ...king capacity for AC cos 0 4 250 V 8 0 A 250 V 8 0 A Breaking capacity for DC with L R 40 ms 48 V 1 A 110 V 0 4 A 125 V 0 35 A 220 V 0 2 A 250 V 0 15 A 48 V 1 A 110 V 0 4 A 125 V 0 35 A 220 V 0 2 A 25...

Page 58: ...24 30 V 0 1 A Breaking capacity for AC cos j 0 4 250 V 8 0 A 250 V 8 0 A Breaking capacity for DC with L R 40 ms 48 V 1 A 110 V 0 4 A 220 V 0 2 A 250 V 0 15 A 48 V 1 A 110 V 0 4 A 220 V 0 2 A 250 V 0...

Page 59: ...y for DC with L R 40 ms 48 V 1 A 110 V 0 4 A 60 V 0 75 A 125 V 0 35 A 220 V 0 2 A 250 V 0 15 A Operating time 1 ms 1 ms Table 21 SOM Static Output module data reference standard IEC 61810 2 Electromec...

Page 60: ...ors Table 23 Temperature and humidity influence Parameter Reference value Nominal range Influence Ambient temperature operate value 20 C 10 C to 55 C 0 02 C Relative humidity Operative range 10 90 0 9...

Page 61: ...SI C37 90 1 Electrostatic discharge Direct application Indirect application 15 kV air discharge 8 kV contact discharge 8 kV contact discharge IEC 60255 26 IEC 61000 4 2 Class IV Electrostatic discharg...

Page 62: ...les at 25 C to 70 C IEC 60068 2 14 Damp heat test steady state Test Ca for 10 days at 40 C and humidity 93 IEC 60068 2 78 Damp heat test cyclic Test Db for 6 cycles at 25 to 55 C and humidity 93 to 95...

Page 63: ...ential protection LDRGFC Function Range or value Accuracy Operate current zero sequence current 1 100 of lBase 1 0 of Ir Operate current low current operation 1 100 of lBase 1 0 of Ir Operate voltage...

Page 64: ...r Angle at 0 degrees and 85 degrees Positive sequence resistance 0 01 1000 00 phase Zero sequence reactance 0 10 9000 00 phase Zero sequence resistance 0 01 3000 00 phase Fault resistance phase to ear...

Page 65: ...r is greater Operate time 25 ms typically IEC 60255 121 Reset ratio 105 typically Reset time at 0 1 x Zreach to 2 x Zreach Min 20 ms Max 50 ms Table 35 Phase selection quadrilateral characteristic wit...

Page 66: ...eset time at 0 5 x Zreach to 1 5 x Zreach Min 30 ms Max 50 ms Table 37 Full scheme distance protection quadrilateral for earth faults ZMMPDIS Function Range or value Accuracy Number of zones Max 5 wit...

Page 67: ...e Positive sequence reactance 0 10 3000 00 phase 2 0 static accuracy 2 0 degrees static angular accuracy Conditions Voltage range 0 1 1 1 x Ur Current range 0 5 30 x Ir Angle at 0 degrees and 85 degre...

Page 68: ...racy Conditions Voltage range 0 1 1 1 x Ur Current range 0 5 30 x Ir Angle at 0 degrees and 85 degrees Resistive reach positive sequence 0 10 1000 00 phase Reactive reach zero sequence 0 50 9000 00 ph...

Page 69: ...nce reach Ph E and Ph Ph 0 01 9000 00 ohm l Dynamic overreach 5 at 85 degrees measured with CVTs and 0 5 SIR 30 IEC 60255 121 Reset ratio 105 typically Directional blinders Forward 15 120 degrees Reve...

Page 70: ...each zone with detected difference in operating time 0 000 60 0000 s 0 2 or 15 ms whichever is greater Conditional timer for sending the CS at power swings 0 000 60 0000 s 0 2 or 15 ms whichever is gr...

Page 71: ...er NoPref Cyclic 1231c 1321c Acyclic 123a 132a 213a 231a 312a 321a Table 47 Phase preference logic PPL2PHIZ Function Range or value Accuracy Operate value phase to phase and phase to neutral undervolt...

Page 72: ...or the switch onto fault function 0 03 120 00 s 0 2 or 20 ms whichever is greater Time delay for UI detection 0 000 60 000 s 0 2 or 20 ms whichever is greater Delay time for activation of dead line de...

Page 73: ...equency 0 1 x fr 1 0 TVE Signal magnitude Voltage phasor Current phasor 0 1 1 2 x Ur 0 5 2 0 x Ir Phase angle 180 Harmonic distortion 10 from 2nd 50th Interfering signal Magnitude Minimum frequency Ma...

Page 74: ...1 10000 of lBase 1 0 of Ir at I Ir 1 0 of I at I Ir Relay characteristic angle RCA 40 0 65 0 degrees 2 0 degrees Relay operating angle ROA 40 0 89 0 degrees 2 0 degrees Second harmonic blocking 5 100...

Page 75: ...e at 0 to 2 x Iset Min 15 ms Max 25 ms Reset time at 2 x Iset to 0 Min 15 ms Max 25 ms Critical impulse time 10 ms typically at 0 to 2 x Iset Operate time at 0 to 10 x Iset Min 5 ms Max 15 ms Reset ti...

Page 76: ...and Table 182 16 curve types See Table 180 Table 181 and Table 182 Second harmonic blocking 5 100 of fundamental 2 0 of Ir Minimum polarizing voltage 1 100 of UBase 0 5 of Ur Minimum polarizing curre...

Page 77: ...80 degrees 2 0 degrees Operate current for directional release 1 100 of IBase For RCA 60 degrees 2 5 of Ir at I Ir 2 5 of I at I Ir Minimum polarizing voltage 1 100 of UBase 0 5 of Ur Real part of neg...

Page 78: ...Ur Operate time for non directional residual overcurrent at 0 to 2 x Iset Min 40 ms Max 65 ms Reset time for non directional residual overcurrent at 2 x Iset to 0 Min 40 ms Max 65 ms Operate time for...

Page 79: ...se current 5 200 of lBase 1 0 of Ir at I Ir 1 0 of I at I Ir Reset ratio phase current 95 Operate residual current 2 200 of lBase 1 0 of Ir at I Ir 1 0 of I at I Ir Reset ratio residual current 95 Pha...

Page 80: ...or value Accuracy Power level for Step 1 and Step 2 0 0 500 0 of SBase 1 0 of Sr at S Sr 1 0 of S at S Sr where 1 732 r r r S U I Characteristic angle for Step 1 and Step 2 180 0 180 0 degrees 2 0 de...

Page 81: ...current 1 0 of Ir Independent operate time delay 0 000 60 000 s 0 2 or 45 ms whichever is greater Independent reset time delay 0 010 60 000 s 0 2 or 30 ms whichever is greater Start time at current ch...

Page 82: ...181 Minimum operate time for inverse time characteristics 0 00 60 00 s 0 2 or 35 ms whichever is greater High voltage limit voltage dependent operation 30 0 100 0 of UBase 1 0 of Ur Start undervoltage...

Page 83: ...s 0 2 or 40ms whichever is greater Definite time delay step 2 at 1 2 x Uset to 0 0 000 60 000 s 0 2 or 40ms whichever is greater Minimum operate time inverse characteristics 0 000 60 000 s 0 5 or 40ms...

Page 84: ...is greater Definite time delay high step step 2 at 0 to 1 2 x Uset 0 000 60 000 s 0 2 or 45 ms whichever is greater Minimum operate time Inverse characteristics 0 000 60 000 s 0 2 or 45 ms whichever...

Page 85: ...te time start at 0 to 1 2 x Uset Min 20 ms Max 35 ms Reset time start at 1 2 x Uset to 0 Min 5 ms Max 25 ms Critical impulse time 10 ms typically at 0 to 2 x Uset Impulse margin time 15 ms typically T...

Page 86: ...ter restoration 0 000 60 000 s 0 2 or 35 ms whichever is greater Operate time delay when disconnecting all three phases 0 000 60 000 s 0 2 or 35 ms whichever is greater Time delay to block when all th...

Page 87: ...base UMin 50 150 of Ubase Exponent 0 0 5 0 tMax 0 010 60 000 s tMin 0 010 60 000 s 1 0 or 100 ms whichever is greater Exponent U UMin t tMax tMin tMin UNom UMin EQUATION1182 V1 EN Equation 3 U Umeasur...

Page 88: ...able frequency 45 00 65 00 Hz 2 0 mHz Definite restore time delay 0 000 60 000 s 0 2 or 100 ms whichever is greater Definite time delay for frequency gradient trip 0 200 60 000 s 0 2 or 120 ms whichev...

Page 89: ...ater Independent time delay undercurrent at 2 x Iset to 0 step 1 2 0 00 6000 00 s 0 2 or 35 ms whichever is greater Overcurrent non directional Start time at 0 to 2 x Iset Min 15 ms Max 30 ms Reset ti...

Page 90: ...cs see table 188 4 curve types See table 188 Undervoltage Inverse time characteristics see table 189 3 curve types See table 189 High and low voltage limit voltage dependent operation step 1 2 1 0 200...

Page 91: ...n CVGAPC continued Function Range or value Accuracy Undervoltage Critical impulse time 10 ms typically at 1 2 x Uset to 0 8 x Uset Impulse margin time 15 ms typically 1MRK 506 372 BEN Line distance pr...

Page 92: ...phase voltage 1 100 of UBase 0 5 of Ur Operate phase current 1 100 of IBase 0 5 of Ir Operate phase dead line voltage 1 100 of UBase 0 5 of Ur Operate phase dead line current 1 100 of IBase 0 5 of Ir...

Page 93: ...nd line for synchronizing 15 30 degrees 2 0 degrees Breaker closing pulse duration 0 050 1 000 s 0 2 or 15 ms whichever is greater tMaxSynch which resets synchronizing function if no close has been ma...

Page 94: ...ichever is greater Circuit breaker closing pulse duration tPulse 0 000 60 000 s 0 2 or 15 ms whichever is greater Reclaim time tReclaim 0 00 6000 00 s 0 2 or 15 ms whichever is greater Maximum wait ti...

Page 95: ...f NoRestart Restart Table 81 Phase segregated scheme communication logic for distance protection ZC1PPSCH Function Range or value Accuracy Scheme type Intertrip Permissive UR Permissive OR Blocking Co...

Page 96: ...able 85 Local acceleration logic ZCLCPSCH Function Range or value Accuracy Operate current LoadCurr 1 100 of IBase 1 0 of Ir Operate current MinCurr 1 100 of IBase 1 0 of Ir Delay time on pick up for...

Page 97: ...Base 0 5 of Ur Absolute hysteresis 0 00 50 0 of UBase 0 5 of Ur at U Ur 0 5 of U at U Ur Critical impulse time undervoltage 10 ms typically at 1 2 x Uset to 0 8 x Uset Impulse margin time undervoltage...

Page 98: ...margin time negative sequence overvoltage 15 ms typically Independent time delay to operate at 0 to 1 2 x Uset 0 000 120 000 s 0 2 or 40 ms whichever is greater Table 92 Zero sequence overvoltage prot...

Page 99: ...00 60 000 s 0 2 or 35 ms whichever is greater Transient overreach start function 10 at 100 ms Table 94 Zero sequence overcurrent protection LCZSPTOC Function Range or value Accuracy Operate value zero...

Page 100: ...ay to operate at 0 to 2 x Iset 0 000 60 000 s 0 2 or 30 ms whichever is greater Table 96 Three phase undercurrent LCP3PTUC Function Range or value Accuracy Operate value undercurrent 1 00 100 00 of IB...

Page 101: ...APC instances Function Quantity with cycle time 3 ms 8 ms 100 ms SMAGAPC 12 Table 100 Number of STARTCOMB instances Function Quantity with cycle time 3 ms 8 ms 100 ms STARTCOMB 32 Table 101 Number of...

Page 102: ...00 ms LLD 10 10 20 Table 109 Number of OR instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms OR 78 60 160 Table 110 Number of PULSETIMER instances Logic block Quantity with cycle time Ran...

Page 103: ...instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms INDCOMBSPQT 10 10 Table 117 Number of INDEXTSPQT instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms INDEXTSPQT 10 10 Table...

Page 104: ...ERSETQT instances Logic block Quantity with cycle time Range or Value Accuracy 3 ms 8 ms 100 ms TIMERSETQT 10 30 0 000 90000 000 s 0 5 10 ms Table 125 Number of XORQT instances Logic block Quantity wi...

Page 105: ...on and overflow supervision TEIGAPC Function Cycle time ms Range or value Accuracy Elapsed time integration 3 0 999999 9 s 0 2 or 20 ms whichever is greater 8 0 999999 9 s 0 2 or 100 ms whichever is g...

Page 106: ...of Q Apparent power S 10 to 300 V 0 1 4 0 x Ir 0 5 of Sr at S 0 5 x Sr 0 5 of S at S 0 5 x Sr 100 to 220 V 0 5 2 0 x Ir 0 2 of S Power factor cos 10 to 300 V 0 1 4 0 x Ir 0 02 100 to 220 V 0 5 2 0 x I...

Page 107: ...0 5 Ir I 4 0 Ir Table 140 Voltage sequence measurement VMSQI Function Range or value Accuracy Voltage positive sequence U1 10 to 300 V 0 5 of U at U 50 V 0 2 of U at U 50 V Voltage zero sequence 3U0...

Page 108: ...Hz Sampling rate 1 kHz at 50 Hz 1 2 kHz at 60 Hz Recording bandwidth 5 300 Hz Table 143 Insulation supervision for gas medium function SSIMG Function Range or value Accuracy Pressure alarm level 1 00...

Page 109: ...or value Accuracy Alarm level for open and close travel time 0 200 ms 3 ms Alarm level for number of operations 0 9999 Independent time delay for spring charging time alarm 0 00 60 00 s 0 2 or 30 ms...

Page 110: ...of analog inputs 40 Maximum number of binary inputs 352 Maximum number of disturbance reports 100 Maximum total recording time 3 4 s recording time and maximum number of channels typical value 340 se...

Page 111: ...time for report of counter value 1 3600 s Table 155 Function for energy calculation and demand handling ETPMMTR Function Range or value Accuracy Energy metering kWh Export Import kvarh Export Import...

Page 112: ...unication speed for the IEDs 300 38400 Bd Table 157 IEC 61850 9 2 communication protocol Function Value Protocol IEC 61850 9 2 Communication speed for the IEDs 100BASE FX Table 158 LON communication p...

Page 113: ...typically Fiber diameter Glass fiber 62 5 125 mm Plastic fiber 1 mm depending on optical budget calculation Table 163 Galvanic RS485 communication module Quantity Range or value Communication speed 2...

Page 114: ...6 dB typical distance 110 km 68 mile Graded index multimode 50 125 mm 9 dB typical distance about 2 km 1 mile Optical connector Type ST Type FC PC Type FC PC Protocol C37 94 C37 94 implementation C37...

Page 115: ...at occasionally a temporary conductivity caused by condensation is to be expected Connection system Table 170 CT and VT circuit connectors Connector type Rated voltage and current Maximum conductor ar...

Page 116: ...3 Optional Ethernet connection type SFP Optical LC Carrier modules supported OEM LDCM Table 173 OEM Number of Ethernet ports OEM 2 Ethernet Ports Ethernet connection type SFP Optical LC 1MRK 506 372...

Page 117: ...C Transparent Clock TC Accuracy According to standard IEC IEEE 61850 9 3 Number of nodes According to standard IEC IEEE 61850 9 3 Ports supported All rear Ethernet ports Table 177 GPS time synchroniza...

Page 118: ...ted low level high level 1 3 Vpp 3 x low level max 9 Vpp Supported formats IRIG B 00x IRIG B 12x Accuracy 10 s for IRIG B 00x and 100 s for IRIG B 12x Input impedance 100 k ohm Optical connector Optic...

Page 119: ...2 0 or 40 ms whichever is greater ANSI Extremely Inverse A 28 2 B 0 1217 P 2 0 tr 29 1 ANSI Very inverse A 19 61 B 0 491 P 2 0 tr 21 6 ANSI Normal Inverse A 0 0086 B 0 0185 P 0 02 tr 0 46 ANSI Moderat...

Page 120: ...TR t k I CR EQUATION1253 SMALL V1 EN I Imeasured Iset k 0 05 999 in steps of 0 01 A 0 005 200 000 in steps of 0 001 B 0 00 20 00 in steps of 0 01 C 0 1 10 0 in steps of 0 1 P 0 005 3 000 in steps of 0...

Page 121: ...set ANSI IEEE C37 112 5 0 or 160 ms whichever is greater ANSI Extremely Inverse A 28 2 B 0 1217 P 2 0 tr 29 1 ANSI Very inverse A 19 61 B 0 491 P 2 0 tr 21 6 ANSI Normal Inverse A 0 0086 B 0 0185 P 0...

Page 122: ...TR t k I CR EQUATION1253 SMALL V1 EN I Imeasured Iset k 0 05 999 in steps of 0 01 A 0 005 200 000 in steps of 0 001 B 0 00 20 00 in steps of 0 01 C 0 1 10 0 in steps of 0 1 P 0 005 3 000 in steps of 0...

Page 123: ...0 P 0 02 tr 4 85 ANSI Long Time Extremely Inverse A 64 07 B 0 250 P 2 0 tr 30 ANSI Long Time Very Inverse A 28 55 B 0 712 P 2 0 tr 13 46 ANSI Long Time Inverse A 0 086 B 0 185 P 0 02 tr 4 6 Table 187...

Page 124: ...IECEQUATION2423 V2 EN k 0 05 1 10 in steps of 0 01 Type C curve 3 0 480 0 035 32 0 5 n k t U U U IECEQUATION2421 V1 EN k 0 05 1 10 in steps of 0 01 Programmable curve P k A t D U U B C U EQUATION1439...

Page 125: ...80 0 055 32 0 5 k t U U U EQUATION1432 SMALL V1 EN U Uset U Umeasured k 0 05 1 10 in steps of 0 01 Programmable curve P k A t D U U B C U EQUATION1433 SMALL V1 EN U Uset U Umeasured k 0 05 1 10 in ste...

Page 126: ...EQUATION1437 SMALL V2 EN k 0 05 1 10 in steps of 0 01 Type C curve 3 0 480 32 0 5 0 035 t k U U U EQUATION1438 SMALL V2 EN k 0 05 1 10 in steps of 0 01 Programmable curve P k A t D U U B C U EQUATION1...

Page 127: ...KKXXHKKLAGXSY Product definition Differential protection REL670 2 2 F00 X00 A 0 0 0 0 0 0 0 0 0 0 0 0 0 Impedance protection B 1 0 0 0 0 Current protection C 00 0 00 1 0 0 0 0 0 Voltage protection Fre...

Page 128: ...ifferential protection single phase HZPDIF 1MRK005904 HB 6 0 3 Additional security logic for differential protection LDRGFC 1MRK005904 TA 15 0 1 Table 197 Impedance protection Position 1 2 3 4 5 6 7 8...

Page 129: ...ngs for PP and PE Directional impedance quadrilateral ZDRDIR 1MRK005907 BA 2 1 2 Distance measuring zone quad characteristic separate Ph Ph and Ph E settings ZMRPDIS ZMRAPDIS 1MRK005907 NA 12 1 5 Phas...

Page 130: ...strained overcurrent protection VRPVOC 1MRK005910 XA 21 0 3 Table 201 Voltage protection Position 1 2 3 4 5 6 7 8 D 0 1 Table 202 Voltage functions Function Function identification Ordering no Positio...

Page 131: ...of control functionality can be ordered Control functionality for a single bay max 15 objects 2CB including interlocking APC15 1MRK005917 BZ 6 0 1 Table 213 Scheme communication Position 1 2 3 4 5 6...

Page 132: ...rocess bus communication 8 merging units 1MRK005933 HA 1 0 1 IEC 62439 3 Parallel redundancy protocol PRP 1MRK005932 FA 2 0 1 PRP or HSR require two SFPs placed in pairs IEC 62439 3 High availability...

Page 133: ...ted Table 224 Power supply module selection Power supply module Ordering no Selection Notes and rules Compression terminals 1MRK002960 GA C Ringlug terminals 1MRK002960 HA R Power supply module 24 60...

Page 134: ...terminals 1MRK002247 BD B4 B4 TRM 5I 1A 4I 5A 3U 110 220V 50 60Hz ring lug terminals 1MRK002247 BF B5 B5 TRM 6I 1A 6U 110 220V 50 60Hz ring lug terminals 1MRK002247 AC B6 B6 TRM 6I 5A 6U 110 220V 50...

Page 135: ...P15 1 1 x 19 rack casing two 2 TRM 5 5 4 4 5 possible locations P3 P5 P7 P9 P11 3 4 x 19 rack casing one 1 TRM 4 4 4 4 4 possible locations P3 P5 P7 P9 3 4 x 19 rack casing two 2 TRM 2 2 2 2 2 possibl...

Page 136: ...C1 C1 C1 C1 C1 BIM 16 inputs RL110 110 125VDC 50mA 1MRK000508 BD D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 BIM 16 inputs RL220 220 250VDC 50mA 1MRK000508 CD E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 B...

Page 137: ...2 outputs RL110 110 125VDC 50mA 1MRK000173 BD W W W W W W W W W W W W W W IOM with MOV 8 inputs 10 2 outputs RL220 220 250VDC 50mA 1MRK000173 CD Y Y Y Y Y Y Y Y Y Y Y Y Y Y mA input module MIM 6 chann...

Page 138: ...e the Optical Ethernet module in P30 6 Optical Ethernet module 1MRK002266 EA H Serial SPA LON DNP IEC 60870 5 103 plastic interface 1MRK001608 AB L Serial SPA LON DNP IEC 60870 5 103 plastic glass int...

Page 139: ...n High impedance differential protection 3 blocks 1MRK004001 AB A02 Only for A42 B42 D42 Phase segregated scheme communication 1MRK004001 BE B05 Pole slip protection 1MRK004001 VU B24 Only for A42 B42...

Page 140: ...mounting kit for 3 4 x 19 case or 3xRHGS6 1MRK002420 BA B 19 rack mounting kit for 1 1 x 19 case 1MRK002420 CA C Wall mounting kit 1MRK002420 DA D Wall mounting not recommended with communication modu...

Page 141: ...0 220V 50 60Hz compression terminals 1MRK002247 AP A12 TRM 7I 5A 5U 110 220V 50 60Hz compression terminals 1MRK002247 AR A13 TRM 3I 5A 3I 1A 6U 110 220V 50 60Hz compression terminals 1MRK002247 AE A16...

Page 142: ...C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 BIM 16 inputs RL110 110 125VDC 50mA 1MRK000508 BD D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 BIM 16 inputs RL220 220 250VDC 50mA 1MRK000508 CD E1 E1 E1 E1 E1 E...

Page 143: ...puts 10 2 outputs RL110 110 125VDC 50mA 1MRK000173 BD W W W W W W W W W W W W W W IOM with MOV 8 inputs 10 2 outputs RL220 220 250VDC 50mA 1MRK000173 CD Y Y Y Y Y Y Y Y Y Y Y Y Y Y mA input module MIM...

Page 144: ...et module 1MRK002266 EA H Serial SPA LON DNP IEC 60870 5 103 plastic interface 1MRK001608 AB L Serial SPA LON DNP IEC 60870 5 103 plastic glass interface 1MRK001608 BB M Serial SPA LON DNP IEC 60870 5...

Page 145: ...rdering number RK926 315 AK Single breaker Single or Three Phase trip with external neutral on current circuits ordering number RK926 315 AC Multi breaker Single or Three Phase trip with internal neut...

Page 146: ...ads with 10 A Combiflex socket on one end must be used Mounting kit Ordering number Side by side mounting kit Quantity 1MRK 002 420 Z Configuration and monitoring tools Front connection cable between...

Page 147: ...IEC Quantity 1MRK 511 393 UEN Communication protocol manual IEC 60870 5 103 IEC Quantity 1MRK 511 394 UEN Communication protocol manual LON IEC Quantity 1MRK 511 395 UEN Communication protocol manual...

Page 148: ...peration manual IEC 1MRK 500 127 UEN ANSI 1MRK 500 127 UUS Engineering manual IEC 1MRK 511 398 UEN ANSI 1MRK 511 398 UUS Installation manual IEC 1MRK 514 026 UEN ANSI 1MRK 514 026 UUS Communication pr...

Page 149: ...149...

Page 150: ...AB Grid Automation Products 721 59 V ster s Sweden Phone 46 0 21 32 50 00 abb com protection control Copyright 2017 ABB All rights reserved Specifications subject to change without notice 1MRK 506 372...

Reviews: