background image

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

                                                     

ablerex MSII-RT 

 
 
 

Parallel Redundancy On-Line UPS 

User’s Manual 

 
 
 
 
 
 
 

6Kva 

 

1

Table of Contents 

 

 

1.

 

Important Safety Instruction....................................................................2

 

1.1.

 

An Important Notice................................................................................2

 

1.2.

 

Storage Instruction .................................................................................4

 

2.

 

Product Introduction ...............................................................................5

 

2.1.

 

General Characteristics ..........................................................................5

 

2.2.

 

Symbols on the LCD Display Panel .......................................................7

 

2.3.

 

Panel explanation ...................................................................................9

 

2.4.

 

Communication Port Explanation .........................................................11

 

3.

 

Installation and Operation.....................................................................12

 

3.1.

 

Unpacking.............................................................................................12

 

3.2.

 

Selecting Installation Position...............................................................13

 

3.3.

 

Installation of Casters Cover ................................................................14

 

3.4.

 

Terminal Block Explanation ..................................................................20

 

3.5.

 

Operation Test and Installation Instruction...........................................27

 

4.

 

Troubleshooting Guide .........................................................................38

 

4.1.

 

Trouble Shooting ..................................................................................38

 

5.

 

Bundled Software Installation Guide ....................................................40

 

5.1.

 

Hardware Installation............................................................................40

 

5.2.

 

Software Installation .............................................................................40

 

6.

 

Customer Options Slots........................................................................41

 

6.1.

 

All the below interface cards are with built-in EPO function.................41

 

6.2.

 

R2E(2nd RS-232 ) card ........................................................................41

 

6.3.

 

RSE(RS-485) card................................................................................41

 

6.4.

 

USE(USB) card ....................................................................................41

 

6.5.

 

DCE(Dry Contact) card.........................................................................42

 

6.6.

 

SNMP Cards.........................................................................................43

 

6.7.

 

The Installation of those Interface Cards..............................................43

 

7.

 

Hot Swappable Battery Replacement ..................................................45

 

8.

 

Specifications .......................................................................................47

 

 
 

Summary of Contents for MSII-RT

Page 1: ... Position 13 3 3 Installation of Casters Cover 14 3 4 Terminal Block Explanation 20 3 5 Operation Test and Installation Instruction 27 4 Troubleshooting Guide 38 4 1 Trouble Shooting 38 5 Bundled Software Installation Guide 40 5 1 Hardware Installation 40 5 2 Software Installation 40 6 Customer Options Slots 41 6 1 All the below interface cards are with built in EPO function 41 6 2 R2E 2nd RS 232 ...

Page 2: ... 3 months if unused If this is not done then the warranty will be null and void When installed and being used the batteries will be automatically recharged and kept in top condition 1 1 17 This UPS supports electronic equipment in offices telecommunications process control medical and security applications Non authorized technician is not allowed to install the UPS in the following areas a Medical...

Page 3: ...ility Status and UPS Abnormal status in the mean while the LCD display may show Input Output Voltage Frequency Load Status Inner cabinet temperature and Abnormal Phenomenon 2 1 4 To protect the unit from overloading it automatically switches to bypass mode in 160 seconds 40ms if loading is at 105 150 of rating and in case of overloading at 150 of rating it switches to bypass mode immediately It wi...

Page 4: ... LCD screen directly which may reduce down unnecessary repair task a lot 7 2 2 Symbols on the LCD Display Panel Item Symbol Description 1 LINE Utility or Bypass Source 2 Battery Low 3 Battery Abnormal 4 UPS Overloading 5 UPS Working in specified mode 6 A Blackout Transfer occurred in UPS Output 7 Bypass Input Abnormal UPS fails to transfer to bypass Bypass Abnormal at ECO mode 8 Utility Input Abno...

Page 5: ...ypass input 33 Er Other Error code The specified modes include Normal mode ECO mode CVCF mode etc 9 2 3 Panel explanation 2 3 1 Front Panel Function Explanations LCD Display Green LED steadily lights up to indicate that the Utility input voltage is within the window the LED flashes flickeringly to indicate that the Utility input voltage is within the acceptable window Green LED lights up to indica...

Page 6: ...us EPO as well as SNMP card you may combine them according to your demand However the R2E card RSE card and USE card are prohibited to be used Simultaneously The bundled software of the UPS is compatible with many operating systems such as Windows 98 2000 ME NT and XP For other applications like Novell NetWare Unix Linux please contact your local distributor for a proper solution When the optional...

Page 7: ...0R 3 1 5 Package for the Isolation Transformer without Maintenance Bypass Switch 3pcs additional No 10 AWG 60 C copper wire p s 2pcs 12 inches long NEMA L5 30P and 1pcs 12 inches long NEMA L5 30R are to be used at the input output terminal block of the UPS Please refer to Chapter 0 for installation 13 3 2 Selecting Installation Position It is necessary to select a proper environment to install the...

Page 8: ...ule Step1 Installation of the Foot Covers of the Power Module Step2 Installation of the Power Module and the Battery Module 15 3 3 1 2 Power Module Isolation Transformer Module Battery Module Step1 Installation of the Power Module Isolation Transformer Module and Battery Module ...

Page 9: ... 3 3 2 1 Power Module Battery Module Step1 Installation of the Ear Covers 17 Step2 Installation of the Ear Covers to Power Module Isolation Transformer Module and Battery Module Step3 Installation of the Rail kit to Rack Cabinet ...

Page 10: ...e Power Module to the Rack Cabinet 19 3 3 2 2 Power Module Isolation Transformer Module Battery Module Step1 Installation of the Isolation Transformer Module to the Rail Step2 Installation of the Power Module to the Rack Cabinet ...

Page 11: ...Output G2 the terminal for UPS Output Ground Remarks 1 When the Isolation transformer and Maintenance Bypass Switch are not installed a For 200 220 230 240Vac system you may connect as shown in below 1a1 1a2 21 2 When the Maintenance Bypass Switch is installed 2a1 2a2 3 When the Isolation transformer and Maintenance Bypass Switch are installed a For 200 220 230 240Vac system you may connect as sho...

Page 12: ...0 110 115 120Vac system you may connect as shown in below 23 b c For 200 100Vac 220 110Vac 230V 115Vac or 240 120Vac system You may connect as shown in below c d For 240 208 120Vac system you may connect as shown in below ...

Page 13: ...Bypass Switch isn t installed a For 200 220 230 240Vac system you may connect as shown in below 4a1 25 4a2 b For 100 110 115 120Vac system you may connect as shown in below b c For 200 100Vac 220 110Vac 230V 115Vac or 240 120Vac system You may connect as shown in below ...

Page 14: ... Breaker of the distribution panel and the breaker of the UPS Utility Inputs and then the UPS starts up Green LEDs light up to show the Utility and Bypass Inputs are normal and the LCD display will illustrate from drawing A to drawing B A B 3 5 1 5 Then the UPS is on Bypass Mode now and it will proceed self test automatically If there is no abnormal message occurred it means the pre startup of the...

Page 15: ...at least 1 set 20pcs of 12V 7AH or 12V 5AH batteries 3 5 2 2 Push the UPS On Switch to awake the UPS for approx 3 seconds and then the buzzer sounds twice The LCD display will illustrate from drawing A to drawing G and keep awake for approx 10 seconds 3 5 2 3 Press the UPS On Switch of the UPS again for about 3 seconds till the LCD display illustrates from drawing G to drawing H then the UPS will ...

Page 16: ...s Input Æ Drawing J Frequency from Utility Input ÆDrawing K Frequency from Bypass Input ÆDrawing L UPS Output Voltage ÆDrawing M UPS Output Frequency ÆDrawing N UPS Output Load ÆDrawing O UPS Battery Voltage ÆDrawing P UPS Inner Temperature I1 It shows voltage comes from Bypass Input J It shows frequency from Utility Input K It shows frequency from Bypass Input 31 L It shows UPS output Voltage M I...

Page 17: ... Drawing Q1 buzzer Æ Drawing R1 Self test ÆDrawing S1 Bypass Voltage Windows Æ Drawing T Output Frequency Synchronization Window ÆDrawing U Inverter Output Voltage ÆDrawing V1 UPS Operation Mode ÆDrawing W Output Voltage Micro Tune Value ÆDrawing X UPS Id ÆDrawing Y No of UPS in Parallel R1 It shows self test is NOT on 33 R2 It shows self test is On S1 It shows Bypass Voltage is adjusted to narrow...

Page 18: ...5 4 3 Press scroll up key pad you may execute special functions The Functions includes buzzer ON as drawing Q1 or buzzer OFF as drawing Q2 Alarm silence for UPS Warning and self test OFF As drawing R1 or self test ON as drawing R2 UPS will execute battery test for 10 seconds If the self test is successful it will show as Drawing E1 otherwise it will show as drawing E2 error message in the same tim...

Page 19: ...elf in OFF position as shown in drawing AA and a abnormal message will show in the LCD screen 3 5 6 2 To release the UPS lock please check those error messages shown in Chapter 2 2 to trouble shoot the problem of the UPS Otherwise consult your local distributor for service Press Off key pad for 5 seconds and buzzer will sound twice Turn Off the Breaker of Utility Input The UPS lock problem is solv...

Page 20: ...otherwise consult your local distributor right away 2 Remove some uncritical load at the UPS output end If any damage of the coating of AC power cord please replace a new one 3 Remove the short circuit occurred at the EPO terminal 4 Remove the objects blocked onto the ventilation holes 5 Make sure the UPS is operated normally If it is on CVCF mode you have to turn off and turn on the UPS again 6 W...

Page 21: ...ts of the EPO are 1 Æ EPO 2 Æ Ground 6 1 1 To enable the EPO function please short Pin 1 2 6 2 R2E 2nd RS 232 card 6 2 1 CN1 is for RS232 DB9 and CN3 is for EPO 6 2 2 For communication protocol please refer to Chapter 2 4 1 6 2 3 Installation Position slot1 or slot 2 6 2 4 Adapted flat cable cable A or cable B 6 2 5 For installation please refer to Chapter 6 7 6 3 RSE RS 485 card 6 3 1 CN1 for EPO...

Page 22: ...own function please short Pin 8 10 6 5 4 Adapted flat cable cable A or cable B 6 5 5 For installation please refer to Chapter 6 7 1 Æ VCC 5V 2 Æ D 3 Æ D 4 Æ Ground 43 1 6 6 SNMP Cards 6 6 1 SNMP WEB card For installation please refer to the user s manual attached with the card Installation Position slot1 or slot 2 Adapted flat cable cable A or cable B For installation please refer to Chapter 6 7 6...

Page 23: ...5 7 Hot Swappable Battery Replacement 1 Remove the screw covers as well as screws as shown in Step 1 2 Remove the front panel as indicated in Step 2 3 Remove the screws of the battery module as shown in Step 3 ...

Page 24: ...ad Frequency Stability 0 2 Free Running Frequency Regulation 1 3 Transfer Time 0ms Efficiency AC to AC Normal Up to 90 Efficiency AC to AC ECO Up to 97 Autonomy 12 min 8 min DC Start Yes BATTERY Type Sealed Lead Acid Maintenance Free 7AH Quantity 20pcs Voltage 240Vdc Recharge Time 4 hours to 90 DISPLAY Status On LED LCD Line Mode Backup Mode ECO Mode Bypass Supply Battery Low Battery Bad Disconnec...

Page 25: ...ass Switch 41kgs ENVIRONMENT Operating Temperature 0 C to 40 C Temperature Warning The battery design life is based on a temperature of 25 C Ambient temperature above this range will reduce battery life Altitude 0 2000m up to 40 C 3000m up to 35 C Humidity 90 RH Maximum Non Condensing Noise 50dB at 1 meter COMPUTER INTERFACE Interface Type Standard RS232 Interface Communication Slots 2nd RS232 EPO...

Page 26: ...50 51 192321142000000 ...

Reviews: