TAURUS Series  

10-80 kVA UPS 

Installation and Operation Manual 

Summary of Contents for TAURUS 10 kVA

Page 1: ...TAURUS Series 10 80 kVA UPS Installation and Operation Manual...

Page 2: ...Connections 33 2 6 UPS Parallel Connections 37 3 Operation Descriptions 42 3 1 Operating Mode 42 3 2 Online Operations 43 3 3 Manual Bypass Operation 43 3 4 Operation Processes 44 4 Control Panel Ope...

Page 3: ...nd to provide instructions for its safe operation The manual also provides troubleshooting assistance should an abnormal message or behavior occur Should an abnormal message not covered in this manual...

Page 4: ...nd fully discharged If the UPS is not discharged the UPS will switch to battery power after grid power is disconnected and pose an electrocution hazard 7 Do not place any objects liquid containers or...

Page 5: ...ss input for dual inputs application The system blockdiagram is shown as below 1E Input Switch A 5E Inverter A 2E Bypass Switch A 6E Static Switch A 3E Manual Bypass Switch A 7E Charger Booster A 4E R...

Page 6: ...1 2 UPS Outlook View 10 40kVA Front View 1 2 4 3 A 1E Control Panel with Colorful LCD Touch Screen A 3E Ventilation Grille A 2E Handle with Lock A 4E Wheels for Handling 4 192321262008007...

Page 7: ...10 20kVA Right Side View 1 A 1E Through Hole for Parallel Communication Cable 5 192321262008007...

Page 8: ...or Setting Switch for Parallel Communication A 6E Status LED Indictors A 7E EPO A 8E Backfeed Protection A 9E MBP Detector A 10E Communication Card Slot1 A 11E Communication Card Slot2 Please find the...

Page 9: ...10kVA 20kVA A 1E X10 X40 Mains Bypass Input Connections Terminal 1N 2N 1L3 2L3 1L2 2L2 1L1 2L1 A 2E X50 Output Connections Terminal 3N 3L3 3L2 3L1 A 3E X20 External Battery Connections Terminal B N B...

Page 10: ...30 40kVA Right Side View 1 A 1E Through Hole for Parallel Communication Cable 8 192321262008007...

Page 11: ...or Setting Switch for Parallel Communication A 6E Status LED Indictors A 7E EPO A 8E Backfeed Protection A 9E MBP Detector A 10E Communication Card Slot1 A 11E Communication Card Slot2 Please find the...

Page 12: ...3 1 2 30kVA 40kVA A 1E X10 X40 Mains Bypass Input Connections Terminal 1N 2N 1L3 2L3 1L2 2L2 1L1 2L1 A 2E X50 Output Connections Terminal 3N 3L3 3L2 3L1 A 3E X20 External Battery Connections Terminal...

Page 13: ...VA Front View 1 2 3 1 2 3 A 1E Control Panel with Colorful LCD Touch Screen A 3E Ventilation Grille A 2E Handle with Lock A 4E Wheels for Handling Wheel Type Stationary Type Without Wheel 11 192321262...

Page 14: ...60 80kVA Left Side View A 1E Through Hole for Parallel Communication Cable 1 1 Wheel Type Stationary Type Without Wheel 12 192321262008007...

Page 15: ...ctions Terminal 3N 3L3 3L2 3L1 A 1E Parallel Communication Ports A 2E HMICommunicationPort A 3E Communication Selector for Service Only A 4E USB Port for Service Only A 5E Terminal Resistor Setting Sw...

Page 16: ...A 4E Output Input Contacts A 2E SD Card Slot A 5E RS 232 Port for Setting Software A 3E External Battery Temperature Connector A 6E CommunicationPort for Remote Panel Please find the detail descriptio...

Page 17: ...o prevent arcing injuryand fire hazards Avoid using dusty materials volatile gases or corrosive substances with a high salt content in the environment where the UPS is installed The installation locat...

Page 18: ...ing and removing processes for wheel type Remove the packing materials and cut straps Remove the cardboard box 10 40kVA 60 80kVA Unscrew the fasteningrail kits on the front and rear side of 10 40kVA a...

Page 19: ...Put 2 fasteningrail kits on the pallet edge and make them steady by fastening 4 screws in the pallet 10 40kVA 60 80kVA 17 192321262008007...

Page 20: ...Raise 2 wheel brakes or expansion foots for remove the UPS from the pallet 10 40kVA 60 80kVA Wheel Brake Wheel Brake 18 192321262008007...

Page 21: ...Block 2wheel brakes or adjust the expansion foots to fix the UPS 10 40kVA 60 80kVA Wheel Brake Wheel Brake 19 192321262008007...

Page 22: ...Floor Fixing for 10 40kVA It is possible to reuse the fasteningrail kits to fix the UPS to the floor 20 192321262008007...

Page 23: ...Floor Fixing for 60 80kVA Stationary Type Without Wheel 21 192321262008007...

Page 24: ...Floor Fixing for 60 80kVA Wheel Type It is possible to reuse the fasteningrail kits to fix the UPS to the floor 22 192321262008007...

Page 25: ...east 1000 mm of free space in front of the UPS for air flow and future maintenance purposes Keep at least 300mmof free space in rear of the UPS for air flow space Keep at least 500mm of free space in...

Page 26: ...Power Cable Sizing The drawing below shows the positions of power terminals Mains X10 Bypass X40 Output Battery 10kVA Power Terminal Positions Mains X10 Bypass X40 Output Battery 20kVA Power Terminal...

Page 27: ...10 Bypass X40 Output Battery 30kVA Power Terminal Positions Mains X10 Bypass X40 Output Battery 40kVA Power Terminal Positions 60 80kVA Power Terminal Positions Output Mains Bypass Battery 25 19232126...

Page 28: ...operating at rated voltage rated power and batteries are charging but regardless of the overload 2 The UPS is operating at rated voltage and rated power but regardless of the overload 3 12Vbattery bl...

Page 29: ...60kVA 60kW 185 A 160 A 80kVA 80kW 250 A 210 A 400 V 10kVA 10kW 30 A 25 A 20kVA 20kW 60 A 50 A 30kVA 30kW 90 A 75 A 40kVA 40kW 120 A 100 A 60kVA 60kW 175 A 150 A 80kVA 80kW 240 A 200 A 415 V 10kVA 10k...

Page 30: ...Electrical System Connections UPS with single Input Load 3P N UPS with single input and isolation transformer Load 3P 3P N UPS with dual inputs Load 3P N 3P N 28 192321262008007...

Page 31: ...nputsand isolation transformer Load 3P 3P N 3P 3P N Load 3P N 3P 3P N Load 3P 3P N 3P N Note You have to install an isolation transformer on one of the inputs if the two power system are different 29...

Page 32: ...UPS in parallel use separate battery Load 3P N UPS in parallel use common battery Load 3P N 30 192321262008007...

Page 33: ...UPS in parallel with output transformer Please donot useseparateoutput transformer for each UPS A common output transformer is recommended Load 3P N Load 3P N 31 192321262008007...

Page 34: ...erter Mode Please do not connect the bypass input Load 3P N Load 3P N Note Up to 6 units can be operated in parallel for Converter Mode operation and common battery function is available 32 1923212620...

Page 35: ...2 5 Communication Cables Connections 10 20kVA 30 40kVA 60 80kVA 33 192321262008007...

Page 36: ...HMI port is workable USB This port is for service only LED Status Indictors Normal The UPS is normal Alarm The UPS has some abnormal conditions EPO Emergence Power Off This EPO contact allows you to t...

Page 37: ...re the SW2 switch to correct position when this slot is used USB Complies with USB V 2 0 12 Mbps Pin Assignment This port is available for change the setting of UPS by setting software Batt Temp Exter...

Page 38: ...e UPS provides 3 output dry contacts and1 input contact Specification of Output dry contact 250 VAC 2 A 30 VDC 2 A There have 3 jumpers J1 J3 to set NC NO for each output contact To short the input co...

Page 39: ...configuration must be performed by authorized and qualified technicians who are familiar with this UPS Parallel communication cables are requested to connect to UPS each other Please only use the par...

Page 40: ...When installing the parallel communication cables please let the parallel communication cable through the hole at side of UPS as shown below 38 192321262008007...

Page 41: ...Recommended 1 1 parallel system configuration Mains Load Mains Bypass Load 1 1 parallel Single Input 1 1 parallel Dual Input Parallel Communication Cables 39 192321262008007...

Page 42: ...Recommended N 1 parallel for single input system configuration Up to 6 UPS Units Load Mains External Manual Bypass Switch Parallel Communication Cables 40 192321262008007...

Page 43: ...Recommended N 1 parallel for dual input system configuration Up to 6 UPS Units Load Mains External Manual Bypass Switch Bypass Parallel Communication Cables 41 192321262008007...

Page 44: ...setup as VFI Mode Inverter is also kept ready to switch power supply modes at any time If VFI mode is set then power can be quickly routed from Bypass to Inverter Attention In ECO Mode the power supp...

Page 45: ...wer supply circuit switches from Inverter to the bypass output Battery Mode When the UPS detects a failure in the main power supply then power is provided from the battery instead The touch screen at...

Page 46: ...tch fuses before start up the rectifier of UPS if the UPS don t install optional DC Cold Start Kit 1 Close UPS Mains Input and Bypass Input Switches 2 Select Command Operation Normal mode on LCD displ...

Page 47: ...e battery line switch fuses to connect the batteries after rectifier turn on 5 The inverter will be started and supply output voltage 6 Close UPS Output Switch to supply the power to the load 45 19232...

Page 48: ...maintenance bypass 1 Select Command Operation Shutdown converter except bypass on LCD display 2 The Inverter will be shutdown and bypass will supply the power to the load 3 Open the Main Input and Ba...

Page 49: ...rent and battery information from the touch panel Please refer to below section for learn more detail information and functions of the LCD touch panel 4 1 Screen Introduction A Display current time st...

Page 50: ...ch to other menu page and click the menu icon to enter to the desire function Click to hide show the sub menu The button below will appear on some function pages Button Function Click it to save the n...

Page 51: ...attery Test Battery Test Turn off the battery test Monitor Identification Display UPS information Real Time Information Display real time measurements of input output bypass and battery Maintenance Co...

Page 52: ...the turn off time of LCD backlight Date and Time Set date and time Peripherals 1 Set communication card Parameters 1 UPS parameters which can be modified Event Log Display the event log list of UPS Lo...

Page 53: ...nter in the Setting Icon then tap the blue row to see additional Parameters Use the login password Default is 3366 then press enter Now you are able to modify the UPS parameters be sure that the conve...

Page 54: ...voltage V cell 1 600 1 800 1 600 Battery test 2 minutes Yes No Yes Output Output voltage 220 230 240 230 Output frequency 50 60 50 Fine adjustment voltage 8 8 0 Transformer Input transformer No Mains...

Page 55: ...Click D E F to change the measure parameter and press for 3 seconds to enter to Real Time Information G Display the status of battery Press it for 3 second to enter to Real Time Information The batter...

Page 56: ...le and user can change the definition for each contact Please refer to Dry Contact Card manual for more detail 5 2 RS 485 MODBUSCard RS 485 ports with JBUS MODBUS protocol Please refer to RS 485 Card...

Page 57: ...s input 5 6 Parallel Communication Cable The parallel communication cablesare required when UPS in parallel Each UPS provides a 1 5 meters parallel communication cable as standard and it can use for 2...

Page 58: ...e UPS Click to have an alarm list as below picture We recommend checking the error code using the following method when troubleshooting Click Monitor Maintenance Code to bring up the screen shown belo...

Page 59: ...nuously with alarm Parallel Up to 6 units Bypass Voltage 380 400 415V 3 Phase N Voltage Tolerance Preventive range 10 Adjustable 5 15 Critical range 25 Adjustable 16 30 Frequency 50 60Hz Frequency Tol...

Page 60: ...haracteristics Dimensions W x D x H mm 440 x 860 x 1390 Wheel type 600 x 827 x 1253 w o wheel 600 x 827 x 1345 Wheel type Weight 84 kg 86 kg 130kg 132kg 194kg w o wheel 200kg Wheel type 204kg w o whee...