I0000816

FIGURE 1: 

ENCLOSURE

HAZARDOUS ROOM SERIES

Installation & Operation Instructions

Phone:

 1-888-967-5224

Website:

 workaci.com

3.09"

(78.59 mm)

3.09"

(78.59 mm)

SEAL FITTING

PRECAUTIONS
• DO NOT RUN THE WIRING IN ANY CONDUIT 

WITH LINE VOLTAGE (24/120/230 VAC).

GENERAL INFORMATION

The ACI Hazardous Room Sensor is a single point 
wall mounted temperature sensor that is designed 
for use with electronic controllers in commercial and 
industrial heating and cooling building manage-
ment systems. It is available with multiple thermistor 
or RTD options. Hazardous Room sensors come 
standard with a heavy-duty Copper-Free Aluminum 
Connection Head that meets Class I, Division 1 & 2, 
Group A, B, C, D; Class II, Division 1, Groups E, F, G; 
Class II, Division 2, Group F & G; class III standards.

For optimal temperature measurement, follow 
these tips:  

Do not install on external walls.

Do not install near heat sources. eg: lamps, radiators, 

direct  sunlight, copiers, chimney walls, walls concealing 
hot-water pipes.

Avoid air registers, diffusers, vents, and windows

MOUNTING INSTRUCTIONS

This product must be installed by a trained profession-
al with knowledge of local codes and regulations. Before carrying out any work, ensure local regulations and 
site procedures are followed to maintain the overall certification of the sensor. The sensor should be mounted 
in an area where air circulation is well mixed and not blocked by obstructions. 

For mounting on a wall, ACI recommends a height of 48-60” (1.2-1.5 m) off the ground and at least 1.5’ (0.5 
m) from the adjacent wall. Remove the cover from the housing by twisting off the cover. Attach the base 
directly to the wall.  Mounting holes are located at the  corners of the housing – see 

FIGURE 1

 (above). Seal 

fittings, intrinsically safe barriers, and explosion proof flex fittings 

not provided by ACI

.

Drill pilot holes for the mounting screws. Use the enclosure mounting holes as a guide, or use the 
dimensions listed in 

FIGURE 1

(p. 1). A 1/2” NPT tapping is located at the top of the enclosure.

Refer to the wiring instructions (p 2) to make necessary connections. The housing is provided with Green ground 
screw if the housing requires an earth ground. After wiring, attach the cover to the base.