Instruction Manual All In One R47_1pag1-12_A24.AAA.006A41.doc 

 

 

Operator manual: ADELSystem reserves the right to change the contents of this document without prior 
notice. 

1  “ALL IN ONE” DC UPS SERIES 

Thank you for having chosen one of our products for your work.  
We are certain that it will give the utmost satisfaction and be a notable help on the job. 

2  GENERAL DESCRIPTION  

Thanks to “All In One” CBI series of DC-UPS, it will 
be  possible  to  optimize  the  power  management  of 
your system with one single, extremely compact and 
cost-effective  device,  connected  directly  to  the 
mains.  The  available  power  is  automatically 
distributed  between  load  and  battery  giving  priority 
to  the  load.  Battery  can  supply  the  load  even  with 
mains so the output power to the load can be twice 
the  nominal  power  if  it  is required  (Power  Boost). When  mains  failure  occurs, the  load  continues  to  be 
supplied by the battery in backup mode. It is also possible to switch on the device with no mains directly 
from  battery.  The  “Battery  Care”  algorithm  performs  rapid  and  automatic  charging,  battery  charge 
optimization during time, flat batteries recovery and real time diagnosis during installation and operation. 
Temperature compensation is possible by connecting the temperature sensor probe. The real time auto-
diagnostic  system  monitors  battery  faults  such  as  sulphated  battery,  shorted  cells,  accidental  reverse 
polarity  connection  or  disconnection  of  the  battery.  Every  fault  is  signaled  by  a  blink code  of  Diagnosis 
Led  or  via  Modbus  (only  in  some  models)  in  order  to  be  easily  detected  and  removed  during  the 
installation  and  after  sales.  The  continuous  monitoring  of  battery  efficiency  reduces  risk  of  battery 
damage  and  allows  a  safe  operation  in  permanent  connection.  Predefined  curves  can  be  selected  by 
jumpers or DIP switch to optimize the charge of different battery types: Open Lead Acid, AGM and Gel 
Lead  Acid;  Ni-Cd  are  rechargeable  using  the  same  device.  Charging  curves  can  be  customized  via 
Modbus (only in some models). Output dry contacts are used to signal both backup and fault conditions. 
A rugged casing with bracket for DIN rail mounting provides IP20 protection degree. 

3  MAIN CHARACTERISTICS 

  Universal input voltage: single-phase 115–230-277 Vac 

  Load  output:24  Vdc  3,5,10,20A;  12  Vdc  3,6,10,15,35A  48 

Vdc 5,10A  

  Battery output:24 Vdc 3,5,10,20A; 12 Vdc 3,6,10,15,35A; 48 

Vdc 5,10A 

  “All  In  One”  solution:  power  supply  +  battery  charger  + 

backup  module  in  one  single  device  connected  directly  to  the 
mains 

  Suited  for  different  battery  types:  Open  Lead  Acid,  Sealed 

Lead  Acid,  AGM  and  Gel  Lead  Acid;  Ni-Cd  and  Li-ion  are 
available  as  options.  Four  stage  charging  curve  for  Lead  Acid 
batteries:  5-stage  IUoU  (Recovery,  Bulk,  Absorption,  Float, 
Refresh  Battery)  plus  Recovery  stage  for  deeply  discharged 
batteries 

  Automatic  diagnosis  of  battery  status  and  battery  Life  Test 

function (Battery Care) 

  Switching technology with high efficiency 

  Protected against short circuit, overload and inverted polarity 

  Output  dry  contact  for  signaling  Low  Battery  or  Battery 

Replacement and Fault system 

  Output dry contact for signaling Mains or Backup 

  IP20 protection degree  

  Space saving on DIN rail 

4  SAFETY AND WARNING NOTES 

  WARNING  –  Explosion  Hazard.  Do  not  disconnect  Equipment  unless  power  has 

been switched off or the area is known to be non-hazardous.  

  WARNING – Explosion Hazard. Substitution of components may impair suitability for 

class I, Division 2. 

  WARNING – Switch off the system before connecting the module. Never work on the machine when it 

is live. The device must be installed in according with UL508 or UL60950. The device must have a 

Summary of Contents for ALL IN ONE CBI Series

Page 1: ...y efficiency reduces risk of battery damage and allows a safe operation in permanent connection Predefined curves can be selected by jumpers or DIP switch to optimize the charge of different battery t...

Page 2: ...or Load DC Bus one Input Output for connection to the battery N 1 battery 12 Vdc for CBI 12xx N 2 battery 12 Vdc connected in Series for CBI 24xx N 4 battery 12 Vdc connected in Series for CBI 48xx 5...

Page 3: ...installation clearance of 10 mm left right between two power supplies and avoid installing the power supplies on top of each other Note Avoid return voltage e g from a decelerating motor or battery w...

Page 4: ...45 min 20 h Load 12 A No 3 min 12 min 30 min 600 min Load 15 A No No 9 min 20 min 400 min Load 20 A No No 7 min 13 min 240 min 6 LAY OUT AND CONNECTIONS 7 INPUT AND OUTPUT LOAD AND BATTERY CONNECTION...

Page 5: ...wer 2 See Diagnosis Led 8 1 4 Relay Contact Rating Max DC1 30 Vdc 1 A AC1 60 Vac 1A Resistive load EN 60947 4 1 Min 1mA at 5 Vdc Min permissive load 8 1 5 Charging Mode STATUS Status Led Diagnosis No...

Page 6: ...Acid Gel Ni Cd option They guarantee battery reliability in time by continuously testing the internal impedance status avoids any possible risk of damages and grants a permanent reliable and safe conn...

Page 7: ...er Position Size 1 Jumper Position Size 2 Jumper Position Size 3 Dip Switch Position Size 4 Float charge Volt Cell Fast charge Volt Cell Open Lead 2 23 2 40 AGM Low 2 25 2 40 Gel Battery 2 30 2 40 NiC...

Page 8: ...he quality resistance on the battery connection is checked every 60 sec This to detect if the cable connection has been properly made Battery in Open Circuit or Sulphated In Float charging mode the Al...

Page 9: ...STICS The unit is a SLAVE in a MODBUS network The slave units are compliant to the following specifications Transmission mode MODBUS RTU Electrical Interface RS485 half duplex serial line Baud rate 48...

Page 10: ...onnection Diagram Size3 CBI500 DPYCONN500 is a special cable for the connection of CBI Size3 and the other device max leght 0 5m RJ45COUPLER is e T connection RJ45 for daisy Chain with CBI Size3 RJCON...

Page 11: ...ections to the external device like RTU PC DPY351 For the connection to RTU PLC or similar devices refer to the instruction manuals Modbus specifications_R14 Web Site www adelsystem com For configurat...

Page 12: ...ity to EN60950 UL60950 1 and CSA C22 2 No 60950 1 07 Information Technology Equipment Safety Part1 General Requirement Device is intended to be installed in a cabinet protected from external shocks or...

Reviews: