MRF102  

2- Channels Electronic Circuit Breaker 

Instruction Manual

 

Thank you for having chosen one of our products for your work.  
We are certain that it will give the utmost satisfaction and be a notable 
help on your job and application. 

Product Description 

The MRF102 2-channel electronic circuit breaker with Din Rail and Wall 
mounting is designed for current distribution and protection of 12V or 
24V load circuits.  

 

 

Safety and warning notes 

WARNING 

–  Explosion  Hazard  Do  not  disconnect 

Equipment unless power has been switched off or the area 
is known to be non-hazardous. 

WARNING 

– Explosion Hazard. Substitution of components 

may impair suitability for class I, Division 2. 

WARNING 

– Switch off the system before connecting the module. Never 

work  on  the  machine  when  it  is  live.  The  device  must  be  installed  in 
according to EN61010 or EN62368-1. The device must have a suitable 
isolating facility outside the power supply unit, via which can be switched 
to idle. Danger of fatal Injury! 

WARNING 

– The device is equipped whit an internal fuse. If the internal 

fuse blows Up (fails opens), it is most probable that there is a fault in the 
device. If this failure occurs, the device must be returned to the factory. 

How to Install  

 

Mounting 

 

Fig. 1 

– Drawing of the MRF102 

 

Din Rail or Panel Mounting 

Fig.  1  shows  a  dimensional  drawing  of  the  MRF102.  It  is  possible  to 
mount the device on Din rail or in panel and fix it by 4 screws 2.9x8-16. 
There is no limit for the Panel thickness.  
 

 

How to Supply MRF102 

The  MRF102  is  supplied  directly  from  the  power  source  which  provide 
power to the load. The device it is protected by internal physic fuse, also 
in worst case situations. The input rating is 8 

– 35Vdc. 

 

 

Device Connection (Fig.2) 

The following cable cross-sections may be used: 

 

Solid  
(mm2) 

Stranded 
(mm2)  

AWG 

Torque 
(Nm) 

Stripping Length 

 

In:  

0.2

–2.5 

0.2

–2.5 

24 

– 14 

0.5

–0.6  

7 mm  

Out: 

0.2

–2.5 

0.2

–2.5 

24

–14 

0.5

–0.6  

7 mm 

Signal: 

 

 

 

AMP Modu II 

 
Connection by the screw, type 2.5 mm2. Wiring terminal shall be 
marked to indicate the proper connection for the power supply. Use 
copper cables only, for supply connections, use wires suitable for at 
least 75°C. 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 2 

– Connections to MRF102 

 

 

Connection terminal and wiring 

Reference  Description 

+ Input Power

 

- Input Signal 

Push Botton: ON / OFF Channel 1 and 2 / Config.Mode 

LED Green, Orange, Red: Channel controls / Config.Mode 

LED Green, Orange, Red: Channel controls / Config.Mode 

Output 1 

Output 2 

Output Fail CN1 and CN2 or ADELBus connection 

Drive a Channel 

 

Turn On Channel 

On the first power up, all channel are OFF. 
To enabling channel 1(LED Blink Red for short time) push the set button 
for short time: one time; < 1 sec. 
To enabling channel 2(LED Blink Red for short time) push the set button 
for short time: two time; < 1 sec. 
Each channel could be enabled  after  a Switch  off for  Overload or Short 
circuit, (LED Red ON). When the LED Red flash for 3 time, the devise 

it’s 

ready to turn ON the channel. If the channel is ON, the device maintains 
in memory the state also without the power; this function it is not enabled 
if the device is in configuration mode.  
 

 

Turn Off Channel 

When  the  channel  1  is  ON  (LED  Blink  Green  or  Orange  for  short  time) 
push button for short time: one time and the channel turn OFF; < 1 sec. 
When  the  channel  2  is  ON  (LED  Blink  Green  or  Orange  for  short  time) 
push button for short time: Two time and the channel turn OFF; < 1 sec. 
If  the  channel  is  OFF,  the  device  maintains  in  memory  the  state  also 
without the power. 
 

LED indication 

  Led RED ON: the channel is in protection due to Overtemperature, 

Overcurrent, 

Over/Under 

voltage 

(<8.5V 

or 

>32.5V).  

The  device  could  be  in  this  situation  for  some  sec.  
In this condition it is not possible turn ON the device. 

  Led RED flashes three times for short time: the channel is OFF after 

switch 

protection, 

but 

is 

ready 

to 

be 

turned 

ON.  

Push the set button to turn ON the device. 

  Led RED flashes one for short time, the channel is OFF but ready 

for turn ON. Push the set button to turn ON the device. 

  Led GREEN blinks for short time: the channel is ON and the current 

through the channel is <80% of the tipping point switch. 

  Led  ORANGE  blinks  for  short  time:  the  channel  is  ON  and  the 

current through the channel is >80% of the tipping point switch. 

  Config. Mode: One Led OFF and the second Led ORANGE blinks, 

in this condition it is enabled the procedure: 

 

Verify the trip current set for each channel 

 

Configure the trip current for each channel 

7

 Out 1 

6

 Out 2 

1

 Input + 

2

 Input - 

4

 LED CN1 

5

 LED CN2 

 

ON / OFF out 1: Tich -  

ON / OFF out 2: Tich 

– Tich - 

PROG: Press 2 sec. -  

 
 

 

Fail _ ADELBus 

 