MODEL 0160

FIRE DAMPER

AIR CONTROL

INSTALLATION, OPERATION 

AND MAINTENANCE MANUAL

Summary of Contents for 0160 Series

Page 1: ...0160_IOM_1 2_Mar21_1 1 MODEL 0160 FIRE DAMPER AIR CONTROL INSTALLATION OPERATION AND MAINTENANCE MANUAL...

Page 2: ...all AFS with drop rods in wall 5 Two hour flexible wall multi section AFS with drop rods two sides 6 Two hour rigid wall AFS with drop rods one side 7 Two hour rigid wall HEVAC 8 Two hour flexible wal...

Page 3: ...luded within this manual an example of the Fire Damper Certificate DW145 Inspection and Handover Check Sheet which is to be completed by the installer A separate certificate is required per damper The...

Page 4: ...for any duct expansion in a fire situation 10 The galvanised mild steel ductwork connections must be sealed with an approved galvanised mild steel ductwork sealer and fixed with low resistance fixings...

Page 5: ...to the slot through the Z piece fitting the nut until tight to secure the rail 8 The damper should be mounted centrally in the opening as detailed in the drawing The drop rods are to slide through the...

Page 6: ...ork sealer and fixed with low resistance fixings such as aluminium rivets that will melt at high temperature allowing the duct to break away without effecting the integrity of the installation 12 The...

Page 7: ...et slot pushing it up against the underside of the rail Insert the 8mm bolt from above into the slot through the Z piece fitting the nut until tight to secure the rail 7 The damper should be centrally...

Page 8: ...ture allowing the duct to break away with affecting the integrity of the installation 11 The connecting galvanised mild steel ductwork must be independently supported within one metre of the connectio...

Page 9: ...l ductwork sealer and fixed with low resistance fixings such as aluminium rivets that will melt at high temperature allowing the duct to break away without effecting the integrity of the installation...

Page 10: ...tend past the opening on each side by 100mm 5 Position the dampers evenly in the centre of the opening 6 Secure the angles to the floor Mark the hole positions on the angle at least 50mm away from the...

Page 11: ...nised mild steel ductwork connecting to the damper spigots must overlap by up to 40mm leaving minimum 10mm clearance for any duct expansion in a fire situation 12 The galvanised mild steel ductwork co...

Page 12: ...the blades and spring system 0160 OPERATION AND MAINTENANCE Visually inspect the damper blades to ensure that they are all interlocked that the springs are straight and that the bottom damper is lock...

Page 13: ...o damper also through ceiling void and adjacent services 7 Confirm the space around the damper has not been used for the passage of other services The presence of other services will invalidate the in...