PHOTOELECTRIC SMOKE DETECTOR MOD.: AE002/OP

The  AE002/OP Photoelectric  smoke  detector  operates based on the light scatte ring  effect  (Tyndall  principle)  providing  a  fast alarm activ ation

particularly in case of slow-burning (smouldering) fires occurs.

The main detector component is a dark chamber equipped with a light-emitting diode cell  faced to a photodiode receptor set capables by a join

operation to detect if any smoke particles have entry into the dark chamber.

Each detector has a LEDs located at the external assembly cover to inform to users by  flashing about if the detector is in stand-by operation or in

permanent alarm as well. Remote LED annunciator capability is available upon request as an optional accessory to be wired to the detector base

terminals block.

This  detector have  a latchi ng  alarm  feature.  In  case  the detector  in  alarm  function  to m ove  it to stand-b y operation  is  requested  to produce a

detector power supply switch-off  from the remote fire alarm panel.

This detector model is manufactured and certified according to EN 54-7:2000 standard.

In general all photoelectric detector types for smoke alarm applications are recommended to be installed within no dust polluted  ambient rooms or

inner zones.

INSTALLATION GUIDELINES.

Mounting

The fixed base of the smoke detector should be mounted directly onto an electrical junction box such as an octagonal (75mm, 90mm or 100mm),

a round (75mm) or a square (100mm) box without using any type of mechanical adapter.

Detectors loop wiring

Switch-off power supply to the detector’s fixed base before plug-in any detector main frame to the fixed base.

§

Positive wire from  detection loop s hall  be connected to t he block termi nal marked as  + (loop input). T he terminal block has  double and

separate terminals marked as + and +C, one for loop input and the other one as loop output.

§

Negative wire from detection loop shall be connected to the block terminal marked as -.

§

To built-up  the detection loop to the next one detector or to the end of line  proceed connecting by wire the poC at the terminal block

with the po (loop input) at  the nex t one detector’s block terminal or to the end of line .  T his procedure allows detection loop as an

open line operation type.

§

Proceed with negative wire in the same way as before mentioned for terminal block marked as -.

§

In case it is required to install a remote LED annunciator, connections from annunciator will be made between positive to an external power

supply  and negative to terminal block R at the base detector.

+

+C

R

+

+C

R

REMOTE

LED

REMOTE

LED

E.O.L.

2K7 Ohm 1/2 W

BASE  (ZCA - ZCB)

POSITIVE DETECTION LOOP

POSITIVE POWER SUPPLY

NEGATIVE DETECTION LOOP

FROM FIRE

CONTROL PANEL

BASE (ZCA - ZCB)