Ae-man-429-0.0 v1.1 

 

 

 

 

 

 

 

 

USER  MANUAL 

 

www.aguilera.es 

 

 

 

 

 
 

(CH

4

) METHANE GAS DETECTOR  

AE09/GM , AE09/GM-12 , AE09/GM-24 

 

Microprocessed gas detector, designed according to Regulation UNE-EN 50194, allows for METHANE 
gas detection  (natural or town gas).  
 
The detector is gauged in order to inform about a danger when gas concentration over 10% of the 
Explosive Lower Limit (L.I.E.)

1

 is reached. When the concentration level is lower than 10% L.I.E. 

again, within a particular time, the detector will be reset automatically. 
 
The detector is catalogued as “Type-A device”, as a visual and sound alarm is produced and an outlet 
which can act directly or indirectly on a cutting device and/or other auxiliary devices.  

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

It is provided with: 
 

Green light indicator for feeding and operation detector.  
Alarm red light indicator. 
Failure orange light indicator. 
Acoustic indicator for prealarm and alarm through piezoelectric buzzer. 
Relay output through tension-free NA, C and NC contacts. 
Internal push-button for operation test cycle.  

 
The detector feeding tension may vary according to the selected model.  
 

AE09/GM 

230V AC 

AE09/GM-12  12V DC 

AE09/GM-24  24V DC 

 
The detector needs to be fed for proper performance. When the detector is fed, 120 seconds are 
needed for warming and stabilization, during such time, the detector is not able to detect the presence 
of METHANE gas.   

                                                

1

 

L.I.E.

 Volumetric concentration of gas or flammable vapour in the air under which a gas explosive atmosphere can not be 

formed.   

Summary of Contents for AE09/GM-12

Page 1: ...tly on a cutting device and or other auxiliary devices It is provided with Green light indicator for feeding and operation detector Alarm red light indicator Failure orange light indicator Acoustic in...

Page 2: ...emperature may decrease below 10 C or over 40 C In places where dust and dirt may block the sensor In a wet or humid place WARNINGS Installation and dismantling of these devices is to be made by autho...

Page 3: ...to be feed at 12V DC for proper performance Such tension from a power supply is to be directly connected to CL2 terminal AE09 GM 24 Model AE09 GM 24 needs to be feed at 24V DC for proper performance...

Page 4: ...0 v1 1 USER MANUAL www aguilera es Feeding examples for normally fed electrovalves Electrovalves are usually open when being fed When cutting off the power supply blocks the gas flow and manual reset...

Page 5: ...ARM STATE When the level of METHANE gas concentration is over 10 L I E the detector activates 1 time per second the acoustic alarm and the red indicator for ALARM in an intermittent way ALARM STATE If...

Page 6: ...ny case it has been calibrated below the level of gas explosion The detector should be installed between 1 and 4 metres from gas appliances The detector should not be installed in a closed place for e...

Page 7: ...coustic indication intermittent activation Alarm state indicator Red and acoustic indication fixed activation Acoustic alarm piezoelectric buzzer 3300Hz 85 dB Alarm level 10 L I E METHANE gas CH4 Alar...