background image

Ultima Compact™ 

Air Cooled Liquid Chiller

R32

30kW - 150kW

Technical Manual

Summary of Contents for Ultima Compact UCCL030-75 1 FAN

Page 1: ...Ultima Compact Air Cooled Liquid Chiller R32 30kW 150kW Technical Manual ...

Page 2: ...le Customer Services For further assistance please e mail connect airedale com or telephone UK Sales Enquiries 44 0 113 239 1000 connect airedale com International Enquiries 44 0 113 239 1000 connect airedale com Spares Hot Line 44 0 113 238 7878 spares airedale com Airedale Service 44 0 113 239 1000 service airedale com Technical Support 44 0 113 239 1000 tech support airedale com Training Enquir...

Page 3: ...tored in a clean dry area away from sunlight The refrigerant must never be stored above 50 C Pressure Equipment Directive 2014 68 EU Minimum and Maximum Operation Temperature TS and Pressure PS Refrigeration AllowableTemperature Range TS Min 20 C to Max 135 C Maximum Allowable Pressure PS High Side 40 2 Barg Low side 29 Barg Based on the refrigerant temperature in the unit off state in the lowest p...

Page 4: ...frigerant is classified as lower flammability according to the international standard for refrigerant designation and safety classification ISO 817 2014 CAUTION No smoking or NAKED FLAME CAUTION Site risk assesments including fire protocol must be carried out and clear safety instructions must be created for the event of a fire and maintained by the site operator where the equipment is installed R...

Page 5: ...ue opportunities to conserve resources prevent pollution and eliminate waste Manufacture products in a responsible manner with minimum impact on the environment Reduce our use of chemicals and minimise their release to the environment Measure control and verify environmental performance through internal and external audits Continually improve our environmental performance CE Directive Airedale cer...

Page 6: ...Water System 22 Technical Data R Type 25 Mechanical and Electrical Data 25 Sound Data 28 Technical Data X Type 29 Mechanical and Electrical Data 29 Sound Data 32 Hydronics Data 33 Waterside Pressure Drops 33 Performance Data 34 Installation 36 Dimensions 36 Point Loadings Weights and Centre of Gravity C of G 37 Lifting 39 Positioning 41 Anti Vibration Mounting Optional 42 Electrical 44 Interconnec...

Page 7: ...eatherproof construction The superstructure is manufactured from galvanised sheet steel coated with epoxy baked powder paint to provide a durable and weatherproof finish Standard unit colour is Light Grey RAL 7035 Compressors and evaporator are mounted on a rigid galvanised heavy duty sub frame Fully weatherproofed electrical panels are situated at one end of the unit Access to the compressors is ...

Page 8: ...tioned to optimise airflow and heat transfer it shall be manufactured from refrigeration quality copper tubes with mechanically bonded aluminium fins Epoxy Coated Condenser Coil In atmospheres where high corrosion is anticipated epoxy coated aluminium finned coils can be offered as an option Refrigeration System Configuration R Type X Type Features UCCL030 75 1 FAN UCCL030 75 2 FAN UCCL085 150 2 F...

Page 9: ...chieved Heat of Rejection Reduction in Compressor Input Power Enthalpy kJ kg Increase in Cooling Duty Evaporating Pressure Reduced Condensing Pressure Presssure Bara Thermostatic Expansion Valve 1 Electronic Expansion Valve 2 1 2 3 4 Dual Pressure Relief Valve A 3 way dual shut off valve that incorporates 2 relief valve assemblies per circuit The valve allows the maintenance of individual pressure...

Page 10: ...racap module is an external backup device for the EVD Evolution used to close the valve in the event of mains power failures The module guarantees temporary power to the EVD Evolution in the event of power failures for enough time to immediately close the connected electronic valve It avoids the need to install a solenoid valve in the refrigerant circuit or use the battery backup module Ultracap s...

Page 11: ...he factory fitted plenum directs discharge air vertically thus limiting air re circulation and provides a degree of acoustic reduction in the horizontal plane Please contact Airedale for further details Standard unit colour is Light Grey RAL 7035 For further details refer to dimensions Anti Vibration Mounts Spring Type Spring vibration isolators can be supplied loose for on site fitting to the bas...

Page 12: ... interlinked operation of the complete system thereby providing optimum temperature control and minimum power consumption Included within this package is a site visit by Airedale Controls Specialists to set up multiple unit sequence control BMS Interface Card BMS cards provide an interface between the Airedale unit and the majority of BMS systems they can be selected and factory fitted as a standa...

Page 13: ...ng the unit operating status and making adjustments to control parameters by allowing the operator access to a series of display pages It features a visual alarm and the facility to adjust and display control settings by a local operator for information and control LCD display Alarm Red LED indicates alarm present Program opens the available menus Esc Green LED lit when operating page displayed re...

Page 14: ...and allow viewing of the last 150 conditions recorded in descending chronological order through the keypad display The following conditions shall be detected triggering a visual display High compressor discharge temperature per compressor Low supply temperature Phase rotation Emergency stop Evaporator flow failure Low pressure safety switch Low suction pressure per compressor High liquid pressure ...

Page 15: ...essure drop monitoring via the microprocessor Remote Setback Temperature Set point Switch A setback set point for supply water temperature shall be selected to suit summer winter conditions or night setback Remote Set point Adjust Shall allow the chilled water set point to be adjusted via an external 0 10V signal Compressor Hours Run Displays hours run of each compressor Optimised Head Pressure Se...

Page 16: ...ntegral finger proof grille The fans offer maximum airflow performance while keeping sound levels to a minimum The in built EC fan control module allows for fan speed modulation from 15 100 a standard AC fans modulating range is typically 40 100 of full fan speed The EC fan presents superior energy efficiency at full and reduced fan speed compared to the equivalent AC fan motor offering efficiency...

Page 17: ...L030 75 2 FAN UCCL085 150 2 FAN UCCL085 150 3 FAN UCCL085 150 4 FAN Waterside Flow Switch Differential Water Pressure Transducer Pump Interlock Water Filter Water Inlet Outlet Threaded Connection Flanged Connections Water Drain Air Bleed Flush Bypass Kit standard Flush Bypass Kit regulating Single Head Pump Single Head Run standby Pump Twin Head Pump Twin Head Run standby Pump Standard Features Op...

Page 18: ...ages Integral pumps may be fitted standard or larger sizes selected to suit installed system requirements The following configurations are available Single Head Pump Factory fitted with electrical switchgear and isolating valve Single Head Run Standby Pumps Factory fitted dual pumps with shut off valves on the inlet and outlet and non return valves on the outlet in automatic changeover configurati...

Page 19: ...imum water volume in litres Vmin is Vmin Water Flow Rate litres min x Minimum Compressor Run Time min x Chiller Loading Factor CLF Example 150kW Cooling Duty at 35 C Ambient and 7 12 C Water Minimum Turndown 0 25 25 4 Compressors 150 x 3600 x 0 25 x 1 2 773 3 Litres 4 19 x 5 10 Where Vmin is the minimum water volume in litres Minimum Compressor Run Time is 6 minutes CLF Minimum Turndown x Cooling ...

Page 20: ...expanded parallelpiped method according to BS EN ISO9614 2009 Resultant performance figures obtained from test will be proven to not differ from the claimed figures by more than the allowable deviations specified in table 7 of section VII of Eurovent RS 6 C 003 2016 A weighted sound power 3dBA Sound Directivity The global sound measurements quoted in the following tables do not incorporate any dir...

Page 21: ...opean Seasonal Energy Efficiency Ratio calculation method has been developed by Eurovent to give a single value that is a realistic indication of the efficiency of the chiller across the year round range of operation The ESEER value is calculated from the unit s performance at 20 25 30 and 35 C ambient temperatures for 25 50 75 and 100 loading stages respectively and with a fixed 7 C supply temper...

Page 22: ...t all low points in the system and in particular adjacent to the unit for maintenance to be carried out Isolating valves should be installed adjacent to all major items of equipment for ease of maintenance Balancing valves can be installed if required to aid correct system balancing All chilled water pipework must be insulated and vapour sealed to avoid condensation If several units are installed ...

Page 23: ...w Switch T FS M P P TT FLUSHING BYPASS LEG TT TT FS Filter Only Scheme Comprises Standard Circuit plus Optional Extras Flow Switch 20 Mesh Water Filter TT TT FS Standard Recommended Installation Parts Supplied By Others Key Water In Temperature Sensor Water Out Drain Filter Bleed Valve Pump Isolation Valve Pressure Sensor Check Valve Flow Switch Bypass Valve Shut Off Valve Pressure Guage Installat...

Page 24: ...ad Pump Scheme Comprises Standard Circuit plus Optional Extras Flow Switch 20 Mesh Water Filter Flushing Bypass Circuit Twin Head Pump Single Head Run Standby Pump Scheme Comprises Standard Circuit plus Optional Extras Flow Switch 20 Mesh Water Filter Flushing Bypass Circuit Single Head Run Standby Pump TT TT M FS TT TT M FS M TT TT M M FS Filter Flushing Bypass Scheme Comprises Standard Circuit p...

Page 25: ...74 10 13 6 08 10 13 10 13 Water System Water Inlet Outlet 1 1 2 BSP 1 1 2 BSP 1 1 2 BSP 1 1 2 BSP 1 1 2 BSP 1 1 2 BSP 2 BSP Water Volume l 5 7 8 4 5 7 8 4 5 7 8 4 9 3 Minimum System Water Volume 5 l 549 579 429 445 382 416 536 Electrical Data Nominal Run Amps 6 A 22 7 26 0 33 2 36 5 33 2 36 5 42 3 Maximum Start Amps A 145 149 116 120 116 120 166 Recommended Mains Fuse Size A 32 32 40 50 40 50 50 M...

Page 26: ...t C02 Tonnes tC02 10 13 10 46 10 80 10 46 10 80 10 80 10 80 Water System Water Inlet Outlet 2 BSP 2 BSP 2 BSP 2 BSP 2 BSP 2 BSP 2 BSP Water Volume l 8 4 13 7 12 7 14 6 13 1 15 0 15 0 Minimum System Water Volume 5 l 488 603 547 686 615 776 690 Electrical Data Nominal Run Amps 6 A 42 3 45 3 45 3 48 6 48 6 53 9 69 6 Maximum Start Amps A 166 168 168 175 175 188 196 Recommended Mains Fuse Size A 50 63 ...

Page 27: ...geration Charge Total kg 8 8 27 5 14 14 28 14 14 33 17 17 17 5 17 5 GWP Equivalent C02 Tonnes tC02 10 80 18 56 18 90 18 90 18 90 22 28 22 95 23 63 Water System Water Inlet Outlet 2 BSP DN65 DN65 DN65 DN65 DN65 DN65 DN65 Water Volume l 13 5 15 6 14 0 16 7 14 8 31 2 28 7 30 3 Minimum System Water Volume 5 l 685 701 442 712 451 835 618 788 Electrical Data Nominal Run Amps 6 A 53 9 69 6 65 4 68 4 70 0...

Page 28: ...73 66 65 62 76 Pressure 10m 47 40 42 41 41 34 33 31 45 UCCL060DX 2AEE Power dB 79 72 74 73 73 66 65 62 76 Pressure 10m 47 40 42 41 41 34 33 31 45 UCCL070SX 2AL0 Power dB 80 72 74 73 73 67 67 63 77 Pressure 10m 48 40 42 41 41 36 36 32 45 UCCL070DX 2AFF Power dB 80 72 74 73 73 67 67 63 77 Pressure 10m 48 40 42 41 41 36 36 32 45 UCCL075SX 2AM0 Power dB 79 72 74 73 71 68 70 67 77 Pressure 10m 48 40 42...

Page 29: ...tC02 5 74 10 13 5 74 10 13 6 08 10 13 10 13 Water System Water Inlet Outlet 1 1 2 BSP 1 1 2 BSP 1 1 2 BSP 1 1 2 BSP 1 1 2 BSP 1 1 2 BSP 2 BSP Water Volume l 5 7 8 4 5 7 8 4 5 7 8 4 9 3 Minimum System Water Volume 5 l 553 583 430 446 386 419 538 Electrical Data Nominal Run Amps 6 A 22 1 24 8 32 6 35 3 32 6 35 3 41 1 Maximum Start Amps A 145 147 116 118 116 118 165 Recommended Mains Fuse Size A 32 3...

Page 30: ...15 5 8 8 16 16 8 8 GWP Equivalent C02 Tonnes tC02 10 13 10 46 10 80 10 46 10 80 10 80 10 80 10 80 Water System Water Inlet Outlet 2 BSP 2 BSP 2 BSP 2 BSP 2 BSP 2 BSP 2 BSP 2 BSP Water Volume l 9 3 12 7 14 6 13 1 15 0 15 0 13 5 Minimum System Water Volume 5 l 538 550 688 620 779 691 692 Electrical Data Nominal Run Amps 6 A 41 1 44 1 44 1 47 4 47 4 52 7 68 4 52 7 Maximum Start Amps A 165 167 167 173...

Page 31: ... Equivalent C02 Tonnes tC02 18 56 18 90 21 94 22 28 28 69 29 03 29 70 Water System Water Inlet Outlet DN65 DN65 DN65 DN65 DN65 DN65 DN65 Water Volume l 15 6 14 0 21 3 19 5 38 5 36 0 37 7 Minimum System Water Volume 5 l 706 446 724 462 849 632 806 Electrical Data Nominal Run Amps 6 A 68 4 64 2 71 1 72 7 81 7 86 7 103 9 Maximum Start Amps A 194 147 197 197 216 209 238 Recommended Mains Fuse Size A 8...

Page 32: ... 68 66 63 78 Pressure 10m 50 42 42 41 44 37 34 32 46 UCCL060DR 2AEE Power dB 81 74 74 72 75 68 66 63 78 Pressure 10m 50 42 42 41 44 37 34 32 46 UCCL070SR 2AL0 Power dB 82 74 74 72 75 70 69 64 79 Pressure 10m 50 42 42 41 44 39 37 33 47 UCCL070DR 2AFF Power dB 82 74 74 72 75 70 69 64 79 Pressure 10m 50 42 42 41 44 39 37 33 47 UCCL075SR 2AM0 Power dB 82 74 74 72 73 72 71 68 79 Pressure 10m 50 42 42 4...

Page 33: ...able Total Pump Head Available Chiller Pressure Drop External Head Available Example UCCL 125DX 4AKK 8 0 l s standard single pump 190 kPa 75 kPa 115 kPa For glycol solutions please refer to Glycol Data Pressure drops shown are for the standard unit without optional pumps and or pipework Waterside Pressure Drops Single Circuit Evaporator Pressure Drop kPa Waterflow l s UCCL30 UCCL40 UCCL50 UCCL60 U...

Page 34: ...Dual Circuit Evaporator Pressure Drop kPa UCCL30 UCCL40 UCCL50 UCCL60 UCCL70 UCCL75 UCCL85 UCCL100 UCCL125 0 50 100 150 200 0 0 2 0 4 0 6 0 8 0 10 0 12 0 14 0 For glycol solutions please refer to Glycol Data Pressure drops shown are for the standard unit without optional pumps and or pipework Waterflow l s Technical ...

Page 35: ...e or R S Pump UCCL 70 75 3 Std Single or R S Pump UCCL 85 150 4 Total Pump Head Available kPa 1 2 3 4 0 00 50 00 100 00 150 00 200 00 250 00 300 00 0 0 2 0 4 0 6 0 8 0 10 0 12 0 14 0 Waterflow l s 6 5 0 00 50 00 100 00 150 00 200 00 250 00 300 00 0 0 2 0 4 0 6 0 8 0 10 0 12 0 14 0 Total Pump Head Available kPa Waterflow l s Range Model Curve Std Twin Pump UCCL 85 150 5 Upg Twin Pump UCCL 85 150 6 ...

Page 36: ...0 00 250 00 300 00 350 00 0 0 2 0 4 0 6 0 8 0 10 0 12 0 14 0 Total Pump Head Available kPa Waterflow l s Performance Data Range Model Curve Upg Single or R S Pump UCCL 30 40 7 Upg Single or R S Pump UCCL 50 60 8 Upg Single or R S Pump UCCL 50 60 9 Upg Single or R S Pump UCCL 70 75 10 Upg Single or R S Pump UCCL 85 150 11 Technical ...

Page 37: ...0 50 1366 2800 702 225 1466 500 2000 2500 UCCL 100 150 3 745 3650 1030 1300 530 50 1197 3650 702 225 1466 500 2000 2500 UCCL124 150 4 745 4500 1030 1300 530 50 1197 4500 702 225 1466 500 2000 2500 H D A C B F G F E M N L I J K DISCHARGE AIR DISCHARGE AIR DISCHARGE AIR SUPPLY RETURN Pipe Water Connection Sizes Supply Return UCCL 30 40 1 1 2 BSP 1 1 2 BSP UCCL 30 75 2 BSP 2 BSP UCCL 85 100 DN65 PN16...

Page 38: ...9 1 1 530 636 700 UCCL040DR 2ACC kg 176 176 153 156 1 1 661 639 945 UCCL050SR 2AJ0 kg 182 183 153 157 1 1 675 639 932 UCCL050DR 2ADD kg 182 183 153 156 1 1 675 639 932 UCCL060SR 2AK0 kg 184 184 157 160 1 1 684 639 933 UCCL060DR 2AEE kg 184 184 156 160 1 1 684 639 933 UCCL070SR 2AL0 kg 188 188 158 161 1 1 695 639 927 UCCL070DR 2AFF kg 188 188 157 160 1 1 693 639 927 UCCL075SR 2AM0 kg 190 191 158 16...

Page 39: ...UCCL060SX 2AK0 kg 184 184 157 160 1 1 684 639 933 UCCL060DX 2AEE kg 184 184 156 160 1 1 684 639 933 UCCL070SX 2AL0 kg 188 188 158 161 1 1 695 639 927 UCCL070DX 2AFF kg 188 188 157 160 1 1 693 639 927 UCCL075SX 2AM0 kg 190 191 158 161 1 1 701 639 923 UCCL075SX 2AP0 kg 224 225 160 163 1 1 771 638 868 UCCL075DX 2AGG kg 190 191 158 161 1 1 700 639 923 UCCL085SX 2AP0 kg 286 287 216 218 1 1 1007 652 120...

Page 40: ...y be checked for damage and reported to Airedale Service The unit should be lifted from the base and where possible with all packing and protection in position If any other type of slinging is used due care should be taken to ensure that the slings do not crush the casework or coil Lifting Dimensions 1 Dimensions in brackets refer to the optional buffer tank when fitted The unit should be lifted f...

Page 41: ...les and emergency stop shall be no higher than 1 9m above the service level A maximum height of 1 7m is recommended whether directly from the service level or from a permanently fixed service level to ensure ease of accessibility If the unit is mounted on a raised plinth the upper limit of 1 9m must be observed and a permanently fixed service platform must be installed to maintain the 1 9m maximum...

Page 42: ...its in the vicinity Allow free space no obstructions above the fans to prevent air recirculation Within a side enclosed installation the condenser fan MUST be higher than the enclosing structure Figures in brackets indicate airflow and maintenance clearances for side enclosed or multiple chiller applications The leak detection fan must not be obstructed and must discharge away from any sources of ...

Page 43: ...taining nut and washer 7 Beginning with the mount with the largest deflection adjust the height of each mount using the levelling screw 3 Mountings must be adjusted incrementally in turn 8 Do not fully adjust 1 mount at a time as this may overload and damage springs 9 When all mounts are level lock each into place using the levelling lock nut 4 10 Lock all retaining nuts 6a and 6b to the extreme e...

Page 44: ...nt is larger than the unit base Consideration must be made with regard to steelwork concrete plinth sizes Full information is available on the approved General Arrangement drawings The base of the unit is open Considerations must be made for service and maintenance requirements if the unit is installed on a gantry AV Mount Overhang Support Steelwork Installation ...

Page 45: ...tection cabling for a maximum voltage drop of 2V Avoid large voltage drops on cable runs particularly low voltage wiring Wires should be capable of carrying the maximum load current under non fault conditions at the stipulated voltage CAUTION A separately fused locally isolated permanent single phase and neutral supply MUST BE FITTED for the compressor sump heater evaporator trace heating and cont...

Page 46: ...arm N O 581 Critical Alarm Common 582 Critical Alarm N C 590 Critical Alarm N O 591 Critical Alarm Common 592 Critical Alarm N C RX TX RX TX GND RX TX RX TX GND Setback Setpoint Switch External Customer Trace Heating 230V 500W Max Mains Incoming Supply Primary 400V 3PH N 50Hz Network In pLAN Network Out pLAN Remote On Off Pumps Remote On Off Separate Permanent Supply 230V 1PH 50Hz UCCL30 150 Insta...

Page 47: ...7 502 1 522 580 Critical Alarm N O 581 Critical Alarm Common 582 Critical Alarm N C 590 Critical Alarm N O 591 Critical Alarm Common 592 Critical Alarm N C RX TX RX TX GND RX TX RX TX GND Remote Pump Interlock Network In pLAN Network Out pLAN Mains Incoming Supply Primary 400V 3PH N 50Hz Separate Permanent Supply 230V 1PH 50Hz External Customer Trace Heating 230V 500W Max Evaporator Flow Switch Re...

Page 48: ... air temperature C Evaportator inlet outlet water temperatures C Fixed outlet A 100 35 12 7 B 93 25 7 C 87 15 7 D 80 5 7 EU 2016 2281 Table 22 Rating Point T1 C Part load ratio Outdoor air dry bulb temperature C Fan coil application inlet outlet water temperature C Cooling floor application inlet outlet water temperatures C Fixed outlet Variable outlet A 35 100 35 12 7 12 7 23 18 B 30 74 30 7 8 5 ...

Page 49: ...ted Cooling Capacity Prated c 2 4 5 kW n a 27 8 n a Declared Cooling Capacity 35 C Pdc 2 3 5 kW n a 27 7 n a Declared EERd 35 C n a 3 00 n a Declared Cooling Capacity 30 C Pdc 2 3 5 kW n a 31 0 n a Declared EERd 30 C n a 3 88 n a Declared Cooling Capacity 25 C Pdc 2 3 5 kW n a 34 3 n a Declared EERd 25 C n a 5 04 n a Declared Cooling Capacity 20 C Pdc 2 3 5 kW n a 37 8 n a Declared EERd 20 C n a 6...

Page 50: ...7 SSCEE Tier NOT Compliant NOT Compliant NOT Compliant Rated Cooling Capacity Prated c 2 4 5 kW n a n a n a Declared Cooling Capacity 35 C Pdc 2 3 5 kW n a n a n a Declared EERd 35 C n a n a n a Declared Cooling Capacity 30 C Pdc 2 3 5 kW n a n a n a Declared EERd 30 C n a n a n a Declared Cooling Capacity 25 C Pdc 2 3 5 kW n a n a n a Declared EERd 25 C n a n a n a Declared Cooling Capacity 20 C ...

Page 51: ...r 1 2018 Rated Cooling Capacity Prated c 2 4 5 kW 48 2 n a 53 5 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 48 1 n a 53 4 Declared EERd 35 C 2 74 n a 2 58 Declared Cooling Capacity 30 C Pdc 2 3 5 kW 53 5 27 3 n a 59 3 30 5 Declared EERd 30 C 3 38 3 67 n a 3 24 3 65 Declared Cooling Capacity 25 C Pdc 2 3 5 kW 30 1 0 0 n a 33 7 0 0 Declared EERd 25 C 4 53 0 00 n a 4 62 0 00 Declared Cooling Capacity...

Page 52: ...mpliant Tier 1 2018 NOT Compliant Rated Cooling Capacity Prated c 2 4 5 kW n a 60 4 n a Declared Cooling Capacity 35 C Pdc 2 3 5 kW n a 60 2 n a Declared EERd 35 C n a 2 56 n a Declared Cooling Capacity 30 C Pdc 2 3 5 kW n a 66 9 34 8 n a Declared EERd 30 C n a 3 17 3 63 n a Declared Cooling Capacity 25 C Pdc 2 3 5 kW n a 38 3 0 0 n a Declared EERd 25 C n a 4 54 0 00 n a Declared Cooling Capacity ...

Page 53: ... 118 4 SSCEE Tier NOT Compliant NOT Compliant NOT Compliant Rated Cooling Capacity Prated c 2 4 5 kW n a n a n a Declared Cooling Capacity 35 C Pdc 2 3 5 kW n a n a n a Declared EERd 35 C n a n a n a Declared Cooling Capacity 30 C Pdc 2 3 5 kW n a n a n a Declared EERd 30 C n a n a n a Declared Cooling Capacity 25 C Pdc 2 3 5 kW n a n a n a Declared EERd 25 C n a n a n a Declared Cooling Capacity ...

Page 54: ...t Tier 2 2021 Rated Cooling Capacity Prated c 2 4 5 kW 86 1 n a 91 2 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 85 8 n a 90 9 Declared EERd 35 C 2 26 n a 2 52 Declared Cooling Capacity 30 C Pdc 2 3 5 kW 67 7 34 9 n a 70 1 35 4 Declared EERd 30 C 3 28 3 64 n a 3 49 3 79 Declared Cooling Capacity 25 C Pdc 2 3 5 kW 74 6 38 6 n a 77 1 39 1 Declared EERd 25 C 4 07 4 56 n a 4 34 4 76 Declared Cooling C...

Page 55: ...2 4 5 kW 90 8 106 9 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 90 6 106 7 Declared EERd 35 C 2 74 2 59 Declared Cooling Capacity 30 C Pdc 2 3 5 kW 75 0 51 9 81 2 40 9 Declared EERd 30 C 3 52 3 70 3 60 3 93 Declared Cooling Capacity 25 C Pdc 2 3 5 kW 56 9 24 2 89 3 45 1 Declared EERd 25 C 4 56 3 81 4 52 4 95 Declared Cooling Capacity 20 C Pdc 2 3 5 kW 26 6 0 0 49 5 0 0 Declared EERd 20 C 4 77 0 00...

Page 56: ...c 2 4 5 kW 113 2 142 2 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 112 9 141 8 Declared EERd 35 C 2 78 2 56 Declared Cooling Capacity 30 C Pdc 2 3 5 kW 94 4 64 0 120 3 82 7 Declared EERd 30 C 3 54 3 86 3 30 3 70 Declared Cooling Capacity 25 C Pdc 2 3 5 kW 70 3 32 9 90 7 42 3 Declared EERd 25 C 4 86 4 15 4 61 3 93 Declared Cooling Capacity 20 C Pdc 2 3 5 kW 36 1 0 0 46 4 0 0 Declared EERd 20 C 5 29...

Page 57: ...ed Cooling Capacity Prated c 2 4 5 kW n a 27 9 n a Declared Cooling Capacity 35 C Pdc 2 3 5 kW n a 27 9 n a Declared EERd 35 C n a 3 03 n a Declared Cooling Capacity 30 C Pdc 2 3 5 kW n a 31 1 n a Declared EERd 30 C n a 3 92 n a Declared Cooling Capacity 25 C Pdc 2 3 5 kW n a 34 5 n a Declared EERd 25 C n a 5 10 n a Declared Cooling Capacity 20 C Pdc 2 3 5 kW n a 37 9 n a Declared EERd 20 C n a 6 ...

Page 58: ...18 NOT Compliant NOT Compliant Rated Cooling Capacity Prated c 2 4 5 kW 40 4 n a n a Declared Cooling Capacity 35 C Pdc 2 3 5 kW 40 2 n a n a Declared EERd 35 C 2 75 n a n a Declared Cooling Capacity 30 C Pdc 2 3 5 kW 44 5 22 6 n a n a Declared EERd 30 C 3 42 3 58 n a n a Declared Cooling Capacity 25 C Pdc 2 3 5 kW 24 9 0 0 n a n a Declared EERd 25 C 4 45 0 00 n a n a Declared Cooling Capacity 20 ...

Page 59: ...r 1 2018 Rated Cooling Capacity Prated c 2 4 5 kW 48 5 n a 53 9 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 48 4 n a 53 7 Declared EERd 35 C 2 79 n a 2 63 Declared Cooling Capacity 30 C Pdc 2 3 5 kW 53 8 27 4 n a 59 7 30 7 Declared EERd 30 C 3 45 3 70 n a 3 32 3 69 Declared Cooling Capacity 25 C Pdc 2 3 5 kW 30 2 0 0 n a 33 8 0 0 Declared EERd 25 C 4 57 0 00 n a 4 67 0 00 Declared Cooling Capacity...

Page 60: ... 128 4 SSCEE Tier NOT Compliant Tier 1 2018 NOT Compliant Rated Cooling Capacity Prated c 2 4 5 kW n a 60 9 n a Declared Cooling Capacity 35 C Pdc 2 3 5 kW n a 60 7 n a Declared EERd 35 C n a 2 61 n a Declared Cooling Capacity 30 C Pdc 2 3 5 kW n a 67 5 34 9 n a Declared EERd 30 C n a 3 25 3 67 n a Declared Cooling Capacity 25 C Pdc 2 3 5 kW n a 38 6 0 0 n a Declared EERd 25 C n a 4 60 0 00 n a De...

Page 61: ...of Sale Warranty and Warranty Procedure available upon request Procedure When a component part fails a replacement part should be obtained through our Spares department If the part is considered to be under warranty the following details are required to process this requirement Full description of part required including Airedale s part number if known The original equipment serial number An appro...

Page 62: ...iredale International Air Conditioning Ltd Leeds Road Rawdon Leeds LS19 6JY Tel 44 0 113 2391000 Fax 44 0 113 2507219 E mail enquiries airedale com Web www airedale com TM_ULTIMA_UCCL30 150_9690553_V 1 1 0_10_2019 ...