A3C Series Condensing Hydronic Boilers
Models: A3C-1000, A3C-1500, A3C-2000, A3C-2500
A3C-3000, A3C-4000, A3C-5000, A3C-6000
ALDRICH SERIES A3C FIRETUBE CONDENSING HYDRONIC BOILERS
PART 1
–
GENERAL
1.1
SUMMARY
A.
This section includes packaged, factory-fabricated and assembled, gas-fired, three pass
condensing firetube boilers, trim, and accessories for generating hot water for pressure as
noted on plans.
1.
Three pass firetube condensing boiler
2.
Burner - Specify Fuel: Natural Gas, LP Gas or Combination Gas/#2 Oil
1.2
SUBMITTALS
A.
Product Data: Include performance data, operating characteristics, furnished specialties,
and accessories.
B.
Shop Drawings: For boilers, boiler trim, and accessories; Include plans, elevations, sections,
details, and attachments to other work.
1.
Wiring Diagrams: Power, signal, and control wiring.
2.
Fuel Train Schematic
1.3
CLOSEOUT SUBMITTALS
A.
Operation and Maintenance Data: For boilers, components, and accessories to include in
emergency, operation and maintenance manuals.
B.
Warranties: As specified in this section.
1.4
QUALITY ASSURANCE
A.
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction.
B.
ASME Compliance: Fabricate and label boilers to comply with ASME Section IV Boiler and
Pressure Vessel Code.
C.
ASHRAE/IESA 90.1 Compliance: Boilers shall have minimum efficiency according to: Gas and
Oil Fired Boilers
–
Minimum Efficiency Requirements.”
D.
UL Compliance: Control devises and control sequences according to requirements of UL.
E.
CSD-1 Compliance: Boilers/burners equipped to meet current state code.