background image

Installation Instructions

PanelView Plus and PanelView Plus Compact

 

400 and 600 Terminals

Catalog Numbers 2711P-x4xxxx, 2711P-x6xxxx, 2711PC-x4xxxx, 
2711PC-x6xxxx 

About This Publication

This document provides instructions on how to install these devices in a panel:

PanelView Plus 400 keypad terminal or keypad and touch terminal

PanelView Plus 600 keypad, touch, or keypad and touch terminal

PanelView Plus Compact 400 keypad terminal or keypad and touch terminal

PanelView Plus Compact 600 touch terminal

For complete information on installing, wiring, and troubleshooting the terminals, refer to the 
publications listed under Additional Resources.

Topic

Page

Important User Information

2

Environment and Enclosure

3

Hazardous Locations

4

Wiring and Safety Guidelines

8

About the Product

8

Parts List

9

Install the Terminal

10

Remove and Install the Power Terminal Block

15

DC Power Connections

16

AC Power Connections

19

Troubleshooting

21

Battery Removal

25

Specifications

26

Additional Resources

28

AB Parts

Summary of Contents for PanelView Plus 400

Page 1: ... Plus Compact 400 keypad terminal or keypad and touch terminal PanelView Plus Compact 600 touch terminal For complete information on installing wiring and troubleshooting the terminals refer to the publications listed under Additional Resources Topic Page Important User Information 2 Environment and Enclosure 3 Hazardous Locations 4 Wiring and Safety Guidelines 8 About the Product 8 Parts List 9 I...

Page 2: ...particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automati...

Page 3: ...ard This equipment is supplied as open type equipment It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts The interior of the enclosure must be accessible only by the use of a tool The terminals meet specified NEMA Type and I...

Page 4: ...g in a 55 C 131 F maximum ambient temperature Do not install the terminals in environments where atmospheric gases have ignition temperatures less than 135 C 275 F WARNING Explosion Hazard Substitution of components may impair suitability for hazardous locations Do not disconnect equipment unless power has been switched off and area is known to be non hazardous Do not connect or disconnect compone...

Page 5: ... de 55 C N installez pas les terminaux dans des environnements contenant des gaz atmosphériques inflammables à moins de 135 C WARNING DANGER D EXPLOSION La substitution de composants peut rendre cet équipement impropre à une utilisation en environnement dangereux Ne pas déconnecter l équipement sans s être assuré que l alimentation est coupée ou que l environnement est classé non dangereux Ne pas ...

Page 6: ...lected nonincendive field wiring apparatus must have nonincendive circuit parameters conforming with Table 2 Table 1 400 and 600 USB Port Circuit Parameters 400 and 600 Terminals Voc Isc Ca La Groups A and B Groups C and D Groups A and B Groups C and D Series A and B 5 25V DC 1 68 A 10 µF 10 µF 15 µH 15 µH Series C or later 5 25V DC 1 68 A 10 µF 10 µF 3 5 µH 15 µH Table 2 Required Circuit Paramete...

Page 7: ...th 501 10 B 3 of the National Electrical Code NEC ANSI NFPA 70 or other local codes as applicable This associated nonincendive field wiring apparatus has not been evaluated for use in combination with another associated nonincendive field wiring apparatus Symbol Definitions Voc Open circuit voltage of the host USB port Isc Maximum output current of the host USB port Vmax Maximum applied voltage ra...

Page 8: ...ly to avoid electromagnetic interference EMI Grounding minimizes noise from EMI and is a safety measure in electrical installations For more information on grounding recommendations refer to the National Electrical Code published by the National Fire Protection Association For more information on terminal wiring and grounding applications refer to publication 2711P TD001 You can find this publicat...

Page 9: ...out Required Tools These tools are required for installation Panel cutout tools Small slotted screwdriver for securing power and RS 232 port connections IMPORTANT When using the DH 485 module catalog number 2711P RN3 with PanelView Plus 400 and 600 terminals the cable length must not exceed 30 m 98 ft to comply with CE requirements For longer cable lengths use the 1761 NET AIC or 1747 AIC module P...

Page 10: ...clearance 0 mm 0 in Minimum side clearance for insertion of memory card is 102 mm 4 in Panel Cutout Dimensions Use the full size template shipped with your terminal to mark the cutout dimensions Mount the Terminal in a Panel Mounting levers secure the terminal to the panel The number of levers you use 4 or 6 varies by terminal type Terminal Type Height mm in Width mm in 400 Keypad or Keypad and To...

Page 11: ...positioned on the terminal This gasket forms a compression type seal Do not use sealing compounds 4 Install legend strips before installing the terminal if you are using keypad legend strips on 600 keypad terminals Be careful not to pinch legend strip during installation 5 Place the terminal in the panel cutout If you are mounting the terminal in an existing 550 panel cutout align the terminal wit...

Page 12: ...gnment Lever Position Panel Thickness Range Typical Gauge 1 1 52 2 01 mm 0 060 0 079 in 16 2 2 03 2 64 mm 0 080 0 104 in 14 3 2 67 3 15 mm 0 105 0 124 in 12 4 3 17 3 66 mm 0 125 0 144 in 10 5 3 68 4 16 mm 0 145 0 164 in 8 9 6 4 19 4 75 mm 0 165 0 187 in 7 ATTENTION Follow the instructions to provide a proper seal and to prevent potential damage to the terminal Rockwell Automation assumes no respon...

Page 13: ...EN P November 2009 Product Dimensions The illustrations show approximate product dimensions for the PanelView Plus and PanelView Plus Compact 400 and 600 terminals Measurements are in mm in 400 Terminal Dimensions 60 2 35 90 3 54 152 6 0 185 7 28 154 6 08 71 2 81 400 Keypad or Keypad and Touch ...

Page 14: ...ompact 400 and 600 Terminals Publication 2711P IN002G EN P November 2009 600 Terminal Dimensions 266 10 47 167 6 58 185 7 28 152 6 0 68 2 68 98 3 86 98 3 86 68 2 68 154 6 08 600 Keypad or Keypad and Touch 600 Touch 154 6 08 71 2 81 71 2 81 ...

Page 15: ...rminal block base in first with the block leaning outward 2 Gently push the top of terminal block back to vertical position to snap in locking tab WARNING Explosion Hazard Substitution of components may impair suitability for hazardous locations Do not disconnect equipment unless power has been switched off and area is known to be non hazardous Do not connect or disconnect components unless power ...

Page 16: ...ernal Power Supply Use a single 24V DC power supply to power each PanelView Plus terminal such as catalog number 2711P RSACDIN Using a separate isolated and ungrounded source to power each terminal prevents ground loop currents from damaging the terminals The output on the power supply must be isolated from the input and not connected to earth ground Wire Specifications for DC Input Power Terminal...

Page 17: ...nonisolated communication ports For more information on wiring and grounding refer to publication 2711P TD001 available at http www literature rockwellautomation com IMPORTANT The functional earth connection to ground is mandatory This connection is required for noise immunity reliability and Electromagnetic Compliance EMC with the European Union EU EMC directive for CE mark conformance Functional...

Page 18: ...inal for proper connections 3 Secure the functional earth ground wire to the functional earth ground terminal screw on the input power terminal block 4 Apply 24V DC power to the terminal WARNING Explosion Hazard Do not disconnect equipment unless power has been switched off and area is known to be nonhazardous Disconnect all power before installing or replacing components Failure to disconnect pow...

Page 19: ...d connection on the power input terminal block The protective earth terminal wiring requires a minimum wire gauge Wire Specifications for AC Input Power Terminal Block Wire Type Dual wire Gauge 1 1 Two wire max per terminal Single wire Gauge Terminal Screw Torque Stranded or solid Cu 90 C 194 F 0 33 1 31 mm2 22 16 AWG 0 33 2 08 mm2 22 14 AWG 0 45 0 56 N m 4 5 lb in ATTENTION The protective earth c...

Page 20: ...erminal WARNING Explosion Hazard Do not disconnect equipment unless power has been switched off and area is known to be nonhazardous Disconnect all power before installing or replacing components Failure to disconnect power may result in electrical shock and or damage to the terminal ATTENTION Improper wiring of power terminals may result in voltage at the communication connector shells Refer to t...

Page 21: ...redictable behavior Verify the power requirements in the Specifications table Check the Status Indicators The terminal has two status indicators to isolate operating problems COMM indicator green for communications FAULT indicator red for hardware faults When the terminal starts up the fault indicator should be off except for a few brief flashes and the comm indicator on If the indicators remain o...

Page 22: ...ng red indicates a recoverable error Off Last firmware download failed Reload firmware using Firmware Upgrade Wizard FUW utility Blinking EBC boot loader firmware failed or is missing Reload firmware using Firmware Upgrade Wizard FUW utility On Windows CE OS firmware failed or is missing Reload firmware using Firmware Upgrade Wizard FUW utility On 2 2 Solid red indicates a nonrecoverable or fatal ...

Page 23: ...splay for a few seconds These messages do not require that you perform any action Message Message Description 30 Watchdog Test Tests the watchdog circuitry to verify system integrity 1 RAM Test Tests the RAM memory 2 Image Search Checks for new OS firmware upgrade on the external compact flash card and the serial port 11 Downloading Image Transfers a new OS firmware upgrade to internal RAM Message...

Page 24: ...pe of firmware upgrade Reset the terminal and upgrade with the correct firmware version 24 CRC Check Checksum of the OS firmware failed Reload the firmware If error persists replace the terminal 25 Invalid Prod Family OS firmware that is downloading is not compatible with terminal Check that you are using the correct version and type of firmware upgrade Reset the terminal and upgrade with the corr...

Page 25: ... module if attached from the logic module by removing the three screws 4 Unlatch the eight retaining tabs two on each side on the back cover and remove cover 5 Locate the yellow battery on the logic board 6 Remove the battery This product contains a hermetically sealed lithium battery which may need to be replaced during the life of the product At the end of its life the battery contained in this ...

Page 26: ... in Display area WxH Approx 400 grayscale display 400 color display 600 grayscale color display 77 x 58 mm 3 0 x 2 3 in 71 x 53 mm 2 8 x 2 1 in 112 x 84 mm 4 4 x 3 3 in Display resolution 400 grayscale color display 600 grayscale color display 320 x 240 320 x 240 Backlight 400 grayscale color display 600 grayscale color display LED CCFL 50 000 hours life min Touch Screen Touch screen Analog resist...

Page 27: ... C Clock Battery backup 2 minutes per month Status indicators COMM Green Fault Red Application flash memory 20 MB External compact flash storage 512 MB max 1 Add approximately 95 g 0 21 lb for communication module Environmental Specifications Attribute Value Temperature operating 0 55 C 32 131 F Temperature storage 25 70 C 13 158 F Heat dissipation 80 BTU hr Altitude operating 2000 m 6561 ft Vibra...

Page 28: ... Locations CE EMC European Union 2004 108 EC EMC Directive compliant with EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions CE LVD European Union 2006 95 EC Low Voltage Directive compliant with EN 61131 2 Programmable Controllers C Tick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions 1 See the Product Certification link on http www ab com for...

Page 29: ...PanelView Plus and PanelView Plus Compact 400 and 600 Terminals 29 Publication 2711P IN002G EN P November 2009 ...

Page 30: ...30 PanelView Plus and PanelView Plus Compact 400 and 600 Terminals Publication 2711P IN002G EN P November 2009 ...

Page 31: ...PanelView Plus and PanelView Plus Compact 400 and 600 Terminals 31 Publication 2711P IN002G EN P November 2009 ...

Page 32: ... 24 hours of installation please review the information that s contained in this manual You can also contact a special Customer Support number for initial help in getting your product up and running New Product Satisfaction Return Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not funct...

Reviews: