Alpha Sentra: 750/ 1000/ 1500/ 2200/ 3000

Indoor Line Interactive UPS

 User Manual

Summary of Contents for Sentra 1000

Page 1: ...Your Power Solutions Partner member of The Group Alpha Sentra 750 1000 1500 2200 3000 Indoor Line Interactive UPS User Manual ...

Page 2: ......

Page 3: ...his document is for information only and is subject to change without notice While reasonable efforts have been made in the preparation of this document to assure its accuracy Alpha Technologies assumes no liability resulting from errors or omissions in this document or from the use of the information contained herein Alpha Technologies reserves the right to make changes in the product design with...

Page 4: ...ront Panel 11 2 6 UPS Rear Panel 13 3 Installation 18 3 1 Connect Utility and Load 18 3 3 Connect Network Surge protection 19 3 2 Connect Computer Interface Port 19 3 4 REPO Switch 20 4 Operation 21 4 1 Switching On the UPS 21 4 2 Switching Off the UPS 21 4 3 Plug in Charge 21 4 4 Auto Restart 21 4 5 Alarm Silence 21 4 6 Self Test 21 5 UPS Maintenance 23 5 1 Battery Replacement Precautions 23 5 2 ...

Page 5: ... Used Batteries 25 6 Communication 26 6 1 DB 9 Connector 26 6 2 Options for Intellislot SNMP Card Optional 26 7 Specifications 27 8 Signalling Circuit Connections 31 8 1 Models AILI 750 1000 1500 VA 31 8 2 Models AILI 2200 3000 VA 32 ...

Page 6: ...foreign objects into the UPS will void the warranty The battery will gradually discharge if the system is unused for extended periods If unused recharge the UPS every 2 to 3 months Neglecting to do so will void the warranty The batteries charge automatically and are kept in good condition if the UPS is installed and used A battery can present a risk of electrical shock and high short circuit curre...

Page 7: ...ack up system for critical file servers minicomputers network switches and hubs and many other ap plications The sine wave output is compatible with the requirements of many types of loads A user friendly LCD panel displays the system status including the load level battery level AVR boost buck and fault status 90 efficiency in the normal mode meets high energy saving standard and reduces noise an...

Page 8: ...for reuse or dispose of it properly 2 2 Unpacking 1 Take the UPS out of the foam 2 Remove the packing materials 3 A standard unit includes One 1 user manual One 1 AC input power cord not supplied with hard wired models Two 2 IEC output cables for UPS models with IEC sockets only One 1 RJ11 phone jack cable The accessories shown below for tower and rack mounting ...

Page 9: ...inches of clearance between the rear panel of the UPS and the wall or other obstructions 2 Do not block the air flow to the ventilation openings of the unit 3 Ensure that the environmental conditions of the installation site are within the specified temperature and humidity limits Avoid excessive heat and moisture 4 Do not place the UPS in a dusty or corrosive environment or near any flammable obj...

Page 10: ...wo different orientations tower mount stand alone or rack mount To install the UPS as a tower see next section For rack mount see Section 2 4 2 2 4 1 Tower Mount Stand Alone See Section 2 5 to rotate the LCD display to match the physical orientation of the unit NOTE ...

Page 11: ...9 0170000 J0 Rev B 2 4 2 Rack Mount Setup Step 1 Step 2 See Section 2 5 to rotate the LCD display to match the physical orientation of the unit NOTE ...

Page 12: ...0170000 J0 Rev B 10 Step 3 Step 4 Step 5 ...

Page 13: ... 5 UPS Front Panel The front panel can be rotated to accommodate the orientation of the UPS To position the display to match the physical orientation of the unit pull the display out rotate it and then push it back in NOTE ...

Page 14: ... button 4 Off button 5 Battery replacement 6 Battery backup LED 7 Battery low 8 Bypass 9 Utility low UPS boost 10 Utility high UPS buck 11 UPS output indicator 12 Polarity error or ground fault 13 Overload 14 Load battery level 15 Load battery level indication control button ...

Page 15: ...ata line connectors 2 Voltage configuration switch 3 USB Port 4 RS232 DB 9 port 6 1 NEMA 5 15R output receptacles 7 Cooling vents 8 12 A input circuit breaker 750 and 1000 models 15 A input circuit breaker 1500 model only 9 NEMA 5 15P input power cord 10 REPO Remote Emergency Power Off 11 Intellislot port See Section 6 2 ...

Page 16: ...32 DB 9 port 5 1 15 A output circuit breaker for 6 1 5 2 20 A output circuit breaker for 6 2 6 1 NEMA 5 15R output receptacles 6 2 NEMA 5 20R output receptacles 7 Cooling vents 8 30 A input circuit breaker 9 NEMA 5 20P input power cord 10 REPO Remote Emergency Power Off 11 Intellislot port See Section 6 2 2200 VA 120 V 1920 VA 1920 W for UL models 5 1 ...

Page 17: ...RS232 DB 9 port 5 1 15 A output circuit breaker for 6 1 5 2 20 A output circuit breaker for 6 2 6 1 NEMA 5 15R output receptacles 6 2 NEMA 5 20R output receptacles 6 3 NEMA 5 30R output receptacles 7 Cooling vents 8 30 A input circuit breaker 9 NEMA L5 30P input power cord 10 REPO Remote Emergency Power Off 11 Intellislot port See Section 6 2 5 1 ...

Page 18: ...ge configuration switch 3 USB port 4 RS232 DB 9 port 6 1 IEC 320 C13 output receptacles 7 Cooling vents 8 7 A input circuit breaker 750 model only 8 A input circuit breaker 1000 model only 10 A input circuit breaker 1500 model only 9 IEC 320 C14 input socket 10 REPO Remote Emergency Power Off 11 Intellislot port See Section 6 2 ...

Page 19: ... A output circuit breaker for 6 1 5 2 10 A output circuit breaker for 6 2 6 1 IEC 320 C13 output receptacles 6 2 IEC 320 C13 output receptacles 6 3 IEC 320 C19 output receptacles 7 Cooling vents 8 15 A input circuit breaker 2200 model only 20 A input circuit breaker 3000 model only 9 IEC 320 C20 input socket 10 REPO Remote Emergency Power Off 11 Intellislot port See Section 6 2 ...

Page 20: ... the rear of the UPS To use the UPS as a master on off switch make sure that all of the loads are switched on The UPS outlets provide battery backup and surge protection for the equipment when the utility voltage is out of range For models 2200 1500 1000 and 750 To reduce the risk of fire connect only to a circuit provided with 20 amperes maximum branch circuit overcurrent protection in accor danc...

Page 21: ...puter interface port See the software installation guide in the CD ROM optional 3 3 Connect Network Surge protection Connect a 10 base T 100 base T network cable to the RJ 45 network surge protection IN jack on the rear of the UPS Use a network cable to connect the OUT jack to the network equipment User Software provided under license from Ablerex Electronics Co Ltd ...

Page 22: ...y a means of interfacing with the REPO circuit so that the UPS input feeder breaker can be switched off to interrupt all sources of power to the UPS and connected equipment This must be done to comply with national and local wiring codes and regulations 1 REPO 2 Ground Short Pin 1 and Pin 2 to enable the REPO function 1 2 ...

Page 23: ...toff point reached in the backup mode 3 The UPS automatically switches off the output beeps for 5 seconds then completely switches off 4 3 Plug in Charge 1 If the input power cord is properly connected to the wall receptacle and the utility power is normal the UPS automatically starts charging the batteries without processing the switch on procedure 2 If the UPS isn t used for extended periods cha...

Page 24: ...nput power cord is connected to the wall receptacle CAUTION Plug the UPS into the wall receptacle to charge the UPS for more than 8 hours after the initial installation NOTE If stored at 15 to 30 C 5 to 86 F charge the UPS batteries every three months If stored at 30 to 40 C 86 to 104 F charge the UPS batteries every two months NOTE ...

Page 25: ... 5 2 Battery Replacement Procedure When the UPS is started up or a self test is executed the battery replacement symbol on the LCD panel may appear because of a weak or dead battery 1 If the battery replacement symbol on the LCD panel appears charge the UPS for at least 8 to 10 hours The symbol should disappear after the self test function has executed 2 If the battery replacement symbol stays on ...

Page 26: ...0170000 J0 Rev B 24 5 3 Replacing Batteries STEP 1 STEP 2 STEP 3 750 1000 1500 VA ...

Page 27: ...200 3000 VA 5 4 Recycling Used Batteries Contact your local recycling or hazardous waste center for information on the proper disposal of used batteries Use scissors to cut the tie wraps Disconnect the cables Remove the batteries ...

Page 28: ...tion 6 1 DB 9 Connector The UPS has a DB 9 9 pin female connector on the rear panel that allows the UPS to communicate with a computer with UPS software The connection provides serial communications for utility and battery signals 6 2 Options for Intellislot SNMP Card Optional When this card is plugged in it enables the user to communicate monitor manage and control the UPS remotely via simple net...

Page 29: ...utput receptacles 8 NEMA 5 15R 6 NEMA 5 15R 2 NEMA 5 20R 6 NEMA 5 15R 2 NEMA 5 20R 1 NEMA L5 30R Voltage normal mode 110 120 127 VAC configurable 10 Voltage battery mode 110 120 127 VAC configurable Transfer time 4 to 6 ms typical Waveform Sine wave Frequency normal mode 45 to 65 Hz 0 5 Hz Frequency battery mode 50 60 Hz 0 5 Hz auto sensing Overload Warning Normal mode 100 to 109 Continuous overlo...

Page 30: ... Up to 10 000 ft 3000 m at 95 F 35 C without derating Audible noise 40 dBA internal fan s off 45 dBA internal fan s on Agency Safety UL 1778 c UL listed Surge ANSI C62 41 CatA Lev3 surges IEC61000 4 5 ESD IEC61000 4 2 Susceptibility IEC61000 4 3 Electrical fast transient IEC61000 4 4 Emissions FCC Part 15 Class A Conducted immunity EN61000 4 6 Harmonics EN61000 3 2 Network surge UL 497 B Transport...

Page 31: ...0 IEC 320 C20 Output receptacles 8 IEC 320 C13 8 IEC 320 C13 8 IEC 320 C13 1 IEC 320 C19 8 IEC 320 C13 1 IEC 320 C19 Voltage normal mode 220 230 240 VAC configurable 10 Voltage battery mode 220 230 240 VAC configurable 5 before low battery warning Transfer time 4 6 ms typical Waveform Sine wave Frequency normal mode 45 to 65 Hz 0 5 Hz Frequency battery mode 50 60 Hz 0 5 Hz auto sensing Overload Wa...

Page 32: ...e Up to 10 000 ft 3000 m at 95 F 35 C without derating Audible noise 40 dBA internal fan s off 45 dBA internal fan s on Agency Safety CE IEC61000 4 5 Surge IEC61000 4 2 ESD IEC61000 4 3 Susceptibility IEC61000 4 4 Electrical fast transient IEC EN AS 62040 2 2nd Ed class A Emissions EN61000 4 6 Conducted immunity EN61000 3 2 Harmonics IEC61000 4 5 Transportation ISTA procedure 1A certification ...

Page 33: ...LI 750 1000 1500 VA CPU To PC RS232 Port USB Port SNMP Port I board Fan Driver Circuit M board LCD Display D board Battery Inverter Charger Main Transformer Filter Relay Switch Outlet Line Input K board Input Voltage Sensor Output Output Voltage Current Sensor Sensor ...

Page 34: ...A CPU To PC RS232 Port USB Port SNMP Port I board Fan Driver Circuit M board LCD Display D board Battery Inverter Charger Main Transformer Filter Relay Switch Outlet Line Input F board Input Voltage Sensor Output Output Voltage Current Sensor Sensor ...

Page 35: ......

Page 36: ...D 91126 Schwabach Germany Tel 49 9122 79889 0 Fax 49 9122 79889 21 Technologies Argus First de Mexico Anatole France Num 17 Colonia Polanco 11560 México D F Tel 52 55 5280 6990 Alpha Technologies Europe Ltd Twyford House Thorley Bishop s Stortford Hertfordshire CM22 7PA United Kingdom Tel 44 1279 501110 Fax 44 1279 659870 Alphatec Ltd 339 St Andrews St Suite 101 Andrea Chambers P O Box 56468 3307 ...