background image

Rev. 090710

More than just power.

TM

Rack Mount Power Supplies

Installation Guide

Models Include:

Vertiline3D

  -  12VDC @ 8A
  -  Eight (8) PTC protected outputs

Vertiline6D

  -  24VDC @ 8A
  -  Eight (8) PTC protected outputs

Summary of Contents for VERTILINE Series

Page 1: ...Rev 090710 More than just power TM Rack Mount Power Supplies Installation Guide Models Include Vertiline3D 12VDC 8A Eight 8 PTC protected outputs Vertiline6D 24VDC 8A Eight 8 PTC protected outputs ...

Page 2: ...t 8 power LED indicators Illuminated master power disconnect circuit breaker with manual reset IEC 320 3 wire grounded line cord detachable Removable terminal blocks with locking screw flange Mechanical Units can be rack wall or shelf mounted Modular 1U standard EIA 19 rack mount chassis Enclosure Dimensions H x W x D approx 1 625 x 19 125 x 8 5 41 3mm x 486mm x 216mm Eight 8 Output Rack Mount Con...

Page 3: ...ower disconnect circuit breaker to the OFF position Fig 1c pg 4 8 Connect the power output of terminals marked 1 to the power input of device Fig 1b pg 4 Repeat this step for each additional device Outputs 2 8 9 Upon completion of wiring set illuminated master power disconnect circuit breaker to the ON RESET position Fig 1c pg 4 10 The power LEDs on the faceplate for Outputs 1 8 will illuminate wh...

Page 4: ...nnect circuit breaker switch OFF position Circuit breaker tripped Switch not illuminated RESET ON position Switch illuminated 1d IEC 320 Connector 115VAC 60Hz grounded line cord included 1e Removable Terminal Block Fig 1 Vertiline3D and Vertiline6D front Vertiline3D and Vertiline6D rear 1a 1b 1c 1d 1e Removable Terminal Block ...

Page 5: ...Vertiline3D VertiLine6D 5 Fig 2 Typical Application Drawing 12VDC VertiLine3D or 24VDC VertiLine6D Power Outputs to Devices ...

Page 6: ...reduce the risk of electric shock do not open enclosure There are no user serviceable parts inside Refer servicing to qualified service personnel Fig 3 Power switch with built in circuit breaker OFF position Switch not illuminated Outputs not powered RESET ON position Switch illuminated Outputs powered Circuit breaker tripped Switch not illuminated Power LEDs on faceplate are not illuminated Outpu...

Page 7: ...ve Wall Mount Installation 1 Install mounting brackets A on the left and right side of rack chassis using two 2 flat head screws B included Fig 5a 2 Place unit at desired location and secure with mounting screws not included Fig 5b Caution It is necessary to make sure mounting screws are securely fastened to a beam when installing Fig 5 A B Fig 5b Fig 5a Fig 6 Shelf Installation 1 Position and aff...

Page 8: ...esponsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIVertiline3D Vertiline6D G23R MEMBER Notes ...