4Q SCR Chassis Microprocessor-based
Adjustable Speed Drive with Speed
or Torque Mode for PMDC Brushed Motors
MGB400
An ISO 9001:2008 Certified Company
TM
......................................................115/230 VAC ± 10%, 50/60 Hz, single phase
........................................................................................................0 - 15 Amps
...................................................................................................1.37 at base speed
..................................................................................................1% base speed
.........................................................................................................................50:1
......................................................................................0.25 seconds
......................................................................................0.25 seconds
.........................................0 to ± 10 VDC
...............................................................................>100K ohms
............................................................................................0.5G maximum
...............................................................................................0.1G maximum
.......................................................................10°C - 50°C
.............................................................................................................0.62 lbs (0.28 kg)
......................................cULus Recognized, UL 61800-5-1, File # E132235
AC Line Voltage
AC Line Current
Form Factor
Load Regula
on
Speed Range
Accelera
on Time Range
Decelera
on Time Range
Analog Input Voltage Range
(Signal must be isolated)
Input Impedance (COM to SIG)
Vibra
on
(0 - 50 Hz)
(>50 Hz)
Surrounding Air Temperature Range
Weight
Safety Cer
fica
ons
* Heat sink kit 223-0159 must be used when the output is over 8 amps.
1/50 - 1/8
1/25 - 1/4
1/8 - 1
1/4 - 2
Armature
Horsepower
Range
1.5
11.0*
Armature
Current (Amps)
0 - 90
0 - 180
0 - 90
0 - 180
Armature
Voltage Range
(VDC)
115
230
115
230
Line
Voltage
(VAC)
MGB400-1.5
MGB400-11
Model
Specifications
WARNING:
The circuits connected to terminals COM, AX1, AX2, SIG, and +V are NOT isolated from
power circuits by Protec
ve Separa
on in accordance with UL 61800-5-1. Protec
ve separa
on to
protect these circuits against direct contact is to be supplied by the end user.
•
DO NOT INSTALL, REMOVE, OR REWIRE THIS EQUIPMENT WITH POWER APPLIED.
Have a
•
qualified electrical technician install, adjust and service this equipment. Follow the Na
onal
•
Electrical Code and all other applicable electrical and safety codes, including the provisions of the
•
Occupa
onal Safety and Health Act (OSHA), when installing equipment.
•
Circuit poten
als are at 115 or 230 VAC above earth ground
. Avoid direct contact with the printed
•
circuit board or with circuit elements to prevent the risk of serious injury or fatality. Use a non-
•
metallic screwdriver for adjus
ng the calibra
on trim pots. Use approved personal protec
on
•
equipment and insulated tools if working on this drive with power applied.
• Reduce the chance of an electrical fire, shock, or explosion by using proper grounding, over-current
•
protec
on, thermal protec
on, and enclosure. Follow sound maintenance procedures.
•
ACE strongly recommends the installa
on of a master power switch in the line voltage input.
The
•
switch contacts should be rated for 250 VAC and 200% of motor nameplate current.
•
Removing AC line power is the only acceptable method for emergency stopping.
Do not use
•
regenera
ve braking, decelera
ng to minimum speed, or coas
ng to a stop for emergency stopping.
•
They may not stop a drive that is malfunc
oning. Removing AC line power is the only acceptable
•
method for emergency stopping.
• Line star
ng and stopping (applying and removing AC line voltage) is recommended for infrequent
•
star
ng and stopping of a drive only. Regenera
ve braking, decelera
ng to minimum speed, or
•
coas
ng to a stop is recommended for frequent starts and stops. Frequent star
ng and stopping can
•
produce high torque. This may cause damage to motors.
•
Do not disconnect any of the motor leads from the drive
unless power is removed or the drive is
•
disabled. Opening any one lead while the drive is running may destroy the drive.
• Under no circumstances should power and logic level wires be bundled together.
• Be sure poten
ometer tabs do no make contact with the poten
ometer’s body. Grounding the
•
input will cause damage to the drive.
• This product does not contain speed sensi
ve overload protec
on, thermal memory reten
on, or
•
provisions to receive and act upon signals from remote devices for over temperature protec
on. If
•
motor protec
on is needed in the end-use product, it needs to be provided by addi
onal equipment
•
in accordance with NEC standards.
• This product does not have internal solid state motor overload protec
on. It does not contain speed-
•
sensi
ve overload protec
on, thermal memory reten
on, or provisions to receive and act upon
•
signals from remote devices for over temperature protec
on. If motor protec
on is needed in the
•
end-use product, it needs to be provided by addi
onal equipment in accordance with NEC standards.
READ ALL SAFETY WARNINGS BEFORE INSTALLING THIS EQUIPMENT
Safety Warnings
ALL DIMENSIONS IN INCHES [MILLIMETERS]
3.64 [93]
3.00 [76]
1.25 [32]
0.50 [13]
3.80 [97]
4.30 [110]
1.34 [34]
0.95 [24]
Dimensions
SCCR (Short Circuit Current Ra
ng):
MGB400 series drives are suitable for use on a circuit capable of
delivering not more than 5,000 RMS symmetrical amperes, 115/230 volts maximum.
Branch Circuit Protec
on:
Class J, Class CC, or Class T fuses are to be rated with a minimum of 230 VAC
and a maximum current ra
ng of 40 amps. Circuit breakers are to be rated at a minimum of 230 VAC
with a maximum current ra
ng of 30 amps.
Moun
ng
•
Install the drive in a Pollu
on Degree 2 environment only.
• Drive components are sensi
ve to electrosta
c discharge. Avoid direct contact with the circuit
•
board. Hold the drive by the chassis only.
• Protect the drive from dirt, moisture, and accidental contact.
• Provide sufficient room for access to the terminal block and calibra
on trim pots.
• Mount the drive away from heat sources. Operate the drive within the specified ambient opera
ng
•
temperature range.
• Prevent loose connec
ons by avoiding excessive vibra
on of the drive.
• Mount the drive with its board in either a horizontal or ver
cal plane. Eight 0.19” (5 mm) wide slots
•
in the chassis accept #8 pan head screws. Fasten either the large base or the narrow flange of the
•
chassis to the subplate.
• The chassis should be earth grounded. Connect the ground to the green screw on the chassis.
Heat Sinking:
The MGB400-11 requires an addi
onal heat sink when the con
nuous armature current
is above 8 amps. Use heat sink kit part number 223-0159. Use a thermally conduc
ve heat sink
compound (such as Dow Corning 340® Heat Sink Compound) between the chassis and the heat sink
surface for op
mal heat transfer.
Wiring:
60°C wire was used in UL evalua
on of the power wiring terminals (L1, L2, A1, A2). Use
18 - 24 AWG wire for logic wiring. Use 14 AWG wire for AC line (L1, L2) and motor (A1, A2) wiring.
Shielding Guidelines:
As a general rule, it is recommended to shield all conductors. If it is not prac
cal
to shield power conductors, it is recommended to shield all logic-level leads. If shielding of logic-level
leads is not prac
cal, the user should twist all logic leads with themselves to minimize induced noise.
Refer to the user’s manual for details on earth grounding shielded wires and filtering.
Installation
DIRECTION
SWITCH
STOP
SWITCH
AC LINE
VOLTAGE
115 / 230 VAC
10K OHM
SPEED ADJUST
POTENTIOMETER
CW
ENABLE / INHIBIT
SWITCH
MOTOR
Speed Poten
ometer
Use a 10K ohm, 1/4 W poten
ometer for speed control. Connect the counter-clockwise end of the
poten
ometer to COM, wiper to SIG, and the clockwise end to +V. If the poten
ometer works
inveresly of desired func
onality, (i.e. to increase motor speed, you must turn the poten
ometer
counterclockwire), power off the drive and swap the COM and +V connec
ons. To use an isolated
analog signal instead, connect the signal nega
ve (-) to COM and the signal reference (+) to SIG.
Direc
on (AX1)
Short terminals AX1 and COM to change the direc
on of The motor. If no direc
on switch is desired,
leave this connec
on open.
Inhibit / Enable (AX2)
Short terminals AX2 and COM to stop the motor. Refer to jumpers 2 and 3 in the Startup sec
on to
determine if the switch is normally open or normally closed, and if the motor will regenera
vely brake
or coast to a stop.
Do not use the inhibit or enable for emergency stopping.
Warning:
The circuits connected to terminals AX1, AX2, COM, SIG, and +V are not isolated from the
power circuits by Protec
ve Separa
on in accordance with UL 61800-5-1. Protec
ve separa
on to
protect these circuits against direct contact is to be supplied by the end user.
Line Input
Connect the AC line power leads to terminals L1 and L2, or to a double-pole, single-throw master
power switch (recommended). The switch should be rated at a minimum of 250 VAC and 200% of
motor current.
Motor
Connect the DC armature leads to terminals A1 and A2. If the motor does not spin in the desired
direc
on, power down the drive and reverse these connec
ons.
LOGIC
POWER
Connections
Email distribuidores: acotron@acotron.com
Calz. Federalismo Sur 214, Col. Centro,
C.P. 44100, Guadalajara, Jalisco.
Tel Oficina Central: 33- 3826-7004
www.acotron.com