background image

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

IMPORTANT —

This Document is 

customer property

 and is to remain with this unit. Please return to service information

pack upon completion of work.

 

HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING

WARNING:

Installer’s Guide

A. GENERAL INFORMATION

WARNING

!

THIS INFORMATION IS FOR USE BY INDIVIDUALS
HAVING  ADEQUATE BACKGROUNDS OF ELECTRICAL
AND MECHANICAL EXPERIENCE. ANY ATTEMPT TO
REPAIR A CENTRAL AIR CONDITIONING PRODUCT
MAY RESULT IN PERSONAL INJURY AND/OR PROP-
ERTY DAMAGE. THE MANUFACTURER OR SELLER
CANNOT BE RESPONSIBLE FOR THE INTERPRETA-
TION OF THIS INFORMATION, NOR CAN IT ASSUME
ANY LIABILITY IN CONNECTION WITH ITS USE.

CAUTION

!

To prevent shortening its service life, the air handler
should not be used during the finishing phases of con-
struction. The low return air temperatures can lead to
the formation of condensate. Condensate in the pres-
ence of chlorides and fluorides from paint, varnish,
stains, adhesives, cleaning compounds, and cement
creates a corrosive condition which may cause rapid
deterioration of the cabinet and internal components.

This unit is equipped with an integrated high efficiency
Whole House Air Cleaner. Careful consideration must
be taken in the installation process to avoid personal in-
jury or equipment damage. These instructions do not
cover all variations in systems or provide for every pos-
sible contingency. Should further information be desired
or particular problems arise which are not covered suffi-
ciently by this manual, contact your local distributor or
the manufacturer as listed on the air handler name-
plate.
These Air Handlers are shipped from the factory in the
upflow or horizontal right configuration and are fully
convertible to downflow or horizontal left. Refer to Sec-
tion C beginning on page 4  for additional information.

INSPECTION

Check carefully for any shipping damage. This must be
reported to and claims made against the transportation
company immediately. Check to be sure all major com-
ponents are in the unit. Any missing parts should be re-
ported to your supplier at once, and replaced with au-
thorized parts only.

Convertible Variable Speed –  

Air Handlers 2 1/2 - 5 Ton

with Integrated Whole House Air Cleaner

2/4TEE3D31A1000A, 2/4TEE3D37A1000A, 2/4TEE3D40A1000A,
2/4TEE3D49A1000A, 2/4TEE3D65A1000A

CONTENTS

General Information .............................................. 1

Installation Limitations & Recommendations ...................... 1

Two Piece Cabinet Disassembly ........................ 4

Unit Installation ...................................................... 4

Vertical Upflow ....................................................................... 4
Vertical Downflow ................................................................... 5
Horizontal Left ........................................................................ 9
Horizontal Right ................................................................... 10

Duct Connection ................................................... 10

Refrigerant Piping ............................................... 13

Brazing to Evaporator Section ......................... 13

Condensate Drain Piping .................................... 13

Electrical - Wiring ................................................. 14

Airflow Adjustment ............................................... 15

Maintenance Check Out Procedure ................ 16

Cleaning the COLLECTION CELL .................. 16

Cleaning the FIELD CHARGER ........................ 17

Hook Up Diagrams ............................................... 18

Outline Drawings ................................................. 20

Checkout Procedures .......................................... 23

INSTALLATION LIMITATIONS & RECOMMENDATIONS

The general location of the air handler is normally se-
lected by the architect, contractor and/or home owner
for the most effective application and satisfaction.

NOTE: Condensation may occur on the surface of the
air handler when installed in an unconditioned loca-
tion. When units are installed in unconditioned spaces,
verify that all electrical and refrigerant line penetrations
on the air handler are sealed completely.

18-GE10D1-5

Summary of Contents for 2TEE3D31A1000A

Page 1: ...r local distributor or the manufacturer as listed on the air handler name plate These Air Handlers are shipped from the factory in the upflow or horizontal right configuration and are fully convertibl...

Page 2: ...rs are suitable for installation in a closet alcove or utility room with free non ducted air return using the area space as a return air plenum With ducted supply air if the minimum clearances to comb...

Page 3: ...d to and claims made against the transporta tion company immediately Check to be sure all major components are in the unit Any missing parts should be reported to your supplier at once and replaced wi...

Page 4: ...that do not have a grill or return air duct installation will re quire the use of either BAYPLNM120 TASB215 TASB235 or TASB260 depending on cabinet size TASB accessories can be purchaed from Miami Tec...

Page 5: ...flow Ionizing pins must face downward into the return air stream and electrical contacts must be on the left side of the unit n Reinstall FIELD CHARGER retainer bracket o Install COLLECTION CELL as sh...

Page 6: ...GE10D1 5 Installer s Guide Figure 8 FIELD CHARGER Removal Figure 6 COLLECTION CELL Removal Figure 7 FIELD CHARGER Retainer Bracket Removal Figure 10 Drip Pan Foam Removal Figure 9 Protector Plate Rem...

Page 7: ...e of the drain pan See Figure 14 Fill the bend in the baffle which fits the in ner edge of the drain pan with non acetic acid RTV type adhesive sealant before installing the baffle Ensure sealant is d...

Page 8: ...cal contacts and ac tuator tab are on the right side of the unit t Install filter panel with thumbscrews u Openings where field wiring enters the cabinet must be completely sealed Location of power en...

Page 9: ...15 CAUTION When installing the narrow coil baffle make sure to align the baffle up with the holes so NOT to puncture the coil tubing f The coil is then inserted back into the cabinet on the opposite...

Page 10: ...he front of the unit to re move d Unit is shipped from the factory in the upflow or horizontal right configuration Unit conversion is not required e If the unit is suspended it must be supported from...

Page 11: ...NFLOW UPFLOW Actuator Tab Actuator Tab Electrical Contacts Electrical Contacts Electrical Contacts Electrical Contacts FIELD CHARGER COLLECTION CELL FIELD CHARGER COLLECTION CELL Figure 18 COLLECTION...

Page 12: ...ttom side Electrical Contacts on Bottom side Electrical Contacts on Bottom side FIELD CHARGER COLLECTION CELL FIELD CHARGER COLLECTION CELL HORIZONTAL RIGHT Actuator Tab Electrical Contacts Electrical...

Page 13: ...e made outside the cabinet NOTE TXV bulb MUST be protected wrap a wet rag around the suction line between the TXV bulb and the braze joint or removed while brazing the tubing Over heating of the sensi...

Page 14: ...t a clean out tee or cross be installed in the primary drain line for future main tenance See Figures 22 23 4 Do not use reducing fittings in the condensate drain lines 5 Slope the drain lines downwar...

Page 15: ...onnectors are provided for use with supplementary heaters IMPORTANT When supplementary heaters are installed inspect to insure that all packaging material has been removed J AIRFLOW ADJUSTMENT CAUTION...

Page 16: ...shock do not perform any servicing other than that contained in these operating instructions unless you are qualified to do so NOTE System Information Before cleaning the coil or ducts in the air hand...

Page 17: ...Push a block of foam down over the FIELD CHARGER Pin as in Figure 28 6 Rotate the foam block on the FIELD CHARGER Pin See Figure 29 7 Use the foam block to clean the faceplate opening edges 8 Repeat...

Page 18: ...R HANDLER AIR HANDLER 2 STAGE 2 STAGE AIR CONDITIONER AIR CONDITIONER COMFORT CONTROL COMFORT CONTROL 2 STAGE HEAT 2 STAGE HEAT 1 STAGE COOL 1 STAGE COOL VARIABLE SPEED VARIABLE SPEED AIR HANDLER AIR...

Page 19: ...ORT COMFORT CONTROL CONTROL VARIABLE SPEED VARIABLE SPEED AIR HANDLER AIR HANDLER HEAT PUMP HEAT PUMP O D SECTION O D SECTION SINGLE SPEED SINGLE SPEED 2 4TEE3D31 37 40 49 65A AIR HANDLERS WITH SINGLE...

Page 20: ...20 18 GE10D1 5 Installer s Guide OUTLINE DRAWING FOR 2 4TEE3D31 37 40 49 65A1000A From Dwg D802101 Rev 5...

Page 21: ...Installer s Guide H W 21 0 2 4TEE3D31 37 40 49 65A AIR HANDLER DIMENSIONAL DATA Model No H W 2 4TEE3D31A 43 00 21 50 2 4TEE3D37A 45 00 23 50 2 4TEE3D40A 51 75 26 00 2 4TEE3D49A 57 90 26 00 2 4TEE3D65...

Page 22: ...22 18 GE10D1 5 Installer s Guide EXPLODED VIEW From Dwg D802038g05 Rev 11...

Page 23: ...ly for correct requirements per unit nameplate 8 Inform owner of proper procedure for cleaning COLLECTION CELL 9 Energize the system and carefully observe its opera tion make any necessary adjustment...

Page 24: ...TX 75707 For more information contact your local dealer distributor 02 08 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design an...

Reviews: