background image

ARCHON Industries, Inc. 

 

Model EX99-LED Explosion Proof 

Luminaire - 

Instruction No. 1015-2 June 2019

 

 

Installation / Operating / Maintenance 

Instructions 

 

1. 

Suitability

 

1.1 

This luminaire  is suitable, when installed and 

operated in accordance with these instructions, 

for use in the following locations as defined by 

the National Electrical Code: 

 

Class  Division   Groups 

   I 

   1 

    C and D 

   I 

   2 

    C and D 

 

1.2 

This luminaire  is rated for Temperature Code 

T6  for  a  maximum  ambient temperature of 

40°C. 

1.3 

Input: 120-277 VAC / 14.7 W / 50-60 Hz.  

 

2. 

Installation 

2.1 

Install and use in accordance with all 

applicable electrical and fire safety codes. 

2.2 

Ensure electrical service leads are properly 

protected against mechanical damage. 

2.3 

CAUTION:

  To reduce the risk of fire or 

explosion, do not install where the marked 

operating temperature exceeds the ignition 

temperature of the hazardous atmosphere. 

2.4 

CAUTION: 

Mount this luminaire  at any angle 

between the glass lens facing down and the 

glass  lens facing horizontally.  Do not mount 

this luminaire with the lens facing at any angle 

above the horizontal.  See figure 1. 

 

 

 Figure 1 – Operating Position  

 

 

 

2.5 

CAUTION:

 Use wires rated for 105°C minimum 

for supply connections. 

 

3. 

Operation 

3.1 

CAUTION:

  To reduce the risk of ignition of 

hazardous atmospheres, disconnect the 

luminaire from the electrical supply circuit before 

opening any of the covers.  

3.2 

Do not energize luminaire if the glass lens is 

cracked or  broken, or if the lens cap  is not 

screwed on tightly.   

3.3 

Ensure that the lens is securely held  in the 

luminaire before energizing the electrical supply 

circuit.  The lens should not be free to move 

when properly installed.  The lens cap must be 

fully tightened onto the body to properly secure 

the lens. 

3.4 

Ensure that all covers are tightly closed when 

the luminaire is in operation. 

 

4. 

Driver Removal and Installation 
Removal 

4.1 

The LED  driver can be accessed and removed 

from the rear of the unit as follows. 

4.2 

Remove the rear cover and slide the LED driver 

out of the LED heatsink. 

4.3 

With the driver removed, disconnect the input 

and output connectors to the driver. 

Installation 

4.4 

Connect the input and output leads of the new 

driver to the appropriate connectors making sure 

that the new driver  is  of the same type and 

rating as provided by ARCHON. 

To reduce the 

risk of inverting driver wiring, the input  and 

output connectors are not identical.

 

4.5 

With the wire bundle carefully packaged and 

secured to the driver using the recommended 

wire tie, carefully place back into the LED 

heatsink. 

See figure 3 for illustration.

 

4.6 

Install the rear cover and test the luminaire with 

the appropriate AC input voltage. 

 

5. 

Removal of LED Assembly 

5.1 

The LED assembly is provided as a single unit 

which includes LED heatsink, light source (COB 

LED), reflector assembly, LED driver and wiring. 

5.2 

First unscrew the rear cover and disconnect the 

AC leads from the LED driver.  These leads are 

black and white with an orange connector. 

5.3 

Although not required, if necessary, the cable 

entry gland  located in the wiring compartment 

can be removed by unscrewing it from the body. 

5.4 

With the AC wires disconnected,  remove the 

front lens cap and slide the  full  LED assembly 

directly out the front of the unit. 

5.5 

To install a new LED assembly, proceed to 

section 6 of this document. 

Reviews: