COMPATIBILITY

 

This acoustic device is only compatible with conventional control panels and systems, unless an approved optional module is fitted. For more 
specific information regarding compatibility refer to your fire security system supplier and the technical documentation concerning the control 
panel in use. 

INSTALLATION - IMPORTANT NOTES

 

Refer to national and international standards in use for spacing and positioning of the fire security’s system devices; refer also to specific 
standards and your supplier if the system is going to be installed in particular environments or environments where specific risks exist. 

This device is to be used only with conventional control panels and systems (check the COMPATIBILITY paragraph). 

This device must be wired according to the connection details described in this manual. 

Disconnect the sounder line from the control panel before installing this device. 

Test the device after installation. 

SOUNDER OPENING PROCEDURE

 

In order to detach the upper sounder body from the base: 

1)  Insert the pins of the compatible key into the holes of one of the two side locking mechanisms. 

2)  Turn the key 90° to the left whilst applying light pressure. 

3)  Repeat this step for the second side locking mechanism; the locking mechanism appears as in picture 1 when 
in the open position (flush). 

4)  Detach the sounder body from the base by pulling gently to separate (picture 3). 

SOUNDER CLOSING PROCEDURE

 

In order to assemble the sounder body to the base: 

1)  Assemble the sounder body to the base using gentle pressure (picture 3). 

2)  Insert the pins of the compatible key into the holes of one of the two side locking mechanisms. 

3)  Turn the key 90° to the right. 

4)  Repeat this step for the second side locking mechanism, starting from point 2; the locking  mechanism ap-
pears as in picture 2 once closed (recessed). 

5)  To secure use the retaining screws, using the location holes on both sides of the base (picture 4). 

Picture 1 

Picture 2 

ARGUS SECURITY S.R.L.

 - Via del Canneto, 14 - 34015 - Muggia (TS) - Italy 

www.argussecurity.it 

CWS100-AV 

CONVENTIONAL WALL S VISUAL ALARM DEVICE 

Picture 3 

928y/01  

Picture 4 

 
 
 
 
 

OUTDOORS AND DAMP ENVIRONMENTS INSTALLATION 

 
When installing the sounder outdoors or in a damp environment, carefully apply the self-adhesive 
sealing pad to the back of the sounder base (picture 5). 

 
 
 

WALL INSTALLATION

 

1)  Choose the installation location for the sounder based upon system design regulations. 

2)  Fix the sounder base to the wall; the prepared location options for the fixing screws are highlighted in picture 6. 

CABLE ENTRIES

 

The sounder base is provided with a knockout entry for the system cables, located in the centre of the base (picture 7). 

The side wall of the base has prepared drilling points to allow for installation of cable glands; a row of three drilling points are provided to allow 
for single or twin cable connection (picture 8). 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

TERMINAL BLOCKS INSTALLATION 

 
The terminal block on the back of the sounder body is installed as illustrated in picture 9. 

info@argussecurity.it 

L20-CWSVX-0001 (vA.

3

LL 

Picture 6 

Picture 7 

Picture 8 

Picture 9 

Picture 5 

EN 54-3 

Type B - 

approved for 

outdoor use.  

WIRING 

 
Connect the sounder to the sounder circuit from the control panel; wiring terminal connections are as illustrated in picture 10 and described in 
table 1; an example of a typical circuit wiring arrangement is shown in picture 11. 
 
 
 
 
 
 
 
 

ARGUS SECURITY S.R.L.

 - Via del Canneto, 14 - 34015 - Muggia (TS) - Italy 

www.argussecurity.it 

P

o

s

 

T

o

n

A

lt

 

Picture 10 

Table 1 

Terminal block number 

Terminal block designation 

Notes 

Usage 

Pos 

Terminal blocks for the line’s positive terminals 
(+). These block are shorted: either one can be 
used. 

Connect to the positive terminals of the 
control panel’s sounder circuit. 

Tone 

Terminal blocks for the line’s negative terminals 
(-). These block are shorted: either one can be 
used. 

Connect to the negative terminals of 
the control panel’s sounder circuit. 
Wiring to these terminal blocks acti-

Alt 

Terminal blocks for the line’s negative terminals 
(-). These block are shorted: either one can be 
used. 

Connect to the negative terminals of 
the control panel’s sounder circuit. 
Wiring to these terminal blocks acti-

Sounder line (+) 

Sounder line (-) 

Picture 11 

Use of the Tone or Alt terminals enable, respectively, the main tone set or the alternate one; refer to the MAIN TONE SET 
and the ALTERNATE TONE SET paragraphs.  

The sounder line must 
be capable of providing 
a surge/power-up cur-
rent of at least 2 times 

the sum of the indicated current 
of all the AV devices on the line 
itself. 
 
The sounder line must be capable 
of providing a steady state cur-
rent of at least 1.5 times the sum 
of the alarm currents of all the AV 
devices on the line itself. 

OUTPUT TONE SETTING 

 
Use the DIP switch on the back of the sounder body to select the tone required; for this function the first five switches are used, highlighted in 
picture 12. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

The switches positioned upwards acquire value “1”; on the other hand, if positioned downwards acquire value “0”. 
 
1)  From the MAIN TONE SET table or the ALTERNATE TONE SET table (the choice of the table depends on how the sounder’s wiring has 
 

been carried out) select the output alarm tone triggered when the sounder is activated. 

2)  Refer to the corresponding line of the “DIP configuration” column to select the five switch selection settings. 

 

OUTPUT VOLUME SETTING 

 
Use the DIP switch at the back of the sounder body to select the output volume; in particular, switches 6 and 7, highlighted in picture 13, are 
used. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
The switches positioned upwards acquire value “1”; on the other hand, if positioned downwards acquire value “0”. 
 
1)  Select the alarm volume required when the sounder is activated (table 2). 
 
2)  Refer to the corresponding line of the “DIP configuration” column to set the two volume selection switches. 

Picture 12 

Picture 13 

info@argussecurity.it 

L20-CWSVX-0001 (vA.

3

LL 

Tone volume 

DIP configuration - switch 6 and 7 

dB(A) evaluation 

Notes 

HIGH 

11

 

100 dB(A) +/- 3

 

All tones

 

MEDIUM HIGH 

01

 

 

 

MEDIUM LOW 

10

 

 

 

LOW 

00

 

 

 

Table 2 