Quick setup manual
Note: For detailed parameter explanation, please refer to the full manual.
Group P0
:
P0.00=0 (V/F control mode, PA group does not need to be set), =1 (Senseless vector control, you need to set the
motor parameter group PA)
P0.01=_ channel selection of frequency given.
0
:
Analog potentiometer on control panel(single display valid)
1
:
▲
、
▼key on control panel (single display valid) Panel digital potentiometer + ▲
、
▼key on control
panel(double display valid)
2
:
Digital setting 1, control panel given
3
:
Digital setting 2, UP/DOWN terminal given
4
:
Digital setting 3, serial port given
5
:
VI analog given (VI-GND)
6
:
CI analog given (CI-GND)
7
:
Pulse terminal given (PULSE)
8
:
Combination given (refer to P3.00)
P0.02=_ _Running frequency set
,
P0.20 lower limit freq.~P0.19upper limit freq.
P0.03=_Running command mode selection
0
:
Control panel mode
1
:
Terminal control mode
2
:
Serial port control mode
P0.04=00 Running direction setting
P0.06=_ _ Max output freq.
P0.07=_ _ Basic running freq.
P0.08= _ _ Max output voltage, rated voltage.
P0.19=_ _ Upper limit freq. , Lower limit freq.
~
Max output freq. P0.06
P0.20=_ _ Lower limit freq.
Group P9
:
P9.13
This parameter does not need to be set when the VFD is a single channel display.
When the VFD is dual channel display.
P9.13=0000
,
Ordinary three-phase asynchronous motor
P9.13=1000
,
Single-phase asynchronous motor (removing capacitor)
P9.13=2000
,
Single-phase asynchronous motor (without removing the capacitor)
Group PA (When P0.00=1)
:
PA.01=_ _
(
Motor rated voltage
)
PA.02=_ _
(
Motor rated current
)
PA.03=_ _
(
Motor rated frequency
)
PA.04=_ _
(
Motor rated rotating speed
)
PA.05=_ _
(
Motor poles number 2, 4, 6
)
,
1